10
7
Controller settings sheet
Parameter
Description
Factory settings
User Setting
Low pressure
Shutdown
Pressure at which pumps are
shutdown for low discharge pressure
100kPa
Low pressure Timer
Time delay before pump shuts down
5sec
High pressure
Shutdown
Pressure at which pumps are
shutdown for high discharge pressure
600kPa
High pressure Timer
Time delay before pump shuts down
5sec
Duty Pump on
Duty Pump start set point
400kPa
Duty Pump off
Duty Pump stop set point
500kPa
Standby Pump on
Standby Pump Start set Point
350kpa
Standby Pump off
Standby Pump Stop Set Point
500kpa
Sensor calibration
Sensor 100% (20mA) Pressure
1000kpa
Litres per second Pump
No1
Pump No1 output in litre per second
for total flow calculation
4l/s
Litres per second Pump
No2
Pump No2 output in litre per second
for total flow calculation
4l/s
Irrigation Control
Irrigation control (1) or pressure only
control (0)
0