background image

DESCRIPTION

The System Sensor 2400 Series photoelectronic smoke de-

tectors are specifically designed to meet the performance re-
quirements of fire detection/alarm systems. These detectors
use state-of-the-art optical sensing chambers. The detectors
are designed to provide open area detection and are compati-
ble with FCI fire alarm control panels. The detectors’ opera-
tion and sensitivity can be tested in place. The Model 2400T
unit has the same specifications as the Model 2400, but in ad-
dition it features a built-in fixed temperature (135

o

F) thermal

detection unit.

Each detector has an LED which flashes every ten seconds

indicating that power is being applied to the detector. The
LED lights steadily when the detector is in alarm. A remote
LED annunciator is available as an optional accessory.

The 2400 and 2400T detectors include a tamper-resistant

feature that, when used, prevents removal of the detector
without the use of a tool.

Sensitivity testing is performed either by inserting a tool

into the recessed test switch opening or inserting a calibrated
test card according to the test procedures.

Field metering of detector sensitivity may be performed

with the aid of a voltmeter and test kit MOD 400R.

APPROVALS

2400

SYSTEM SENSOR

PHOTOELECTRONIC

SMOKE DETECTOR

9020-0587/Ver. 1.0

16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099

FEATURES

·

Built-in Tamper-resistant Feature

·

Built-in Test Switch

·

Built-in Visual Alarm Indicator

·

Remote LED Option

·

Compatible with FCI Control Panels

·

Field Metering of Detector Sensitivity

·

Removable Insect Screen and Cover
for Field Cleaning

·

Sealed against Dirt, Insects, and Back
Pressure

·

Insect-resistant Screening
(.020"/.508mm openings)

·

Convenient Terminal Strip Wiring

TECHNICAL SPECIFICATIONS

Nominal sensitivity

3.0%/ft. obscuration

Operating voltage

8.5 - 35 VDC (24 VDC nominal)

Operating current

120 uA maximum

Operating temperature

32

o

to 120

o

F  (0

o

to 49

o

C)

Operating humidity

10% to 93% relative humidity

Air velocity

3,000 fpm max.

Construction

Off-white flame-retardant plastic

Diameter

5.5 inches (14 cm)

Height

3.19 inches  (8.0 cm) high,

Weight

0.7 lb. (310 gm)

NOTE: Alarm current is limited by control panel initiating device circuit.

ORDERING INFORMATION

Part Number

Model

Description

2400

Photoelectronic Detector

2400T

Photoelectronic Detector w/135

o

F thermal

An ISO 9001 Certified Company

Reviews: