impro IXP20 Installation Manual Download Page 5

 

ISC304-0-0-GB-06 

April 2011 

Page 5 

 

NOTE:   

The 3 V, CR2032 Lithium cell Battery is partially installed in all models of the 
IXP20 Controller. 

 

An extra Fixed Address Label. 

General 

Remember the following when installing the IXP20 Controller: 

Communications Distance 

RS485 Terminal Port 

The RS485 communications distance between the ImproX Controller and the LAST 
ImproX Terminal in a cable run, MUST NOT exceed 1 km (1 090 yd).  Achieve this by 
using good quality screened, twisted 2-pair cable, with the screen EARTHED at one 
end. 

Jumper Links 

Long tra

nsmission lines or multiple “star” connections, may cause communication 

problems.  Placing a Jumper Link across the jumper (See Figure 3 for position) in the 
LAST UNIT AT THE END OF THE CABLE RUN should solve the problem.   

Distance between the Controller and its Wiegand or Multi-Discipline 
Readers 

CAUTION: 

When implementing the 150 m (164 yd) cable distances with Impro 
Wiegand Readers use the 12 V power output option.  Note, however, 
that the Multi-discipline Readers only connect using the 12 V power 
output option. 

For maximum, data communications distance, install the Readers no further than      
150 m (164 yd) from the Controller.  The cable individual conductor cross-sectional 
area should not be less than 0.2 mm

2

 (0.0003 in

2

). 

Distance between ImproX Units 

You can mount 

IXP20 Controllers (ISC920)

 directly next to each other.  To avoid 

mutual interference, install the 

Touch Screen IXP20 Controllers (ISC921)

 at least 500 

mm (20 in) apart. 

To avoid mutual interference, install the 

Wiegand Readers 

or

 Multi-discipline 

Readers

 at least 500 mm (20 in) apart. 

EARTH Connection 

Connect the IXP20 Controller to a good EARTH point.  Using the RS485 Port, connect 
the ETH Lead to the 

„ETH‟ Terminal.  Mains EARTH can be used, but electrical noise 

may exist. 

CAUTION: 

When using the IXP20 Controller with FCC approved accessories, 
ensure that the RS485 cable is routed through a separate grommet 
to the power cable.  Also ensure that you use a CE approved Power 
Supply Unit. 

 

Blank Space 

 

 

Summary of Contents for IXP20

Page 1: ...connected and relays off 75 0 90 24 V DC with no peripherals connected and relays off 40 0 96 Power Requirements ISC921 12 V DC with no peripherals connected and relays off 130 1 56 24 V DC with no p...

Page 2: ...discipline Reader and Wiegand Readers The function is selectable via the DIP switches See Table 1 Power Output 12 V DC and 5 V DC selectable at maximum 200 mA Modes Supported Tag PIN code or Reason Co...

Page 3: ...Input monitors a constant resistance through the circuit When the circuit is tampered with the Resistors are bypassed the Controller detects the resistance change raising an alarm Door Lock Type 2 Dry...

Page 4: ...o a PC We do NOT however supply this cable with the Controller s accessories Find the following when unpacking the ImproX IXP20 Controller Either an ImproX IXP20 Twin Reader Controller with Web Interf...

Page 5: ...with Impro Wiegand Readers use the 12 V power output option Note however that the Multi discipline Readers only connect using the 12 V power output option For maximum data communications distance inst...

Page 6: ...ttery Tab 3 Pull the removable Battery Tab out of the Battery Holder 4 Immediately apply power to the Controller Replacement NOTE Because of the delicacy of this procedure we recommend you contact you...

Page 7: ...tandard Wiegand Readers can only support one of two options HID Tags only or any other Tag type that is Slim Tags Omega Tags Mifare Standard Mifare Ultralite FeliCa Desfire WriTag 128 and WriTag 2048...

Page 8: ...Button 3 of the ImproX QT Quad Transmitter reports 12 If the ImproX RF is connected then Button 4 of the ImproX QT Quad Transmitter reports Table 1 Reader 1 Select and Reader 2 Select DIP switch Sett...

Page 9: ...he number to be a tag code The Controller discards the previously read Tag for the current one and the Controller will still expect a PIN code If the IXP20 Controller expects a Reason Code and receive...

Page 10: ...ISC304 0 0 GB 06 April 2011 Page 10 ELECTRICAL CONNECTIONS Key Component Positions Figure 3 IXP20 Controller Key Component Positions...

Page 11: ...C304 0 0 GB 06 April 2011 Page 11 Connecting the IXP20 Controller Figure 4 shows a typical electrical connection diagram for the IXP20 Controller Figure 4 Typical IXP20 Controller Electrical Connectio...

Page 12: ...ISC304 0 0 GB 06 April 2011 Page 12 Figure 5 IXP20 Controller connected to Wiegand Reader...

Page 13: ...ISC304 0 0 GB 06 April 2011 Page 13 Figure 6 IXP20 Controller connected to ImproX RF...

Page 14: ...utomatically clears the System Database on the next restart 1 Remove the Controller s Front Cover Assembly 2 With power applied to the Controller toggle switch 1 of the Door Lock Select DIP switch ON...

Page 15: ...e Terminals appear during the Software s Auto ID process MAC Address Figure 7 Sample MAC Address Label Each IXP20 Controller is supplied with a separate MAC Address Label much like the one shown in Fi...

Page 16: ...ISC304 0 0 GB 06 April 2011 Page 16 Fixed Address Label Unique Location Description...

Page 17: ...ISC304 0 0 GB 06 April 2011 Page 17 Fixed Address Label Unique Location Description...

Page 18: ...ISC304 0 0 GB 06 April 2011 Page 18 Fixed Address Label Unique Location Description...

Page 19: ...n Chart GUARANTEE OR WARRANTY CAUTION We reserve the right to nullify the products guarantee or warranty where you have not properly installed the Metal oxide Varistors This product conforms to our Gu...

Page 20: ...to the ImproX IXP20 Controller ISC920 0 0 GB 03 and ISC921 5 0 GB 03 The last two digits of the Impro stock code indicate the issue status of the product ISC304 0 0 GB 06 Issue 07 Apr 2011 IXP20 Cont...

Reviews: