EARTH Connection 

Connect the IXP110 Controller to a good EARTH point.  Using the Power Input Port, 
connect the 

EARTH Lead to the ‘ETH’ Terminal.  Mains EARTH can be used, but 

electrical noise may exist. 

Antenna Readers 

Antenna Reader Distance 

The ideal cable distance between the IXP110 Controller and its Antenna Reader 
ranges between 2 m to 16 m (7 ft to 53 ft).  Optimal performance is not guaranteed 
outside of this range.  Achieve optimal performance using a good quality shielded multi-
strand **3-pair twisted cable.  The cross-sectional area of the cable must not be less 
than 0.2 mm

2

 (0.0003 in

2

).   

NOTE:   

**When installing an ImproX RA, use 1-pair twisted cable. 

Cable Specifications 

The cable specifications should be similar to the following: 

Conductor Resistance: 

 

< 2 ohms. 

Capacitance, Core to Earth: 

< 160 pF/m. 

Capacitance, Core to Core: 

< 100 pF/m. 

Distance between Antenna Readers from the SAME Controller 

To avoid mutual interference install the Antenna Readers no closer than 150 mm (6 in) 
apart. 

Distance between Antenna Readers from DIFFERENT Controllers 

To avoid mutual interference install the Antenna Readers no closer than 500 mm      
(20 in) apart. 

Arc Suppression 

Snubber devices are recommended for EMF Flyback and Arc Suppression when 
driving an inductive load with the Relay, see Figure 2.   

 

Figure 2:  EMF Flyback 

 

Summary of Contents for IXP110

Page 1: ...sing a Sealed Lead Acid Backup Battery and or Strike Lock 9 V AC to 18 V AC 9 V DC to 24 V DC NOTE Battery Charging Voltage and Power Output Voltage are set at between 13 6 V DC and 13 8 V DC NOTE Thi...

Page 2: ...ng Input protection to 50 V DC continuous Figure 1 End of Line EOL Sensing Circuit NOTE These Inputs can be individually configured to have End of Line EOL Sensing in the Software via the Communicatio...

Page 3: ...stors 25 Vrms 500 A 77 V max clamping Four Wood Screws 3 5 mm x 25 mm Four Wall Plugs 7 mm IXP905 1 0 GB XX includes a standard 2 m 7 ft USB Printer Cable The USB Cable will have a Type A plug fitted...

Page 4: ...area of the cable must not be less than 0 2 mm 2 0 0003 in 2 NOTE When installing an ImproX RA use 1 pair twisted cable Cable Specifications The cable specifications should be similar to the following...

Page 5: ...gs supplied nuts and bolts or rivets Top Cover Release Mechanism 1 Remove the top two Thread Cutter Screws 2 2 x 5 mm from each of the End Plates 2 Insert a flat head screwdriver maximum 7 mm into the...

Page 6: ...r the metal clip of the Battery Holder with the Terminal facing UP 3 Press the Battery firmly into the Battery Holder 4 Attach the Controller s Top Cover Replacement 1 Remove the Controller s Top Cove...

Page 7: ...IXP343 0 0 GB 07 April 2009 Page 7 Connecting the IXP110 Controller Figure 6 Input and Power Connections...

Page 8: ...IXP343 0 0 GB 07 April 2009 Page 8 Figure 7 Antenna Reader and Relay Connections...

Page 9: ...s necessary to clear all Tagholders including all Tagholder settings follow these steps Figure 8 Deleting the Database Restore Factory Defaults If it becomes necessary to return the IXP110 System to i...

Page 10: ...ns including deleting the database and restoring factory defaults MAC Address The MAC Address identifies the Lantronix XPort component placed in each Ethernet version of the IXP110 Controller IXP906 1...

Page 11: ...IXP343 0 0 GB 07 April 2009 Page 11 USER NOTES...

Page 12: ...mproX IXP110 Controller IXP904 1 0 GB 02 IXP905 1 0 GB 02 and IXP906 1 0 GB 03 The last two digits of the Impro stock code indicate the issue status of the product IXP343 0 0 GB 07 Issue 08 Apr 2009 I...

Reviews: