7.Appendix

7.Appendix1. Use for overheating protector

     Overheating protector is used to prevent safety accident caused by water temperature inside the 

tank too high in case that the heat pump controller is out of control. When the temperature inside the 

tank reaches the action value of the protector, the power supply will be cut off. It has to be reset 

manually so that the unit returns to normal. The operation in detail is as following: 

Press the red button to reset

Protection cover of the protector

Be careful of electric shock when you press red button.

Warning

6.2  Trouble Shooting

 For any malfunctions, please refer to the table below :

P01

Top tank water 
temp. Failure

P02

Coil temp. Failure

P04

P05

P07

E01

E02

E03

E04

E07

E08

E09

Ambient
temp. Failure

Refrigerant absorb 
temp. Failure

High pressure protection

Low pressure protection

Water flow failure

Electric-heater
overheat protection

Anti-freeze protection

Communication failure

Winter frost protection

P09

Anti-freeze temp. Failure

Bottom water 
temp. Failure

Malfunction

Display

Canse

Solution

The water b

 temp. Sensor 

is open or short circuit

ottom

The water top tank  temp. sensor
is open or short circuit

The ambient temp. sensor
is open or short circuit

The pipe temp. sensor is 
open or short circuit

The evaporator temp. Sensor
 is open or short circuit

The exhaust pressure is high ,
 high pressure switch action

The suction pressure is low,
Low pressure switch action

No water or litter water 
in water system

Wired remote control with master 
signal failure 

Ambient temperature is too low 

Water flow volume not enough,Water 
system pressure difference is small

Water flow volume not enough,Water 
system pressure difference is small

Check or change the water 
bottom  temp. Sensor

Check or change the water 
top tank  temp. Sensor

Check or change the 
ambient temp.

 S

ensor

Check or change the 
pipe temp.

 S

ensor

Check or change the 
evaporator temp. Sensor

Check high pressure switch
and cooling return circuit

Check low pressure switch and 
cooling return circuit

Check the flow volume ,water 
pump is failure or not

Check the flow volume,water 
system is jammed or not

Check the flow volume,water 
system is jammed or not

The a

Sensor

 is open or short circuit

nti-freeze temp. 

Check or change the 
a

Sensor

nti-freeze temp. 

P034

Solar temp. Failure

Check the connection line between 
the wired remote control and 
motherboard

The solar

Sensor

 is open or short circuit

 temp. 

Check or change the 
solar

Sensor

 temp. 

Summary of Contents for 200A++

Page 1: ...Operation Installation Manual Operation Installation Manual Air source hot water heat pump Air source hot water heat pump COMPACT COMPACT INDOL INDOL...

Page 2: ...rding to the manual Once finish the installation and connection please make everything ok before power on the unit The manufacture of this product will not be held responsible if someone is injured or...

Page 3: ...Map 4 2 Choose the Suitable Unit 4 3 Deposited and Transportation 4 4 Installation Position 4 5 Water Loop Connection 4 6 Wire Connection 4 7 Trial Running 5 Usage 5 1 Icons Introduction 5 2 Operation...

Page 4: ...per installation which can lead to water leakage electrical shock or fire Professional installer is required Earthing is required Please make sure that the unit and power connection have good earthing...

Page 5: ...trical shock or fire may be occur When the heat pump need to be repaired please entrust dealer or qualified person to carry it out Improper movement or repair on the unit will lead to water leakage el...

Page 6: ...s a timer for start and stop and an adjustment dial for easy setting of the water temperature depending upon the location of the air exchanger heat may be taken from the outside environment from a sun...

Page 7: ...oderate temperature liquid Then the pressure of the liqiud refrigerant drops as it passes throttling device Finally refrigerant absorbs heat from the surrounding air and evaporates into vapor with low...

Page 8: ...and right sides and 1 at the back 7 in total 5 2 Specs 2 4 Dimensions Unit mm Dimention Model Indol Compact 200A C B Condensation water outlet A Overheating protector Eletricity heater Drainage E F D...

Page 9: ...e of the operating water pressures 0 15 0 7MPa Model Heating capacity Water tank capacity Power input Running current Power supply Compressor Number Compressor Rated outlet water Temp Air volume Air p...

Page 10: ...the unit correctly please run the unit at environment temperature 0 40 The unit includes sophisticated electronic devices prohibited to use water from lake untreated river water and groundwater Power...

Page 11: ...stallation 4 1 Installation Sketch Map Air inlet 160mm pipe Drainage Cold water inlet Manual valve Air outlet Condensation water outlet Hot water outlet NOTE A safety valve MUST be installed on water...

Page 12: ...transported by a fork lift the unit must remain mounted on the pallet The lifting rate should be kept to a minimum Due to its top heaviness the unit must be secured against tipping over To prevent an...

Page 13: ...d heat exchanger of the hot water heat pump enables direct connection to a second heat generator e g a solar heating system or a boiler 2 Dehumidification in the recirculating air mode see picture bel...

Page 14: ...n 1 Choose the right path to move the unit 2 Try to move the unit as original case 3 If the unit installed in the building of the metal part it must work for electrical insulation and comply with the...

Page 15: ...installation has to be executed in compliance with DIN 1988 in case of excessive water pipe pressure a pressure relief valve is to be provided The water pipes may be of the rigid of flexible type to...

Page 16: ...2 3 4 5 6 ON OFF Mode Electric Heater Up Down Turn on off the unit Switch unit running modes or save setting parameters Set the clock or the timer Turn on off the electric heater or switch fan modes M...

Page 17: ...play area displays the minute Second Shows that the main display area displays the second Centigrade Shows that the temperature in Main display area or Auxiliary display area is in Fahrenheit Shows th...

Page 18: ...gent Running interface 2 1 Turn ON OFF the unit Press and hold for 0 5s in the standby interface of the wire controller to turn on the unit and at this time the main display area shows the water outle...

Page 19: ...ure After making the changes to the parameter press to confirm or to cancel the changes then return to the previous interface If no operations are performed on the keypad for 5s the controller exits t...

Page 20: ...do as follows to set the time when in heating mode When press once the time parameter will flash When press again the hour parameter will flash then press or to change it After making the changes to t...

Page 21: ...timer1 setting you can set the turn on time of timer2 After finishing the OFF and 2 will flash and then you can set the turn off time of timer2 Press again to save and back to the interface If you do...

Page 22: ...nto the next setting without confirm the previous one ON 2 Press and hold for 2s to enter into the next setting without confirm the previous one Press and hold for 2s to enter into the next setting wi...

Page 23: ...20 00 Outlet water temperature Current time Press and hold for 2s ON 1 OFF 1 Press to confirm Successful setting Press to cancel the setting and exit Without saving Confirm the time after setting Con...

Page 24: ...lashing at this time Then set the date in the same way as 2 4 Example Set the start up date on September 28 Note Turn off the unit before going out Vacation mode Outlet water temperature The current d...

Page 25: ...Usage 22 2 5 3 If you want to cancel the timer setting follow this below press to cancel all the operation Outlet water temperature Timer state Pressing lasting for 2S The ON and 1 icons are flashing...

Page 26: ...op running when the unit target temperature is reached Definition of the fan icon 1 Running shows that the fan is running at high speed 2 Running shows that the fan is running at low speed 3 Fan icon...

Page 27: ...5 Usage 24 2 8 Keyboard locking Press and hold for 5s once to lock the keyboard Press and hold for 5s again to unlock the keyboard Press and hold for 5s Lock icon...

Page 28: ...ilure part if there is any and recharge the refrigerant if it is needed If the heat pump is not used for a long time please drain out all the water in the unit and seal the unit to keep it good Please...

Page 29: ...tank temp sensor is open or short circuit The ambient temp sensor is open or short circuit The pipe temp sensor is open or short circuit The evaporator temp Sensor is open or short circuit The exhaus...

Page 30: ......

Page 31: ...Code 20201120 0001 Code 20201120 0001...

Page 32: ...0 C6 88 9 1 3 41 70 H D 5 A 27 B8 6 3...

Reviews: