Devices with a high in-rush current demand, such as certain maglocks and 

other electromechanical devices, can momentarily draw more than 3 A.  The 

Power Supply then effectively shuts down as directed by its built in 

protection as exceeding the 3 A rating is considered a short-circuit.  

Overcome this by installing the recommended 12 V 7 Ahr Battery to help 

supplement the in-rush current such a device may draw on activation. 

Power Input 

 

 

Input Voltage  

 

85 V AC to 265 V AC at 50/60 Hz. 

Power Output 

 

 

Output Voltage                      

 

(Mains Power On) 

13.8 V DC ±0.3 V DC. 

 

Output Current   

2 A continuous (Power Output Terminals). 

System Battery 

 

 

Type .......................................   6 V 3 Ahr (Max) Sealed Lead Acid Battery.  

 

Approximate Length ...............   151 mm (6 in) (Max). 

 

Approximate Width .................   65 mm (3 in) (Max). 

 

Approximate Height ................   99 mm (4 in) (Max) including the terminals. 

The following specifications are common to both the Aluminium Extruded Cabinet and 

the Power Supply Combo: 

 

Real Time Clock (RTC) Backup 

Battery 

 

 

Battery Type ...................   1 x 3 V, CR2032, Lithium cell Battery. 

 

Battery Life .....................   2 Years with power OFF,                                     

5 years with power ON,                                            

5 years storage with Battery Tab in place. 

Controller Communication 

Ethernet Port 

 

 

Connection .............................   Standard Ethernet RJ45 connector. 

10/100/1 000 Mbps, half or full duplex. 

 

NOTE: 

The Impro ECII is rated to 100 

MBps, however the Controller will 

work on a 1 000 MBps (1 GB) 

network. 

 

Protocol ..................................   TCP/IP, UDP. 

NOTE: 

The 

RS485 1 (Controller) Port 

connection details only apply to Impro EC

II

 

Controllers with Firmware V7.16 upwards. 

RS485 1 (Controller) Port 

 

 

Configuration ..........................   38 400 Default. 

 

Electrical Interface  .................   RS485. 

 

Baud Rates ............................   9 600, 19 200, 28 800, 38 400 and 57 600 

selectable via the Communications Protocol. 

Summary of Contents for IPS970

Page 1: ...Voltage 10 V DC to 30 V DC Power Requirements Current mA Power W Supply Voltage 10 V DC Maximum 420 4 2 Supply Voltage 30 V DC Maximum 140 4 2 System Battery Battery Type 6 V 3 Ahr Sealed Lead Acid B...

Page 2: ...n Max Approximate Width 65 mm 3 in Max Approximate Height 99 mm 4 in Max including the terminals The following specifications are common to both the Aluminium Extruded Cabinet and the Power Supply Com...

Page 3: ...line termination Default Mode Receive Mode General Memory RAM Non volatile 64 MBytes Flash ROM 8 MBytes Diagnostic LED Indicators Power on LED Red LED internally visible Incoming RS485 1 Controller F...

Page 4: ...85 communications distance between the Impro EC II Controller and the LAST Impro Unit in a cable run MUST NOT exceed 1 km 1 090 yd Achieve this by using good quality screened twisted pair Mylar cable...

Page 5: ...he Controller s Top Cover For IPS970 open the Lid of the Cabinet 2 Remove the old 3 V CR2032 Lithium cell Battery from the Battery Holder by pulling the plastic retaining clip AWAY from the Battery Ho...

Page 6: ...e 8 Attach the Controller s Top Cover Database Backup Battery Low On Battery Low when the Controller reaches the end of its 48 Hour Hibernation Mode the Battery reaches a point where it cannot maintai...

Page 7: ...nt of the Lid during installation After installation we strongly recommend you reattach the Earth Strap to the Lid Use the supplied Connection Leads for the low voltage connections to the Power Supply...

Page 8: ...XEC300 0 0 GB 09 September 2015 Page 8 ELECTRICAL CONNECTIONS Key Component Positions Figure 1 Key Component Positions...

Page 9: ...XEC300 0 0 GB 09 September 2015 Page 9 Figure 2 Power Supply Combo IPS970 Layout Diagram Top View...

Page 10: ...C300 0 0 GB 09 September 2015 Page 10 Connecting the Impro ECII Controller Figure 3 shows the Controller s relationship with the rest of the Impro product range Figure 3 Controller Configuration Optio...

Page 11: ...11 Figure 4 shows typical connection options for the Impro EC II Controller Figure 4 Typical Electrical Connections NOTE DO NOT connect daisy chain additional RS485 Controllers on Port 2 as the Syste...

Page 12: ...TS YOU AT RISK OF ELECTRICAL SHOCK CAUTION DO NOT exceed the Input Voltage specified Wiring the Mains Input Power Cord WARNING DO NOT TOUCH ANY PART OF THE CIRCUIT ONCE YOU VE APPLIED POWER TO THE POW...

Page 13: ...Ratings NOTE Because of the delicacy of the replacement procedure we recommend you contact your distributor before trying to replace the Power Supply Fuse Replacing the Battery Fuse CAUTION Ensure th...

Page 14: ...u have upgraded the Controller s firmware since installation ensure that you upgrade again immediately 1 With power applied to the Impro ECII Controller place a link across the pins of the Factory Def...

Page 15: ...site plan by their Fixed Address and MAC Address Labels file the document for future reference IP Address NOTE All Impro ECII Controllers have the same IP Address 192 168 100 1 In the absence of a DH...

Page 16: ...XEC300 0 0 GB 09 September 2015 Page 16 Fixed Address Label Unique Location Description...

Page 17: ...XEC300 0 0 GB 09 September 2015 Page 17 Fixed Address Label Unique Location Description...

Page 18: ...XEC300 0 0 GB 09 September 2015 Page 18 Fixed Address Label Unique Location Description...

Page 19: ...XEC300 0 0 GB 09 September 2015 Page 19 Fixed Address Label Unique Location Description...

Page 20: ...XEC300 0 0 GB 09 September 2015 Page 20 Fixed Address Label Unique Location Description...

Page 21: ...XEC300 0 0 GB 09 September 2015 Page 21 Fixed Address Label Unique Location Description...

Page 22: ...XEC300 0 0 GB 09 September 2015 Page 22 Fixed Address Label Unique Location Description...

Page 23: ...23 Fixed Address Label Unique Location Description Table 2 Unit Location Chart GUARANTEE OR WARRANTY This product conforms to our Guarantee or Warranty details placed on our Web Site to read further p...

Page 24: ...le to the Impro EC II Ethernet Controller XEC900 0 0 GB 06 and IPS970 0 0 GB 05 The last two digits of the Impro stock code indicate the issue status of the product XEC300 0 0 GB 09 Issue 10 Sept 2015...

Reviews: