Incite Fire Sigma CP AFP-2516 Manual Download Page 7

Sigma_CP_Australian Interface Module.doc 

      Page 7 of 9 

To  terminate  the  data  cable  correctly, 
the  last  board  on  the  comms  line  must 
have jumper J2 fitted as shown. 
 
For the position of J2 on other panels or 
boards refer to the relevant manual. 
 
After  the  AIM  has  been  connected  to 
the  main  panel,  the  main  panel  has  to 
“learn”  that  it  exists.    This  is  necessary 
so that the main panel can announce a 
fault  condition  if  the  AIM  becomes 
disconnected. 
 
To “teach” the main panel that an AIM is 
connected, ensure that all  other  boards 
have the data cable connected with the 
correct  polarity.    Check  that  all  boards 
are  supplied  with  power  and  that  the 
green, OK LED is lit at each one. 
 
Press the processor reset switch on the 
main  panel  PCB.    The  main  panel  will 
display  the  address  of  the  first  board  it 
finds on the seven segment LED display 
such as. 

o1

 

This indicates ancillary board 1 (o1).  To accept this, the enter button on the main panel should be 
pressed  whereupon,  if  more  boards  are  found,  their  addresses  will  be  displayed  and  must  be 
accepted  by  pressing  the  enter  button  once  again.    This  is  repeated  until  all  of  the  boards  are 
recognised by the main panel.  The AIM is fixed at ancillary board address 7 and will appear on the 
display as  

o7

 

If any board becomes disconnected after it has been “learnt” by the main panel, the main panel will 
display  a  comms  fault  and  the  number  of  the  board  will  be  shown  on  the  seven  segment  LED 
display. 
The board/s that have become disconnected from the main panel will also display a comms fault 
on their COMMS LED. 

 
 

 
 

Figure 4-Comms terminating jumper on the AIM

 

Summary of Contents for Sigma CP AFP-2516

Page 1: ...Man AIM AUS Issue 01 October 2011 Conventional Fire Control Panel AFP 2516 Australian Interface Module ...

Page 2: ...ard 5 5 24V Input 6 6 Connection to main panel and other boards 6 7 Operation 8 7 1 Normal condition 8 7 2 ACF Ancillary Control Facility 8 7 2 1 Outputs 8 7 2 2 Configuration 8 7 2 3 Controls only available at Access Level 2 8 7 3 Door Holder Output 8 7 4 ASE Outputs Alarm Signalling Equipment 9 7 5 Fuse fail 9 7 6 COMMS 9 7 7 Microprocessor Reset link 9 7 8 Module Address 9 8 Power requirements ...

Page 3: ...ce ASE from the control panel via a 2 core data bus The Australian Interface Module is compatible with all Sigma CP control panels Only one AIM is permitted on each control panel and has a fixed addressed at o7 output unit 7 NOTE The Australian Interface Module if fitted is fixed at address 7 and in this instance only 6 Ancillary boards can be fitted at addresses 1 to 6 The total length of the dat...

Page 4: ...make any appropriate information about this product available to anyone concerned with its use This Ancillary board is designed for indoor use only and at temperatures between 50 C and 400 C and with a maximum relative humidity of 95 The IP rating for the enclosure is IP30 Operation outside of these limits may render the equipment unreliable and unsafe 2 2 Mounting If not fitted inside a Sigma CP ...

Page 5: ...Maximum total cable distance 1200 metres Metal cable glands should be used Size 155 X 135 X 30 Millimetres Fixing Four 4mm holes One in each corner of the board 4 Connecting to the circuit board All connections for field wiring are to rows of terminals along the top and bottom of the circuit board Cabling must comply with the relevant Australian Standards Shielded fire alarm cable for power and RS...

Page 6: ...ient Four power terminals are provided so that 24V DC wiring can be taken into the module and then out again on to other ancillary boards or other equipment 6 Connection to main panel and other boards If power is supplied locally to the Australian Interface Module board only two wires are required from the main panel Wiring can be standard fire alarm cable or shielded data cable The shield of the ...

Page 7: ...et switch on the main panel PCB The main panel will display the address of the first board it finds on the seven segment LED display such as o1 This indicates ancillary board 1 o1 To accept this the enter button on the main panel should be pressed whereupon if more boards are found their addresses will be displayed and must be accepted by pressing the enter button once again This is repeated until...

Page 8: ...IM module in order to reset the ACF firstly the Alarm must be reset and then the ACF can be reset using the ACF Reset switch on the AIM module When the ACF is set to non latching the ACF output is deactivated when the alarm is reset or disabled The Isolate switch on the AIM module allows the ACF output to be disabled and not operate on an alarm condition A yellow ACF Isolated LED indicates when th...

Page 9: ...ored output If voltages or currents exceeding those in Table 1 on Page 5 need to be switched then a suitable relay or contactor device should be interposed between the ancillary board and the system to be controlled 7 5 Fuse fail The AIM is fitted with a 1 Amp rated self resetting electronic fuse This fuse protects the electronics of the AIM and prevents any excessive loading of the power supply t...

Page 10: ...Sigma_CP_Australian Interface Module doc Page 10 of 10 When supplied from the Sigma CP panel extra battery capacity of 0 6Ah should be allowed to give 24 Hour standby ...

Reviews: