extended by selection of either of the S-ramps:
1 = Accel./decel. time extended by 10%
approx.
2 = Accel./decel. time extended by 20%
approx.
The inverter holds the trip codes of the last four
trips in memory. These are accessed as shown
in the diagram above. When a new trip occurs,
the previous last (fourth) trip is deleted.
For trip codes refer to page 44.
Starting frequency can be set at any value
from 0 up to 15Hz in steps of 1Hz.
NOTE Function 30 = 0 gives 0.2Hz.
Factory-set default is 1.
Torque limitation is set as a percentage of rated
torque computed from Functions 70, 71 and 72.
Setting ranges
0 = No limit (except overcurrent protection)
20 = 20% increasing in steps of 1% to…
180 = 180%
The purpose of this Function is to prevent over-
loading of the braking circuit. Set as follows:
0 = When an external braking circuit is not
used or is not available.
1 = Set to this value when installing an exter-
nal braking circuit.
NOTE External braking is not available with
the VXS20-1 inverter.
32
29 Protection history
Display example
(first select Function 29)
Press
Overvoltage
Undervoltage
FUNC
DATA
for up to 4 trip codes max.
To return to RUN mode press
To go to Function 30 press
FUNC
DATA
PRG
RESET
30 Starting frequency
31 Torque limit during accel./decel.
32 Torque limit at constant speed
33 Braking torque selector
WARNING Accel./decel. times and
speed settings may be altered by
inappropriate settings of the torque
limits. Ensure that the inverter is
commissioned with care if torque
limits are set.
If in any doubt, consult IMO
Precision Controls Ltd.