Incite Fire Sigma CP AFP-2516 Manual Download Page 4

Sigma_CP_Australian Interface Module.doc 

      Page 4 of 9 

2

 

Safety and mounting 

2.1

 

Safety 

Suppliers  of  articles for use  at  work  are required  to  ensure  as reasonably  as  is  practical that  the 
article will be safe and without risk to health when properly used. 

An article is not regarded as properly used if it is used ‘without regard to any relevant information 
or advice’ relating to its use made available by the supplier. 

This  product  should  be  installed,  commissioned  and  maintained  by  trained  service  personnel  in 
accordance with the following: 

 

(i) 

Local regulations for electrical equipment in buildings 

(ii) 

Codes of practice 

(iii) 

Statutory requirements 

(iv) 

Any instructions specifically advised by the manufacturer 

 

You  are  therefore  requested  to  take  such  steps  as  are  necessary  to  ensure  that  you  make  any 
appropriate information about this product available to anyone concerned with its use. 

This Ancillary board is designed for indoor use only and at temperatures between -5

0

C and +40

0

and with a maximum relative humidity of 95%. 

The IP rating for the enclosure is IP30. 

Operation outside of these limits may render the equipment unreliable and unsafe. 

 

 
2.2 

Mounting

 

If  not fitted  inside  a  Sigma  CP  panel, the  board  should  be  mounted  in a  suitable  enclosure such 
that it is protected from ingress of water, dust or foreign bodies. 

It should be positioned in an accessible place as agreed with the end user.   

Suitable fixings should be used at all fixing points such that the board and enclosure are securely 
mounted and not liable to move once fixed. 

The enclosure should not be mounted near sources of excessive heat.   

Cables  should  be  connected  using  suitable,  metal,  shielded  cable  glands.    All  swarf  and  debris 
caused by drilling of additional cable entries must be cleared before power is applied. 

 

 

 

 

 

 

Summary of Contents for Sigma CP AFP-2516

Page 1: ...Man AIM AUS Issue 01 October 2011 Conventional Fire Control Panel AFP 2516 Australian Interface Module ...

Page 2: ...ard 5 5 24V Input 6 6 Connection to main panel and other boards 6 7 Operation 8 7 1 Normal condition 8 7 2 ACF Ancillary Control Facility 8 7 2 1 Outputs 8 7 2 2 Configuration 8 7 2 3 Controls only available at Access Level 2 8 7 3 Door Holder Output 8 7 4 ASE Outputs Alarm Signalling Equipment 9 7 5 Fuse fail 9 7 6 COMMS 9 7 7 Microprocessor Reset link 9 7 8 Module Address 9 8 Power requirements ...

Page 3: ...ce ASE from the control panel via a 2 core data bus The Australian Interface Module is compatible with all Sigma CP control panels Only one AIM is permitted on each control panel and has a fixed addressed at o7 output unit 7 NOTE The Australian Interface Module if fitted is fixed at address 7 and in this instance only 6 Ancillary boards can be fitted at addresses 1 to 6 The total length of the dat...

Page 4: ...make any appropriate information about this product available to anyone concerned with its use This Ancillary board is designed for indoor use only and at temperatures between 50 C and 400 C and with a maximum relative humidity of 95 The IP rating for the enclosure is IP30 Operation outside of these limits may render the equipment unreliable and unsafe 2 2 Mounting If not fitted inside a Sigma CP ...

Page 5: ...Maximum total cable distance 1200 metres Metal cable glands should be used Size 155 X 135 X 30 Millimetres Fixing Four 4mm holes One in each corner of the board 4 Connecting to the circuit board All connections for field wiring are to rows of terminals along the top and bottom of the circuit board Cabling must comply with the relevant Australian Standards Shielded fire alarm cable for power and RS...

Page 6: ...ient Four power terminals are provided so that 24V DC wiring can be taken into the module and then out again on to other ancillary boards or other equipment 6 Connection to main panel and other boards If power is supplied locally to the Australian Interface Module board only two wires are required from the main panel Wiring can be standard fire alarm cable or shielded data cable The shield of the ...

Page 7: ...et switch on the main panel PCB The main panel will display the address of the first board it finds on the seven segment LED display such as o1 This indicates ancillary board 1 o1 To accept this the enter button on the main panel should be pressed whereupon if more boards are found their addresses will be displayed and must be accepted by pressing the enter button once again This is repeated until...

Page 8: ...IM module in order to reset the ACF firstly the Alarm must be reset and then the ACF can be reset using the ACF Reset switch on the AIM module When the ACF is set to non latching the ACF output is deactivated when the alarm is reset or disabled The Isolate switch on the AIM module allows the ACF output to be disabled and not operate on an alarm condition A yellow ACF Isolated LED indicates when th...

Page 9: ...ored output If voltages or currents exceeding those in Table 1 on Page 5 need to be switched then a suitable relay or contactor device should be interposed between the ancillary board and the system to be controlled 7 5 Fuse fail The AIM is fitted with a 1 Amp rated self resetting electronic fuse This fuse protects the electronics of the AIM and prevents any excessive loading of the power supply t...