![Immergas EOLO Maior kW Manual Download Page 40](http://html.mh-extra.com/html/immergas/eolo-maior-kw/eolo-maior-kw_manual_2047764040.webp)
38
STEkW ed 12/06
EOLO Maior kW
Technical Documentation
Technical Documentation
Permanent timing reduction.
The boiler is fitted with an
electronic timer that prevents the burner igniting too frequently
in the central heating phase.
The boiler is supplied with a timer as a standard feature, set
at 180 seconds.
Central heating ignitions timer
(continuous variation)
LED flashing
(slow)
30 seconds
LED 2
55 seconds
LED 3
80 seconds
LED 4
105 seconds
LED 5
130 seconds
LED 6
155 seconds
LED 7
180 seconds
(Standard setting)
LED 8
205 seconds
LED 9
230 seconds
LED 10
255 seconds
LED 11
Central heating ramp timing.
The boiler supplies the maxi-
mum output set in the previous parameter.
The boiler executes an ignition ramp of about 650 seconds to
go from minimum to maximum central heating output.
Central heating ignitions timer
(continuous variation)
LED flashing
(slow)
65 seconds
LED 2
130 seconds
LED 3
195 seconds
LED 4
260 seconds
LED 5
325 seconds
LED 6
390 seconds
LED 7
455 seconds
LED 8
520 seconds
LED 9
585 seconds
LED 10
650 seconds
(Standard setting)
LED 11
Central heating ignitions delayed due to Room thermostat
or Remote control requests.
The boiler is set to turn on im-
mediately after a request.
In the case of particular systems
(i.e. zone systems with mo-
torised thermostat valves, etc.)
it might be necessary to delay
ignition.
Central heating ignitions delayed due to
Room thermostat or Remote control reque-
sts
(continuous variation)
LED flashing
(slow)
0 seconds
(Standard setting)
LED 2
57 seconds
LED 3
113 seconds
LED 4
170 seconds
LED 5
226 seconds
LED 6
283 seconds
LED 7
340 seconds
LED 8
396 seconds
LED 9
453 seconds
LED 10
510 seconds
LED 11
Domestic hot water thermostat.
With the setting of the
“correlated” thermostat the boiler switches off according to
the temperature set with the domestic hot water adjustment
knob.
On the other hand, with the setting of the “fixed” domestic
hot water thermostat, the switching off temperature is set at
65°C.
Domestic hot water thermostat
LED flashing
(slow)
Correlated
(Standard setting)
LED 2
Fixed
LED 11
Circulator function.
Two circulator functioning modes can
be selected in the central heating phase.
In the “intermittent” mode, it is activated either by the room
thermostat or by the Remote control, in the “continuative”
mode the circulator works all the time when the main selector
switch is on heating.
Circulator function
LED flashing
(slow)
Intermittent
(Standard setting)
LED 2
Continuous
LED 11