Ref. 006001001300
Rev. 0: 30-08-2019
10.
Hardware Serial RS-232 & RS-485 Configuration
10.1
Hardware Serial RS-485
Switch configuration:
Jumper configuration:
Having configured GPRS Ardbox Relay HF as it is shown above, these are the features that are
available:
o
Available communication protocols:
Hardware Serial RS-485.
I2C
*If I2C is active I0.0 & Q0.6 are disabled
SPI
TTL
USB
o
Inputs: 8 out of 10 inputs, I0.0, I0.1 and 10.4 to I0.9. If using I2C I0.0 is also disabled
o
Digital Outputs: All 10 outputs. If using I2C Q0.6 is disabled.
o
Analog Outputs: From A0.0 to A0.6. If using I2C A0.6 is disabled
In order to enable the Hardware Serial RS-485 the total configuration of the GPRS Ardbox
Relay HF will be:
LEFT ZONE
SWITCH
MODE
DE-RS485
ON
D10/A0.2-Q0.2
OFF
RE-RS485
ON
D11/A0.1-Q0.1
OFF
SDA-D2/I0.0
-
SCL-D3/Q0.6
-
TOP ZONE
SWITCH
MODE
I0.3
OFF
RS485 HS
ON
I0.2
OFF
RS485 HS
ON
JUMPER ZONE 1
LEFT
RIGHT
RS-485
RS-485
D0
D1
-
-
JUMPER ZONE 2
LEFT
RIGHT
I0.2
I0.3
D4
D8
-
-