background image

 

Installation instructions continued 

Relay connection for external alarm 

One solid state relay is accessible for connection via a terminal strip located beneath the units 

lower cover, this terminal strip is clearly visible in fig 1 top of page, if you need to make a 

connection simply knock out the cable entry cut out beneath the relay terminal strip, and fit a 20 

mm cable gland  the relay contacts carry no voltage and are isolated. 

SRC Relay specification 

The relay is an SCR not ideally suited for switching inductive loads; try to use resistive loads 

where possible, such as lights, buzzers, sounders etc. Only AC loads can be switched by the 

relay, the voltage is 12 VAC to 240 VAC, Max current is 2A, Minimum AC load is 60 Ma 

One normally open connection is available; the relay is active when an alarm condition is 

present. 

Relay connection on PCB 

1= 1 Com 

1= 1 out NO 

Powering for the first time 

After connecting the power, the unit requires up to three minutes to stabilize

During this time the monitor alarm circuit is muted and the displayed reading is held low, this is a 

normal and necessary part of installation, after a short time the reading should settle down close 

to zero, any reading from -0.05 to + 0.05 is acceptable. 

Note: It may take up to 24 hours for the reading to stabilize fully, 

if the unit is 

commissioned in an atmosphere containing the target or other gas of the same group a zero 

reading will not be possible, it is therefore advisable to first connect the unit in a place with clean 

air other than the units intended monitoring location. After a low reading is achieved move the 

monitor to its intended location. 

Mounting location 

Before mounting the monitor, experiment with several different locations, this is to avoid 

nuisance alarming, bear in mind a lot of gasses are heavy and tend to concentrate at lower 
levels, if for example two chemicals are present within the monitoring area, site the monitor 

well away from the second chemical, if the room is not adequately ventilated a below alarm 

level will not be possible. 

Avoid mounting the monitor above a source of heat, radiator heating vent etc, fast moving air is 

not representative of the areas average gas value. 

Summary of Contents for BM350

Page 1: ...m User Guide User Guide www impact test com www impact test co uk www impact testsets co uk Methylene Chloride Monitor BM350 Impact Test Equipment Ltd www impact test co uk www impact test com www imp...

Page 2: ...st Equipment Ltd Building 21 Stevenston Ind Est Stevenston Ayrshire KA20 3LR T 01294 602626 F 01294 461168 E sales impact test co uk Test Equipment www impact test co uk Test Sieves Accessories www im...

Page 3: ...oduct description and safety features Installation instructions Power connection Relay connection and mounting location General information and operation Additional Information re sensor performance M...

Page 4: ...requirements The monitor incorporates three fuses one domestic 3 amp plug head fuse and one internal circuit board mounted 1A time delay fuse and one 2A fuse to protect the alarm relay If required an...

Page 5: ...use the monitor Although every effort is made to ensure accuracy this manual may contain technical unintentional technical inaccuracies On behalf of its clients Impact reserve the right to modify the...

Page 6: ...sary where no socket outlet is present firstly ensure the mains lead is not connected isolate the plug so it cannot be connected accidentally loosen the two screws holding the lower cover in place rem...

Page 7: ...he monitor alarm circuit is muted and the displayed reading is held low this is a normal and necessary part of installation after a short time the reading should settle down close to zero any reading...

Page 8: ...evel has been reached Alarm sounder This activates when the alarm state is reached giving a high pitched continuous tone Sensor malfunction LED This alerts the user that a variation away from normal p...

Page 9: ...f the sensor is exposed in extreme conditions such as very high humidity high temperatures or high contamination levels of organic vapours or other gases for a long period of time sensor performance m...

Page 10: ...tests humidity temperature dust etc calibration should occur at least once a year The site manager is responsible for implementing the safety procedures on his site Impact is not responsible for impl...

Page 11: ...e 0 199ppm 0 2000mg m 3 Dimensions 210 x 185 x 110 mm Accuracy 10 Cal level Visual alarm Red alarm led Weight 0 4kg Audio alarm Integrated sounder Response time 30 Seconds Typical 100 ppm Malfunction...

Reviews: