10 

Controller settings sheet 
 

Parameter 

 

Description 

 

Factory settings 

 

User Setting 
 

Low pressure 
Shutdown

 

Pressure at which pumps are 
shutdown for low discharge pressure

 

100kPa

 

 

Low pressure Timer

 

Time delay before pump shuts down

 

5sec

 

 

High pressure 
Shutdown

 

Pressure at which pumps are 
shutdown for high discharge pressure

 

600kPa

 

 

High pressure Timer

 

Time delay before pump shuts down

 

5sec

 

 

Duty Pump on

 

Duty Pump start set point

 

400kPa

 

 

Duty Pump off

 

Duty Pump stop set point

 

500kPa

 

 

Standby Pump on

 

Standby Pump Start set Point

 

350kpa

 

 

Standby Pump off

 

Standby Pump Stop Set Point

 

500kpa

 

 

Sensor calibration

 

Sensor 100% (20mA) Pressure

 

1000kpa

 

 

Litres per second Pump 
No1

 

Pump No1 output in litre per second 
for total flow calculation

 

4l/s

 

 

Litres per second Pump 
No2

 

Pump No2 output in litre per second 
for total flow calculation

 

4l/s

 

 

Irrigation Control

 

Irrigation control (1) or pressure only 
control (0)

 

0

 

 

 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for PSJ2

Page 1: ...b www incacontrol com au Design Manufacture of Custom built switchboards Electronic control equipment AC DC pumping controls Installation service INCA MODEL PSJ2 PRESSURE CONTROLLER USER MANUAL Inca R...

Page 2: ...igh pressure shutdown 6 4 4 Setting high pressure time delay 6 4 5 Duty start pressure 6 4 6 Duty stop pressure 6 4 7 Standby start pressure 6 4 8 Standby stop pressure 6 4 9 Pressure sensor calibrati...

Page 3: ...ly programmable to suit transducer range Flow Totaliser up to 32000 kilolitres Inputs 2 wire plus shield connected to terminals located on panel base plate for pressure transducer 2 wire plus earth co...

Page 4: ...ntrol panel connect the positive lead to terminal No10 the return signal to terminal No12 The screen must be solidly earthed with a saddle clamp providing the best screening earth Float switch wiring...

Page 5: ...the blue buttons You can only enter a value of as many digits as is displayed on the screen Example an input that displays 3 digits can only have 3 digit entered 3 2 Power Up Display On power up the...

Page 6: ...ss 0 press 0 then press Return Arrow button Press the RIGHT ARROW Button to move onto the next Page 4 4 Setting High Pressure Time Delay High pressure time delay will now be displayed The Cursor will...

Page 7: ...controller The pump will then be controlled via the duty pressure on off settings If selected to OFF the pump will run via the duty pressure on off settings To select the Irrigation control enter 1 i...

Page 8: ...il manually reset If a low level float switch is connected closes this input the pump will be shutdown until the level rises to reset the float switch automatically restart the pump 5 2 Manual Off Aut...

Page 9: ...Fail displayed on screen Reset pump overload by pressing overload reset button on to of overload If problem continues call for service 5 System Produces a Low Pressure shutdown Press the reset button...

Page 10: ...r Time delay before pump shuts down 5sec Duty Pump on Duty Pump start set point 400kPa Duty Pump off Duty Pump stop set point 500kPa Standby Pump on Standby Pump Start set Point 350kpa Standby Pump of...

Page 11: ...tention under guarantee unless otherwise agreed must be returned to the factory freight paid and if accepted for free repair will be returned to the customers address in Australia free of charge Equip...