10
2-1
2
INSTALLATION
2.1 CHOOSING THE PLACE OF
INSTALLATION.
Floor strength
• Withstands a load of 400 kg at least (surface below boiler)
Note:
only install a water storage tank under the water heater when this is positioned above in
residential buildings.
The installation area shall be suitable for protection index IPX1B.
Non-ducted or
semi-ducted configuration
Ducted configuration
Type of installation room
Room examples
Volume of room where air is extracted
Temperature of water heater installation
room
Air inlet temperature
Ceiling height
Surface area required
• Unheated room, characterised by temperature
exceeding 5°C and preferably insulated from
the home's heated rooms.
• Recommended room = underground or base-
ment, room where the temperature is higher
than 10°C all year round.
• garage, boiler room (with the exception of
rooms where type B generators are installed),
basement floor, ironing room, etc.
• Volume > 20 m
3
• from 5°C to 43°C.
• -5°C to 43°C.
• > 2.10 m.
• 2.10 m
2
(Fig. 2-1).
• Crucial for the surface to be level.
•
Room at least frost-free.
• Recommended room = living space (the heat
loss from the water heater is not wasted), close
to the outer walls.
• Do not install close to sleeping areas because of
the noise produced.
• laundry room, cellar, cupboard in entrance hall, etc.
• /
• > 1°C.
• -5°C to 43°C.
• > 2.10 m.
• 2.10 m
2
(Fig. 2-1).
• Crucial for the surface to be level.
"Non ducted" configuration
"Ducted" configuration
"Non ducted" configuration
"Ducted" configuration
min. 400
min. 400
min. 50
min. 50
min. 300
min. 300