Fig. 3 Using the smoke sensor

Displays on the control unit

Several LEDs on the control unit indicate the current status of the 

ASD 533. 

Function / state

Op

er

ati

on

Al

ar

m

Fa

ul

t

D

et.

 d

us

ty

 / d

irty

green red

yellowyellow

System Off (no voltage)

System inactive (reset external)

On

½ T

Smoke sensor Off (from FACP)

On

½ T

Idle state

On

Pipe blockage/pipe breakage,

delay running 

On

1 T

Pipe blockage/pipe breakage,

fault triggered

On

On

Fan tacho signal missing

On

On

Fault triggered

On

On

Pre-signal 1

On

2 T

Pre-signal 2

On

1 T

Pre-signal 3

On

½ T

Alarm

On

On

Smoke sensor filter fault

On

2 T

Smoke sensor dusty

On

1 T

Smoke sensor dirty

On

½ T

Smoke sensor fault

On

On

Lamp test (press “Reset” 10 s)

1 T

1 T

1 T

1 T

No fault triggered (triggers only after delay time has

expired 

 “

Fault

” continuously lit).

T

= flashing display; ½ s cycle / 1 s cycle / 2 s cycle

Displays on the Main Board AMB 33

The AMB 33 has a 3-digit segment display enabling the following 

outputs and displays:

flashing, point and 

AL

= auto-learning running;

flashing, point and 

Fr

= filter replacement is running;

flashing point and continuously lit point = day/night control ac-

tive;

switch position 

E

= event memory 

E01

to 

E99

;

switch position 

F

= firmware version;

press “UP” key = set configuration 

A11

to 

X03

;

switch position 

V

= airflow values (airflow rate);

flashing

000

= invalid entry;

flashing

U - -

= initial reset is running;

flashing

IA1

,

IF1

,

IP1

,

IE1

= test trigger is activated.

Programming

The ASD 533 has switch positions, which are configured with per-

manently assigned parameters:

Normative system limits according to EN 54-20, Class A to C,

positions 

A11

to 

C31

;

Non-normative system limits, positions 

W01

to 

W44

;

Configurable positions for settings after using “ASD PipeFlow”

and/or “ASD Config” or SecuriPro, SecuriFire or Integral FACP

(SLM 35 / XLM 35), 

X01

to 

X03

.

The parameters are saved at the factory with values for 

compliance with EN 54-20. Changing the parameters 

may result in non-compliance with EN 54-20. Re-

programming on the ASD 533 using “ASD Config” may 

be carried out only by the manufacturer or by persons 

under the supervision of and trained by the manufacturer.

Switch positions on the Main Board AMB 33

Pos. Range / Display

Purpose

A

A11

acc. to EN 54-20, Class A

b

b11

/

b21

acc. to EN 54-20, Class B

C

C11

/

C21

/

C31

acc. to EN 54-20, Class C

d

Polling (

RE

)

Setting (

SE

on

/

T

/

R

/

oFF

on

= On / 

oFF

= Off

T

= filter service life

R

= filter replacement

ch1

= channel I

E

E01

to 

E99

G00

to 

G99

Event memory 

E01

E99

Event group 

G00

G99

F

F00

to 

F99

(3 x)

Displays firmware version

I

IA1

IF1

IP1

IE1

Trigger; Test alarm (

IA1

)

Test fault (

IF1

Test pre-signal (

IP1

Test alarm 2 (

IE1

)

o

o00

Logs off additional modules

(optional modules)

T

Y10

to 

Y99

/

M01

to 

M12

d01

to 

d31

/

H00

to 

H23

M00

to 

M59

Polling (

RE

) and setting (

SE

)

the date and time

U

U01

Executes initial reset

V

V01

, from 

000

to 

255

Airflow rate output in %

W W01

to 

W44

non-normative

X

X01

to 

X03

configurable

The table only lists the available switch positions. For in-

formation on the input procedure please refer to the 

Technical description, T 140 287, Sec. 8.3.

Anti-twist rib

Flat cable

Smoke sensor chamber  I

Connection for

smoke sensor

Insect protection

screen

Lock clamp

Lock clamp

Smoke sensor

SSD 533

AMB 33

Smoke sensor chamber  II not used

Air duct II closed

Summary of Contents for ASD 533

Page 1: ... 35 Memory Card Module The ASD 533 can be connected to a higher level FACP via poten tial free change over contacts Fitting an XLM 35 or SLM 35 means that the ASD 533 can be ide ally connected to the SecuriFire and Integral fire alarm systems via the addressable loop with SLM also to the SecuriPro The RIM 35 is available as a further installation option This mod ule enables the availability of all...

Page 2: ...allation of the ASD release the two lock clamps however it should be left inside its protective packaging until the definitive commissioning The definitive installation is carried out as de scribed below see Fig 3 Always leave the smoke sensor inside its protective packaging until it is ready to be installed definitively in the detector housing Depending on the circumstances e g long period of tim...

Page 3: ...manently assigned parameters Normative system limits according to EN 54 20 Class A to C positions A11 to C31 Non normative system limits positions W01 to W44 Configurable positions for settings after using ASD PipeFlow and or ASD Config or SecuriPro SecuriFire or Integral FACP SLM 35 XLM 35 X01 to X03 The parameters are saved at the factory with values for compliance with EN 54 20 Changing the par...

Page 4: ...ior consultation with the manufacturer The airflow monitoring values stored under those switch positions are not tested in accordance with EN For more information on using the table of system limits please refer to the Technical description T 140 287 Sec 4 4 4 3 and 4 4 4 4 Table of system limits for planning without ASD PipeFlow calculation Compliant with EN 54 20 Class A highly sensitive Shape S...

Page 5: ... 5 3 0 7 0 11 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 2 5 4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 U T shaped sampling pipes Number of sam pling holes per sampling branch Hole diameter in mm for the sampling hole number as of ASD 1 2 3 4 5 6 7 8 1 5 0 2 4 0 5 0 3 4 0 4 0 5 0 4 4 0 4 0 4 0 5 0 5 4 0 4 0 4 5 5 0 6 5 6 3 0 3 0 3 5 3 5 4 0 6 5 7 2 5 3 0 3 0 3 5 3 5 4 0 6 5 8 2 5 2 5 3 0 3 0 ...

Page 6: ... 5 60 5 X01 X03 Soiling threshold of Al 75 65 100 5 X01 X03 Dust latching On On Off X01 X03 Soiling latching On On Off X01 X03 Smoke sensor fault delay 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü pipe blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity applies to A01 to C31 20 1 70 1 X01 X03 LS Ü value averaging number 20 1 30 1 X01 X03 LS Ü delay a...

Page 7: ...al 1 s 1 120 s MCM smoke peak value memory Off Off On Carry out new initial reset On Off Smoke sensor mode of operation smoke sensor I SSD DMB SSD DMB or OEM inputs individual or in combination Switched off Isolate smoke sensor smoke sensor I Normal operation Isolate normal operation Filter monitoring smoke sensor I Off Off On Filter service life 6 months 1 24 months Read out operation time months...

Page 8: ... b21 Displays the new set ting Initial reset Measure Display Procedure remarks Before carrying out an initial reset i e after switching on the ASD 533 make sure you observe a waiting time of at least 5 min 1 Press the UP key flashing C31 or others Displays the default setting or the installa tion specific switch position 2 Press the UP key several times until dis play shows U in succession A to U ...

Page 9: ...200006 01 XX SecuriLine eXtended line module XLM 35 11 2200003 01 XX SecuriLine module SLM 35 4000286 0101 Relay interface module RIM 35 4000287 0101 Memory card module MCM 35 4000285 0101 SD memory card industrial version 11 4000007 01 XX USB cable 4 5 m 4301248 Main board AMB 33 1 11 2200004 01 XX BCB 35 without smoke level indicator 4301220 0101 Aspirating fan unit AFU 35 complete 4000299 Airfl...

Page 10: ... C Sampling pipe temperature range 20 60 C Max permissible temperature fluctuation in detector housing and sampling pipe operation 20 C Max permissible storage temperature for detector housing without condensation 20 70 C Ambient pressure difference between detector housing and sampling pipe sampling holes must be identical Humidity ambient condition for detector housing transient without condensa...