Immergas 3.030072 Instructions And Warnings Download Page 22

22

4

 RECOMMENDATIONS 

- MAINTENANCE AND 

REPAIRS

4.1  ADVICE FOR THE USER.

You must empty the water heater if the absence 

mode cannot be used or when the device is 

powered down. Proceed in the following way:

• Cut the power supply.
• Close the cold water inlet tap.
• Open a hot water tap.
• Put the safety valve in the drain position.

Important note - End of the device’s service life:

• At the end of its service life, the device must 

be taken to a sorting centre for electrical and 

electronic equipment for recovery of fluids. 

Do not dispose of the device with household 

waste, but dispose of it in the collection cen-

tres provided, where it can be recycled. Check 

your local collection service to find out about 

existing waste collection centres. 

• It is forbidden by law to discharge into the 

atmosphere the cooling fluid contained in the 

appliance. Degassing operations are strictly 

forbidden, and may be hazardous.

N.B.:

 the GWP (Global Warming Potential) of 

R513A is 631.

4.2  HOUSEHOLD MAINTENANCE.

The user must perform some minor home main-

tenance operations on the water heater: act on the 

safety valve once or twice a month to remove any 

limestone deposits and ensure it is not blocked.
Regularly check that there are no alarms on the 

display. If there are any alarms, contact the au-

thorised local service centre to address the faults.

It is recommended to treat water with a softener 

in the areas where there is a high amount of scale 

(Th>20°f). 

Water hardness must remain above 

15°f.

 The softener does not lead to warranty der-

ogations, provided it is dosed in a workmanlike 

manner and regularly maintained.

Water treatment must comply with the National/

local provisions in force.

4.3  MAINTENANCE BY APPROVED 

PROFESSIONALS.

The appliance must be checked by a profession-

al every 2 years, in order to ensure its long-term 

performance

.

• Disconnect the appliance from the electricity 

(circuit-breaker, fuses, etc.)

• Drain the tank:
  -  close the cold water inlet tap of the safety unit,
  - open a hot water tap,
  - put the safety valve in the drain position.
• Remove the front cover. 
• Disconnect the wires from the thermostat 

terminals.

• Dismantle the heating unit.
•  Replace the magnesium anode. The magnesium 

anode has to be changed every 2 years or as 

soon as its diameter is less than 10mm. 

• Remove the scale deposited as sludge or flakes 

in the bottom of the tank, and carefully clean 

the casings of the heating elements and ther-

mostat. Do not scratch or remove the scale 

attached to the walls, as this could affect the 

coating. Residues may be removed using a 

water and dust vacuum cleaner.

•  Refit the heating unit with a new seal, carefully 

and gradually tightening the nuts (cross-tight-

ening).

• Fill the water heater by leaving a hot water tap 

open, if the water flows it indicates that the 

water heater is full.

• Check the water tightness of the seal and only 

then replace the thermostat and its fittings, and 

reconnect the power supply.

• The next day, check the water tightness of the 

seal again and gently tighten the nuts again if 

necessary.

• Check the electrical connections.
• Check that the temperature probe is properly 

positioned in the sample point near to the 

electrical integration (the probe must be at the 

bottom of the sample point).

Evaporator:

• The cleanliness of the evaporator and the fan 

must be checked 

every year

. Clogging of these 

components may reduce the performance of 

the heat pump.

• Unscrew and remove the front cover to access 

the evaporator. The rear cover may also be 

removed if necessary.

• If necessary, the evaporator and the fan are to 

be cleaned with a soft bristle brush. Brush the 

evaporator very gently to avoid damaging its 

fins. If the fins are folded, straighten them using 

a suitable brush.

Note:

 always disconnect the device from the 

power supply before starting any work.

Expansion valve:

• Only a refrigeration engineer is permitted to 

access the expansion valve adjustment screw. 

If the expansion valve is adjusted without 

approval from the manufacturer, the product 

warranty shall be voided.

• Generally speaking, it is not recommended to 

change the expansion valve setting before all 

other repair solutions have been exhausted.

Condensate draining pipe:

•  Check cleanliness of the condensate evacuation 

pipe. Any pollution (dust) in the room may in 

fact cause deposits in the condensate recovery 

tank. These deposits may block the condensate 

evacuation tube, and cause excessive accumu-

lation of water in the tank, which could lead to 

malfunctions.

4.4  TROUBLESHOOTING SUPPORT.

Control panel alarm codes

Errors can be suspended or reactivated by 

pressing “OK”.

This action also stops the buzzer. 

Error 

Code

Cause

Consequences

System status / Solution

03

Faulty water 

temperature probe or 

out of measurement 

range

Water temperature reading impossible: no central heating / C.H.

Check the connection (reference A1) of the wa-

ter temperature probe (sample point). Check 

the resistance of the probes (see table below). 

If necessary, replace the probe.

07

No water in the 

storage tank or ACI 

connection open

No warming up.

Put the storage tank in the water.

Check the thread connection (reference AC), 

conductivity of the water.

09

Water temperature too 

hot (T> 80°C)

Risk of mechanical safety device activation: no central heating / 

C.H.

Check if the real water temperature at the sam-

ple point is high (T>80°C).

Check the connection (reference A1) and the 

positioning of the water temperature probe 

(sample point), it must be at end run.

Check that the electrical integration is not 

permanently fed. Reset the mechanical safety, if 

necessary.

Summary of Contents for 3.030072

Page 1: ...RAPAX 200 V3 RAPAX 200 SOL V3 RAPAX 300 V3 RAPAX 300 SOL V3 IE Instructions and warnings Installer User Maintenance technician 1 043869ENG 1 043869ENG...

Page 2: ...alve 7 Fan 8 Compressor 9 User terminal board 10 Immersion heater 11 Domestic hot water sensor 12 High pressure sensor 13 Compressor protection thermostat 14 Compressor engage condenser Colour code ke...

Page 3: ...ed by excessive pressure due to the safety valve blocking because of ice Ensuretheflooronwhichthe appliance is to be installed is suitable to withstand the appliance s own weight and that of the water...

Page 4: ...exceed 0 3 MPa 3 bars and its max temperature must not exceed 85 C To perform any discharge operations of the water heater strictlyadheretothefollowing sequence disconnect the appliance from the elect...

Page 5: ...ntenance must be performed in compliance with the regulations in force according to the manufacturer s instructions and by professionally qualified staff intended as staff with specific technical skil...

Page 6: ...d components 8 2 Installation 10 2 1 Choosing the place of installation 10 2 2 Product installation 13 2 3 Hydraulic connection 13 2 4 Air intake connection 14 2 5 Electrical connection 14 2 6 Electri...

Page 7: ...ified staff only POSITIONS ALLOWED DURING TRANSPORT POSITIONS NOT ALLOWED DURING TRANSPORT Technical characteristics Unit of measurement Rapax 200 V3 Rapax 200 SOL V3 Rapax 300 V3 Rapax 300 SOL V3 Dim...

Page 8: ...urn to solar panels Rapax Sol V3 model only SC Condensate drain 20 RC 3 4 M Recirculation Rapax Sol V3 model only Ref Description Rapax 200 V3 Rapax 200 Sol V3 Rapax 300 V3 Rapax 300 Sol V3 A Condensa...

Page 9: ...piral unit 9 Fan 10 Spiral elastic 11 Terminal board unit Not shown manual dielectric connection con densate draining pipe safety unit 12 Front cover 13 Compressor 14 Compressor coating 15 Compressor...

Page 10: ...ferably insulated from the home s heated rooms Recommended room underground or base ment room where the temperature is higher than 10 C all year round garage boiler room with the exception of rooms wh...

Page 11: ...and recovery of waste calories from washing machines and tumble dryers Room in basement recovery of free calories released by the floor and walls of the base ment 2nd configuration installation in a h...

Page 12: ...y harmful for the duration in service of your water heater Connection to an attic In the presence of inadequate insulation between the building and the relative attics this type of installation may in...

Page 13: ...th a permanent downward gradient to remove any expansion water generated by the heating process or drainage water coming from the water heater itself The pipes used must withstand a temperature of 85...

Page 14: ...ductors with 2 5 mm section Installation shall consist of a circuit breaker or 16A multi pole fuse with contacts compliant with regulations in force A 30 mA differential circuit breaker If the power c...

Page 15: ...15 2 11 2 12 The ducts must be fitted to the adjustable air intake and outlet vents Specific cable duct...

Page 16: ...B B2 DHW probe K1 Domestic hot water unabling relay R1 Resistance 2 2 K Key A3 Integrated P C B B2 DHW probe N B With this configuration the boiler can show an error on the domestic probe Power suppl...

Page 17: ...e screen Follow the on screen instructions carefully to set parameters date and time air ducts language recirculation photovoltaic operating time slots anti legionella system After setting the paramet...

Page 18: ...1 Flat solar collectors 2 Electronic control unit 3 solar unit single circulation 4 Expansion vessel 5 Safety valve 6 System probe and venting unit 7 Mixing valve 8 Rapax Sol V3 Water heater 9 Non ret...

Page 19: ...sumes operation with the initial settings The BOOST can be interrupted at any time Pause the BOOST OPERATING mode Choose the operating mode Select AUTO or MANUAL see paragraph 3 6 Operating modes ABSE...

Page 20: ...ate or not the electrical integration support If it is off the device will never use the electrical integration in case of low temperatures a shortage of hot water is possible 3 6 SELECTING THE OPERAT...

Page 21: ...temperature in the tank Our product permanently calculates depending on the air temperature and the water temperature which energy is cheaper This SMART Energy function can decide to start heating wi...

Page 22: ...ing Fill the water heater by leaving a hot water tap open if the water flows it indicates that the water heater is full Check the water tightness of the seal and only then replace the thermostat and i...

Page 23: ...or out of measurement range from 20 to 110 PDC stoppage Central heating C H in ELEC Check the connections reference A4 and the correct application of the probe on the pipe Check the fan operation and...

Page 24: ...aporator works on the fan works on the compressor etc N B it is essential to disconnect the power cable on the terminal board so that the rear cover of the heat pump can be removed Fig 4 2 Remove the...

Page 25: ...an the filter see maintenance chapter Encrusted water heater Descale the water heater Continued water leak to the level of the safety unit outside the heating period Safety valve damaged or clogged Re...

Page 26: ...f calibration etc Insulating sheath cast iron steel or insulat ing missing on hot water connection pipes which could cause their corrosion Faulty electrical connection incorrect earth ing inadequate c...

Page 27: ...ditions 116 Energy efficiency in colder climate conditions 96 Energy efficiency in warmer climate conditions 130 Annual energy consumption in average climate conditions 883 kW h Annual energy consumpt...

Page 28: ...iency in colder climate conditions 100 Energy efficiency in warmer climate conditions 141 Annual energy consumption in average climate conditions 1334 kW h Annual energy consumption in colder climate...

Page 29: ...al energy efficiency after installation since such efficiency is affected by additional factors such as the heat loss in the distribution system and the size of the products compared to the size and f...

Page 30: ...38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy efficiency of the set of products indicated in this sheet may not reflect the actual energy...

Page 31: ...31...

Page 32: ...llo RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper This instruction booklet is made of ecological paper Cod 1 043869ENG rev ST...

Reviews: