Checking fault and alarm release

Test

Procedure

Action

Block or switch off the fire incident control and remote 

alerting on superordinate FACP.

Check airflow 

monitoring

Tape over the 

sampling ho-

les (adhesive 

tape); the 

number de-

pends on the 

pipe configu-

ration.

As soon as the resulting

change in airflow rate exceeds

±20% (which can also be

checked using switch position

V

), the “Fault”  LED begins to

flash.

Once the LS-Ü delay (300 s)

has elapsed, the ASD triggers

a fault 

fault on FACP 

.

Check alarm 

release

Impose 

smoke at the 

maintenance 

sampling hole 

or sampling 

hole.

ASD triggers an alarm 

alarm on FACP; check for cor-

rect alarm transmission (zone/

range release) on the FACP

.

Any pre-signals will also re-

lease.

Reset the ASD 533 between each check (please note: reset-

ting the ASD does not reset the FACP).

Alternatively, this control can also be performed using the “Test 

trigger” function from 

EasyConfig

switch position

I

Article numbers and spare parts

Short designation

Article number

Aspirating smoke detector ASD 533-1

11-2000001-01-XX

Replacement smoke sensor SSD 533

11-2200006-01-XX

SecuriLine eXtended line module XLM 35

11-2200003-01-XX

SecuriLine module SLM 35

4000286.0101

Relay interface module RIM 35

4000287.0101

Memory card module MCM 35

4000285.0101

SD memory card (industrial version)

11-4000007-01-XX

USB cable, 4.5 m

4301248

Main board AMB 33-1

11-2200004-01-XX

BCB 35 (without smoke level indicator)

4301220.0101

Aspirating fan unit AFU 35, complete

4000299

Airflow sensor AFS 35

4000300

Insect protection screen IPS 35 (set of 2)

11-2300012-01-XX

Lithium battery

11-4000002-01-XX

Cable screw union

M20 (set of 10)

11-4000003-01-XX

M25 (set of 10)

11-4000004-01-XX

Adapter US cable screw union AD US M-Inch 11-2300029-01-XX

Universal module support UMS 35

4301252.0101

Technical description ASD 533

T 140 287

Material for the sampling pipe

T 131 194

Commissioning protocol

T 140 299

Data sheets

XLM 35

T 140 088

SLM 35

T 131 197

RIM 35

T 131 196

MCM 35

T 131 195

AFU 35 installation instructions

T 131 200

Declaration of performance

www.securiton.ch/declaration-of-performance

Dimensioned drawing

Fig. 5 Detector housing dimensioned drawing

Position of M25 

screwed cable glands 

and air outlet

Position 

of air outlet

Space requirement 

for offset mounting 

of the housing cover 

for commissioning 

and maintenance

27

(76)

27

35

22

148

57

23

(1

71

)

34

8

ca

. 2

6

(3

97

)

265

114

35

44

74

31

225

20

20

31

0

19

19

10 6,5

Summary of Contents for ASD 533

Page 1: ... 35 Memory Card Module The ASD 533 can be connected to a higher level FACP via poten tial free change over contacts Fitting an XLM 35 or SLM 35 means that the ASD 533 can be ide ally connected to the SecuriFire and Integral fire alarm systems via the addressable loop with SLM also to the SecuriPro The RIM 35 is available as a further installation option This mod ule enables the availability of all...

Page 2: ...allation of the ASD release the two lock clamps however it should be left inside its protective packaging until the definitive commissioning The definitive installation is carried out as de scribed below see Fig 3 Always leave the smoke sensor inside its protective packaging until it is ready to be installed definitively in the detector housing Depending on the circumstances e g long period of tim...

Page 3: ...manently assigned parameters Normative system limits according to EN 54 20 Class A to C positions A11 to C31 Non normative system limits positions W01 to W44 Configurable positions for settings after using ASD PipeFlow and or ASD Config or SecuriPro SecuriFire or Integral FACP SLM 35 XLM 35 X01 to X03 The parameters are saved at the factory with values for compliance with EN 54 20 Changing the par...

Page 4: ...ior consultation with the manufacturer The airflow monitoring values stored under those switch positions are not tested in accordance with EN For more information on using the table of system limits please refer to the Technical description T 140 287 Sec 4 4 4 3 and 4 4 4 4 Table of system limits for planning without ASD PipeFlow calculation Compliant with EN 54 20 Class A highly sensitive Shape S...

Page 5: ... 5 3 0 7 0 11 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 2 5 4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 U T shaped sampling pipes Number of sam pling holes per sampling branch Hole diameter in mm for the sampling hole number as of ASD 1 2 3 4 5 6 7 8 1 5 0 2 4 0 5 0 3 4 0 4 0 5 0 4 4 0 4 0 4 0 5 0 5 4 0 4 0 4 5 5 0 6 5 6 3 0 3 0 3 5 3 5 4 0 6 5 7 2 5 3 0 3 0 3 5 3 5 4 0 6 5 8 2 5 2 5 3 0 3 0 ...

Page 6: ... 5 60 5 X01 X03 Soiling threshold of Al 75 65 100 5 X01 X03 Dust latching On On Off X01 X03 Soiling latching On On Off X01 X03 Smoke sensor fault delay 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü pipe blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity applies to A01 to C31 20 1 70 1 X01 X03 LS Ü value averaging number 20 1 30 1 X01 X03 LS Ü delay a...

Page 7: ...al 1 s 1 120 s MCM smoke peak value memory Off Off On Carry out new initial reset On Off Smoke sensor mode of operation smoke sensor I SSD DMB SSD DMB or OEM inputs individual or in combination Switched off Isolate smoke sensor smoke sensor I Normal operation Isolate normal operation Filter monitoring smoke sensor I Off Off On Filter service life 6 months 1 24 months Read out operation time months...

Page 8: ... b21 Displays the new set ting Initial reset Measure Display Procedure remarks Before carrying out an initial reset i e after switching on the ASD 533 make sure you observe a waiting time of at least 5 min 1 Press the UP key flashing C31 or others Displays the default setting or the installa tion specific switch position 2 Press the UP key several times until dis play shows U in succession A to U ...

Page 9: ...200006 01 XX SecuriLine eXtended line module XLM 35 11 2200003 01 XX SecuriLine module SLM 35 4000286 0101 Relay interface module RIM 35 4000287 0101 Memory card module MCM 35 4000285 0101 SD memory card industrial version 11 4000007 01 XX USB cable 4 5 m 4301248 Main board AMB 33 1 11 2200004 01 XX BCB 35 without smoke level indicator 4301220 0101 Aspirating fan unit AFU 35 complete 4000299 Airfl...

Page 10: ... C Sampling pipe temperature range 20 60 C Max permissible temperature fluctuation in detector housing and sampling pipe operation 20 C Max permissible storage temperature for detector housing without condensation 20 70 C Ambient pressure difference between detector housing and sampling pipe sampling holes must be identical Humidity ambient condition for detector housing transient without condensa...

Reviews: