Overview
The TS-SCM (Secondary Containment Monitoring) system is a continuous secondary containment monitoring system that
monitors the interstitial spaces of double walled tanks and sumps, secondarily contained product and vapor return piping.
This product can be ordered as an available option with Franklin Fueling Systems’s TS-550 and TS-5000 FMS consoles.
The TS-SCM system is comprised of an application running on a T5 series FMS console and all necessary input and
output modules with installation kits. The Secondary Containment Control Module (SCCM) consists of a vacuum sensor,
solenoid valve, mechanical bypass valve, and vacuum manifold. SCM uses the STP siphon port vacuum to evacuate the
containment space and AutoLearn® technology to determine the characteristics of each secondary containment area that
is monitored.
Warning
SCM equipment operates at a standard 2" to 6" Hg and should only be used to monitor contain
-
ments that are designed to withstand these vacuum levels. Refer to the containment manufacturer
for further information.
Applications
The following diagram illustrates a typical installation of SCM equipment inside of a STP sump.
Tank
Containment
Install Kit
Vacuum Sensor
Integral Solenoid
Product Pipe
Double Wall
APT
Test
Boot
APT
Syphon
Check Valve
TS-LSU500
Pump
Submersible
FE Petro
TS-SCCM/1
High Voltage Conduit
Intrinsically
Safe Conduit
To Bottom
of Tank
Figure 1
– TS-SCM System Overview