Fig. 3 Using the smoke sensor
Displays on the control unit
Several LEDs on the control unit indicate the current status of the
ASD 533.
Function / state
Op
er
ati
on
Al
ar
m
Fa
ul
t
D
et.
d
us
ty
/ d
irty
green red
yellowyellow
System Off (no voltage)
System inactive (reset external)
On
½ T
Smoke sensor Off (from FACP)
On
½ T
Idle state
On
Pipe blockage/pipe breakage,
delay running
On
1 T
Pipe blockage/pipe breakage,
fault triggered
On
On
Fan tacho signal missing
On
On
Fault triggered
On
On
Pre-signal 1
On
2 T
Pre-signal 2
On
1 T
Pre-signal 3
On
½ T
Alarm
On
On
Smoke sensor filter fault
On
2 T
Smoke sensor dusty
On
1 T
Smoke sensor dirty
On
½ T
Smoke sensor fault
On
On
Lamp test (press “Reset” 10 s)
1 T
1 T
1 T
1 T
No fault triggered (triggers only after delay time has
expired
“
Fault
” continuously lit).
T
= flashing display; ½ s cycle / 1 s cycle / 2 s cycle
Displays on the Main Board AMB 33
The AMB 33 has a 3-digit segment display enabling the following
outputs and displays:
•
flashing, point and
AL
= auto-learning running;
•
flashing, point and
Fr
= filter replacement is running;
•
flashing point and continuously lit point = day/night control ac-
tive;
•
switch position
E
= event memory
E01
to
E99
;
•
switch position
F
= firmware version;
•
press “UP” key = set configuration
A11
to
X03
;
•
switch position
V
= airflow values (airflow rate);
•
flashing
000
= invalid entry;
•
flashing
U - -
= initial reset is running;
•
flashing
IA1
,
IF1
,
IP1
,
IE1
= test trigger is activated.
Programming
The ASD 533 has switch positions, which are configured with per-
manently assigned parameters:
•
Normative system limits according to EN 54-20, Class A to C,
positions
A11
to
C31
;
•
Non-normative system limits, positions
W01
to
W44
;
•
Configurable positions for settings after using “ASD PipeFlow”
and/or “ASD Config” or SecuriPro, SecuriFire or Integral FACP
(SLM 35 / XLM 35),
X01
to
X03
.
The parameters are saved at the factory with values for
compliance with EN 54-20. Changing the parameters
may result in non-compliance with EN 54-20. Re-
programming on the ASD 533 using “ASD Config” may
be carried out only by the manufacturer or by persons
under the supervision of and trained by the manufacturer.
Switch positions on the Main Board AMB 33
Pos. Range / Display
Purpose
A
A11
acc. to EN 54-20, Class A
b
b11
/
b21
acc. to EN 54-20, Class B
C
C11
/
C21
/
C31
acc. to EN 54-20, Class C
d
Polling (
RE
)
Setting (
SE
)
on
/
T
/
R
/
oFF
on
= On /
oFF
= Off
T
= filter service life
R
= filter replacement
ch1
= channel I
E
E01
to
E99
G00
to
G99
Event memory
E01
–
E99
Event group
G00
–
G99
F
F00
to
F99
(3 x)
Displays firmware version
I
IA1
IF1
IP1
IE1
Trigger; Test alarm (
IA1
)
Test fault (
IF1
)
Test pre-signal (
IP1
)
Test alarm 2 (
IE1
)
o
o00
Logs off additional modules
(optional modules)
T
Y10
to
Y99
/
M01
to
M12
d01
to
d31
/
H00
to
H23
M00
to
M59
Polling (
RE
) and setting (
SE
)
the date and time
U
U01
Executes initial reset
V
V01
, from
000
to
255
Airflow rate output in %
W W01
to
W44
non-normative
X
X01
to
X03
configurable
The table only lists the available switch positions. For in-
formation on the input procedure please refer to the
Technical description, T 140 287, Sec. 8.3.
Anti-twist rib
Flat cable
Smoke sensor chamber I
Connection for
smoke sensor
Insect protection
screen
Lock clamp
Lock clamp
Smoke sensor
SSD 533
AMB 33
Smoke sensor chamber II not used
Air duct II closed