Hydraulic connection.
Attention:

 in order not to void the heat primary 

exchanger warranty, before making the boiler 

connections, carefully clean the heating system 

(pipes, radiators, etc.) with special pickling or 

de-scaling products to remove any deposits that 

could compromise correct boiler operation.
A chemical treatment of the thermal system 

water is required, in compliance with the 

technical standards in force, in order to protect 

the system and the appliance from deposits (e.g., 

limescale), slurry or other hazardous deposits.
Water connections must be made in a rational way 

using the couplings on the boiler template. The 

boiler safety valve outlet must be connected to an 

appropriate drain. Otherwise, the manufacturer 

declines any responsibility in case of flooding if 

the drain valve cuts in.
In order to meet the system requirements 

established by the regulations in terms of 

pollution of drinking water, we recommend 

installing the IMMERGAS anti-backflow kit to be 

used upstream of the cold water inlet connection 

of the boiler. It is also recommended that the heat 

transfer fluid (e.g. water + glycol) entered in the 

primary circuit of the boiler (heating circuit), 

complies with the local regulations in force.

Attention: 

to preserve the duration of appliance 

efficiency features, in the presence of water whose 

features can lead to the deposit of lime scale, 

installation of the “polyphosphate dispenser” kit 

is recommended.

Electrical connection.

 The Nike Mythos 24 2E 

boiler has an IPX4D protection rating for the 

entire appliance. Electrical safety of the appliance 

is reached only when it is correctly connected 

to an efficient earthing system as specified by 

current safety standards.

Attention:

 Immergas S.p.A. declines any 

responsibility for damage or physical injury 

caused by failure to connect the boiler to an 

efficient earth system or failure to comply with 

the reference standards.
Also ensure that the electrical installation 

corresponds to maximum absorbed power 

specifications as shown on the boiler data-plate. 

Boilers are supplied complete with an “X” type 

power cable without plug. The power supply 

cable must be connected to a 230V ±10% / 50Hz 

mains supply respecting L-N polarity and earth 

connection; 

, this network must also have a 

multi-pole circuit breaker with class III over-

voltage category.

When replacing the power supply cable, contact a 

qualified company (e.g. the Immergas Authorised 

After-Sales Technical Assistance Service). The 

power cable must be laid as shown (Fig. 1-3). In 

the event of mains fuse replacement on the P.C.B., 

use a 2A quick-blow fuse. For the main power 

supply to the appliance, never use adapters, 

multiple sockets or extension leads.

1.4  REMOTE CONTROLS AND 

ROOM CHRONO-THERMOSTATS 

(OPTIONAL).

The boiler is prepared for the application of room 

chrono-thermostats or remote controls, which 

are available as optional kits. (Fig. 1-4)

All Immergas chrono-thermostats are connected 

with 2 wires only. Carefully read the user and 

assembly instructions contained in the accessory 

kit.

•  On/Off digital chrono-thermostat. The chrono-

thermostat allows:

  - set two room temperature value: one for 

daytime (comfort temperature) and one for 

nighttime (lower temperature);

  - set a weekly programme with four daily 

switch on and switch off times;

  -  select the required operating mode from the 

various possible alternatives:

  -  manual mode (with adjustable temperature);
  - automatic mode (with set programme);
  - forced automatic mode (momentarily 

changing the temperature of the automatic 

programme).

  The chrono-thermostat is powered by two 1.5V 

LR 6 type alkaline batteries.

• Comando Amico Remoto Remote Control 

Device 

V2

 (CAR

V2

) with climate chrono-

thermostat function. In addition to the 

functions described in the previous point, the 

CAR

V2

 panel enables the user to control all the 

important information regarding operation 

of the appliance and the heating system with 

the opportunity to easily intervene on the 

previously set parameters, without having 

to go to where the appliance is installed. 

The panel is provided with self-diagnosis to 

display any boiler functioning anomalies. 

The climate chrono-thermostat incorporated 

into the remote panel enables the system flow 

temperature to be adjusted to the actual needs 

of the room being heated, in order to obtain 

the desired room temperature with extreme 

precision and therefore with evident saving in 

running costs. The chrono-thermostat is fed 

directly by the boiler by means of the same 2 

wires used for the transmission of data between 

boiler and chrono-thermostat.

CAR

V2

 or chrono-thermostat On/Off electric 

connection (Optional).

 

The operations described 

below must be performed after having removed 

the voltage from the appliance.

 Any On/Off room 

chrono-thermostat must be connected to clamps 

40 and 41 eliminating jumper X40 (Fig. 3-2). 

Make sure that the On/Off thermostat contact is 

of the “clean” type, i.e. independent of the mains 

supply, otherwise the P.C.B. would be damaged. 

Any CAR

V2

 must be connected to clamps 40 and 

41 eliminating jumper X40 on the circuit board, 

paying attention not to invert the polarity in the 

connections (Fig. 3-2). 3-2). Connection with 

the wrong polarity prevents functioning, but 

without damaging the CAR

V2

 The boiler can only 

be connected to one remote control.

Important:

 if the CAR

V2

 remote control is used, 

arrange two separate lines in compliance with 

current regulations regarding electrical systems. 

No boiler pipes must ever be used to earth 

the electric system or telephone lines. Ensure 

elimination of this risk before making the boiler 

electrical connections.

Fig. 1-3

Fig. 1-4

POWER SUPPLY CABLE

Summary of Contents for NIKE MYTHOS 24 2 E

Page 1: ...NIKE MYTHOS 24 2 E IE Instruction and warning book 1 038789ENG ...

Page 2: ... technical information for installing Immergas boilers As for the other issues related to boiler installation e g safety in the work site environment protection injury prevention it is necessary to comply with the provisions specified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within th...

Page 3: ...ing 11 2 6 Restoring central heating system pressure 11 2 7 System draining 11 2 8 Anti freeze protection 12 2 9 Case cleaning 12 2 10 Decommissioning 12 3 Boiler commissioning initial check 13 3 1 Hydraulic diagram 13 3 2 Wiring diagram 14 3 3 Troubleshooting 14 3 4 Converting the boiler to other types of gas 15 3 5 Checks following conversion to another type of gas 15 3 6 Possible adjustments 15...

Page 4: ...of malfunctions faults or incorrect operation turn the appliance off immediately and contact an authorised company e g the Immergas Technical Assistance centre which has specifically trained staff and original spare parts Do not attempt to modify or repair the appliance alone Failure to comply with the above implies personal responsibility and invalidates the warranty Installation regulations thes...

Page 5: ... gas cock connection by following the mounting instructions illustrated in the figure The gas supply pipe must be suitably dimensioned according to current regulations in order to guarantee correct gas flow to the burnereveninconditionsofmaximumgenerator output and to guarantee appliance efficiency technical specifications The coupling system must conform to standards Fuel gas quality The applianc...

Page 6: ... 1 4 REMOTE CONTROLS AND ROOM CHRONO THERMOSTATS OPTIONAL The boiler is prepared for the application of room chrono thermostats or remote controls which are available as optional kits Fig 1 4 All Immergas chrono thermostats are connected with 2 wires only Carefully read the user and assembly instructions contained in the accessory kit On Offdigitalchrono thermostat Thechrono thermostat allows set ...

Page 7: ...responding to the top of the chimney flue independently of any caps must be out of the backflow area in order to prevent the formation of counter pressures that impede the free discharge of the combustion products into the atmosphere It is therefore necessary to use the minimum heights indicated in the figures stated in the regulation depending on the slope of the roof Direct exhaust outside The n...

Page 8: ...p on first speed To ensure optimal boiler operation in the case of new systems single pipe and module it is recommended to use the pump at maximum speed The circulation pump is already fitted with a capacitor Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew the front cap and turn the motor shaft using a screwdriver Take great care during this operation...

Page 9: ... 5 Gas valve 6 System filling valve 7 Flue safety thermostat 8 Primary heat exchanger 9 Delivery probe 10 Safety thermostat 11 Combustion chamber 12 Ignition and detection electrodes 13 System expansion vessel 14 Burner 15 Vent valve 16 By pass 17 DHW heat exchanger 18 Three way valve motorised 19 3 bar safety valve 20 System draining valve N B connection group optional ...

Page 10: ... or other devices Never clean the appliance or connected parts with easily flammable substances Never leave containers or flammable substances in the same environment as the appliance It is prohibited and dangerous to obstruct the air intake even partially for the ventilation of the room in which the boiler is installed Due to the danger functioning is also prohibited in the same room as suction d...

Page 11: ... hours code 03 it is necessary to reset the boiler manually by pressing the Reset button 1 If this anomaly persists contact a qualified technician for assistance e g Immergas After Sales Service Electro mechanical contacts This occurs when thesafetythermostat thefumepressureswitchor the system pressure switch do not work properly code 04 The boiler does not start try resetting the boiler If the an...

Page 12: ... a prolonged absence the system must be drained completely or antifreeze substances must be added to the heating system water In both cases the boiler domestic hot wa ter circuit must be drained In systems that are drained frequently filling must be carried out with suitably treated water to eliminate hardness that can cause lime scale 2 9 CASE CLEANING Use damp cloths and neutral detergent to cle...

Page 13: ...iance e g a draught gauge positioned at the exit of the appliance combustion products check that there is no backflow of combustion products into the room even during functioning of fans 3 1 HYDRAULIC DIAGRAM Fig 3 1 ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modified check the production of domestic hot water check sealing efficiency of w...

Page 14: ...ermostat It can depend on the lack of water in the boiler little water circulation in the system or blocked pump Check on the manometer that the system pressure is within established limits Check that the radiator valves are not closed and also the functionality of the pump The boiler produces condensate This can be caused by obstructions of the chimney or flues with height or section not proporti...

Page 15: ...se direction the heating potential increases and in an anti clockwise direction it decreases Adjust the boiler minimum heat output in the domestic hot water phase Fig 3 3 N B only proceed after having calibrated the nominal pressure Adjustment of the minimum thermal input is obtained by operating on the cross plastic screws 2 on the gas valve maintaining the brass nut blocked 3 disconnect the powe...

Page 16: ... boiler 2 monothermal boiler with boiler P9 3 8 AUTOMATIC SLOW IGNITION FUNCTION WITH TIMED RAMP DELIVERY In the ignition phase the P C B carries out an increasing gas delivery ramp with pressure values that depend on the type of gas selected with preset duration This prevents every calibration or precision adjustment of the boiler ignition phase in any conditions of use 3 9 CHIMNEY SWEEP FUNCTION...

Page 17: ...ing can be completely removed as follows Fig 3 4 remove the frame 1 holding the edges and pulling it towards you as indicated by the arrows undo the 2 front screws 2 and the 2 lower screws 3 which fasten the casing 4 pull the casing 4 towards yourself and upwards at the same time in order to detach it from the upper hooks ...

Page 18: ... be inside the fairleads there must be no traces of blackening or burning N B when performing periodical maintenance of the appliance it is also good practice to check and perform maintenance on the heating system in compliance with that indicated by the regulations in force N B gas flow rates refer to heating power below a temperature of 15 C and pressure of 1013 mbar Burner pressure values refer...

Page 19: ...justable central heating temperature C 38 85 System expansion vessel total volume l 4 2 Expansion vessel factory set pressure bar 1 Water content in generator l 1 9 Head available with 1000 l h flow rate kPa m H2 O 24 5 2 5 Hot water production useful heat output kW kcal h 23 6 20296 Domestic hot water adjustable temperature C 30 38 60 77 Domestic hot water circuit flow limiter at 2 bar l min 7 7 ...

Page 20: ...ode Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum heating capacity domestic Qn min Minimum heating capacity heating Qnw max Maximum heating capacity domestic Qn max Maximum heating capacity heating Pn min Minimum heat output Pn max Maximum heat output PMS Maximum pressure system PMW Maximum pressure domestic D Specific flow rate TM Maximum ...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038789ENG rev ST 002138 000 07 15 Inglese per IRLANDA IE ...

Reviews: