Site Preparation
Summary
We recommend a 4m x 4m concrete slab that is level and flat. Floor must be solid, flat and levelled. The concrete base is
a standard reinforced concrete slab 20cm thick. We recommend replacing the material at a depth of at least 50cm
(applying gravel and compacting to the compressibility modulus M = 80.0 MN/m2.
If being sited in a building/shelter, this to be 4m x 4.2m. Inside installation is acceptable if 15 or more air changes per
hour are provided. The room must be positive pressure as well. This prevents internal combustion products from entering
the room. The room should be designed not to exceed 120°F (50°C) or damage may occur to electrical components.
Local fire and building codes are to be met by the installer.
If the building has a roof, provision will need to be made to allow the chimney to pass through with weather protection as
shown on next drawing: (See APPENDIX 1 for more drawings)
All the fuel (gas or oil) supply installations must be done by approved professionals, in accordance to local regulations.
The control panel has a thermocouple attached via a 3m lead. The control panel will need siting in a suitable position
based on this 3m length. This is where power needs to go to – 230V 50Hz 10amp (if not ordered with power specifica-
tions). It is the client’s responsibility to supply power and a qualified electrician to make this connection in line with local
regulations.
It is also the clients responsibility to provide suitable lifting equipment and operator to place the primary chamber and lift
the secondary chamber into place, either a forklift truck, crane or similar, suitable for 2,000 kgs can be used.