Immergas 3.030072 Instructions And Warnings Download Page 14

14

Solar circuit connection.

N.B.:

 protect from overpressure caused by water 

expansion during heating with a 0.6 MPa (6 bars) 

valve, and with a closed diaphragm expansion 

vessel. The operating pressure of the circuit must 

not exceed 0.6 MPa (6 bars), and its temperature 

must not be higher than 100°C. A glycol mixture 

must be provided as heat transfer fluid for frost 

and corrosion protection.

Removing the condensate.

N.B.:

 cooling of the circulating air in contact with 

the evaporator results in the water contained in 

the air condensing. The condensed water flowing 

down the back of the heat pump must be removed 

from it and conveyed into suitable plastic pipes.

On the basis of air humidity, 

up to 0.5 l/h of con-

densate may be formed

. The condensate run-off 

must not be conveyed into the drain, since the 

ammonia fumes that flow back from the drain 

could damage the heat exchanger fins and parts of 

the heat pump.

It is therefore obligatory to fit a siphon for the 

discharge of waste water (do not use the pipe 

supplied under any circumstances to make a 

siphon). This connection must not in any case 

be included in the safety unit.

2.4  AIR INTAKE CONNECTION.

When the volume of the room where the boiler is 

installed is less than 20 m

3

, the appliance may be 

connected to air ducts with diameter 160 mm. If 

these ducts are not insulated, condensate might 

form in them during appliance operation.

It is therefore essential to choose insulated air 

ducts 

(Fig. 2-11).

Poor-quality air ducts (crushed, too long, or 

with too many bends, etc.) may cause a loss of 

performance.

Flexible ducts are therefore definitely not 

recommended

.

N.B.:

 if there are connections to the ducts, adjust 

fan settings accordingly.

N.B.:

 the overall head loss on ducts and fittings 

for discharge and intake of air 

must be less than 

130 Pa

. Calculation of load losses must be made 

using the measurement instruments supplied 

by the manufacturer, in accordance with the 

proposed ducting accessories.

N.B.:

 adjustable outlets may allow the use of 

ducting bends to be reduced or dispensed with 

altogether. For additional information on adjust-

able outlets, see Parag. 2.2.

2.5  ELECTRICAL CONNECTION.

Note:

 the water heater can be electrically con-

nected only after being filled with water.

Note:

 do not fit a programming clock or timing 

devices that may interrupt the device's power 

supply upstream of the water heater’s electrical 

connection.
The water heater can be connected and operated 

only with single-phase 230V AC power supply. 

Connect the boiler with a cable having conductors 

with 2.5 mm² section. Installation shall consist of: 
- a circuit breaker or 16A multi-pole fuse with 

contacts compliant with regulations in force.

- A 30 mA differential circuit breaker.
If the power cable is damaged, for safety reasons 

it must be replaced by the manufacturer, the 

after-sales service or similarly qualified staff.

N.B.:

 earthing is obligatory.

Do not connect the power supply directly to the 

electrical resistance.
The safety thermostat with which the electrical 

integration is fitted must not be tampered with; if 

required, it may be repaired/serviced exclusively 

by skilled and qualified staff, according to the 

instructions provided by Immergas. 

Failure to comply with this clause shall void 

the warranty

.

The appliance must be installed in compliance 

with the provisions of the regulations in force.

Installation with connection to a Plus boiler 

(model “SOL”).

In the “SOL” version, the internal heat exchanger 

may be used in alternative to Solar connection, 

to connect a boiler.

There is a pre-arrangement for electrical connec-

tion to the boiler, to be made through terminals 

C1 and C2 (clean contact); this contact might be 

placed in series with the NTC probe connection 

of a Plus (although this will lead to DHW probe 

anomaly on the boiler - until there is no demand 

and the probe is therefore interrupted). 

The boiler is triggered with intake air tempera-

tures outside the correct RAPAX operation range, 

or if the BOOST mode is active.

Photovoltaic self-consumption contact.

The water heater is equipped with a contact to 

fully exploit the electricity produced by the PV 

system, in order to accumulate thermal energy 

within the storage tank (self-consumption).

Having an inverter/electronic device which 

supplies a signal when PV production exceeds 

a certain value at least higher than 450W, when 

this contact is closed the boiler is triggered in heat 

pump mode to heat the DHW up to 62°C, as long 

as it is within the allowable ambient temperature 

values (-5°C +43°C).

When the photovoltaic contact is opened, the 

system goes back to the previous settings only 

after about 5 minutes, to avoid alternating op-

eration caused by clouds or temporary shadows

.

See the instructions for removing the front 

cover, and for access to the terminal block see 

paragraph 4.5.

N.B.:

 A cable channel is provided specifically 

for this connection. Ensure it is used (Fig. 2-12).

External/External Coating

Type configurations

Air Outlets / Inlets 

Roof

Wall-mounted

Roof

Wall-mounted

Roof

Wall-mounted

Max.

Lengths

L1 + L2

Isolated semi-rigid gal-

vanic sheath Ø 160 mm

12 m

12 m

5 m

10 m

PEHD Sheath 

Ø 160 mm

28 m

26 m

16 m

24 m

N.B.:

 the adjustable vents can allow to reduce or eliminate the use of coating elbows. 

LENGTH OF THE AUTHORISED SHEATH

Summary of Contents for 3.030072

Page 1: ...RAPAX 200 V3 RAPAX 200 SOL V3 RAPAX 300 V3 RAPAX 300 SOL V3 IE Instructions and warnings Installer User Maintenance technician 1 043869ENG 1 043869ENG...

Page 2: ...alve 7 Fan 8 Compressor 9 User terminal board 10 Immersion heater 11 Domestic hot water sensor 12 High pressure sensor 13 Compressor protection thermostat 14 Compressor engage condenser Colour code ke...

Page 3: ...ed by excessive pressure due to the safety valve blocking because of ice Ensuretheflooronwhichthe appliance is to be installed is suitable to withstand the appliance s own weight and that of the water...

Page 4: ...exceed 0 3 MPa 3 bars and its max temperature must not exceed 85 C To perform any discharge operations of the water heater strictlyadheretothefollowing sequence disconnect the appliance from the elect...

Page 5: ...ntenance must be performed in compliance with the regulations in force according to the manufacturer s instructions and by professionally qualified staff intended as staff with specific technical skil...

Page 6: ...d components 8 2 Installation 10 2 1 Choosing the place of installation 10 2 2 Product installation 13 2 3 Hydraulic connection 13 2 4 Air intake connection 14 2 5 Electrical connection 14 2 6 Electri...

Page 7: ...ified staff only POSITIONS ALLOWED DURING TRANSPORT POSITIONS NOT ALLOWED DURING TRANSPORT Technical characteristics Unit of measurement Rapax 200 V3 Rapax 200 SOL V3 Rapax 300 V3 Rapax 300 SOL V3 Dim...

Page 8: ...urn to solar panels Rapax Sol V3 model only SC Condensate drain 20 RC 3 4 M Recirculation Rapax Sol V3 model only Ref Description Rapax 200 V3 Rapax 200 Sol V3 Rapax 300 V3 Rapax 300 Sol V3 A Condensa...

Page 9: ...piral unit 9 Fan 10 Spiral elastic 11 Terminal board unit Not shown manual dielectric connection con densate draining pipe safety unit 12 Front cover 13 Compressor 14 Compressor coating 15 Compressor...

Page 10: ...ferably insulated from the home s heated rooms Recommended room underground or base ment room where the temperature is higher than 10 C all year round garage boiler room with the exception of rooms wh...

Page 11: ...and recovery of waste calories from washing machines and tumble dryers Room in basement recovery of free calories released by the floor and walls of the base ment 2nd configuration installation in a h...

Page 12: ...y harmful for the duration in service of your water heater Connection to an attic In the presence of inadequate insulation between the building and the relative attics this type of installation may in...

Page 13: ...th a permanent downward gradient to remove any expansion water generated by the heating process or drainage water coming from the water heater itself The pipes used must withstand a temperature of 85...

Page 14: ...ductors with 2 5 mm section Installation shall consist of a circuit breaker or 16A multi pole fuse with contacts compliant with regulations in force A 30 mA differential circuit breaker If the power c...

Page 15: ...15 2 11 2 12 The ducts must be fitted to the adjustable air intake and outlet vents Specific cable duct...

Page 16: ...B B2 DHW probe K1 Domestic hot water unabling relay R1 Resistance 2 2 K Key A3 Integrated P C B B2 DHW probe N B With this configuration the boiler can show an error on the domestic probe Power suppl...

Page 17: ...e screen Follow the on screen instructions carefully to set parameters date and time air ducts language recirculation photovoltaic operating time slots anti legionella system After setting the paramet...

Page 18: ...1 Flat solar collectors 2 Electronic control unit 3 solar unit single circulation 4 Expansion vessel 5 Safety valve 6 System probe and venting unit 7 Mixing valve 8 Rapax Sol V3 Water heater 9 Non ret...

Page 19: ...sumes operation with the initial settings The BOOST can be interrupted at any time Pause the BOOST OPERATING mode Choose the operating mode Select AUTO or MANUAL see paragraph 3 6 Operating modes ABSE...

Page 20: ...ate or not the electrical integration support If it is off the device will never use the electrical integration in case of low temperatures a shortage of hot water is possible 3 6 SELECTING THE OPERAT...

Page 21: ...temperature in the tank Our product permanently calculates depending on the air temperature and the water temperature which energy is cheaper This SMART Energy function can decide to start heating wi...

Page 22: ...ing Fill the water heater by leaving a hot water tap open if the water flows it indicates that the water heater is full Check the water tightness of the seal and only then replace the thermostat and i...

Page 23: ...or out of measurement range from 20 to 110 PDC stoppage Central heating C H in ELEC Check the connections reference A4 and the correct application of the probe on the pipe Check the fan operation and...

Page 24: ...aporator works on the fan works on the compressor etc N B it is essential to disconnect the power cable on the terminal board so that the rear cover of the heat pump can be removed Fig 4 2 Remove the...

Page 25: ...an the filter see maintenance chapter Encrusted water heater Descale the water heater Continued water leak to the level of the safety unit outside the heating period Safety valve damaged or clogged Re...

Page 26: ...f calibration etc Insulating sheath cast iron steel or insulat ing missing on hot water connection pipes which could cause their corrosion Faulty electrical connection incorrect earth ing inadequate c...

Page 27: ...ditions 116 Energy efficiency in colder climate conditions 96 Energy efficiency in warmer climate conditions 130 Annual energy consumption in average climate conditions 883 kW h Annual energy consumpt...

Page 28: ...iency in colder climate conditions 100 Energy efficiency in warmer climate conditions 141 Annual energy consumption in average climate conditions 1334 kW h Annual energy consumption in colder climate...

Page 29: ...al energy efficiency after installation since such efficiency is affected by additional factors such as the heat loss in the distribution system and the size of the products compared to the size and f...

Page 30: ...38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy efficiency of the set of products indicated in this sheet may not reflect the actual energy...

Page 31: ...31...

Page 32: ...llo RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper This instruction booklet is made of ecological paper Cod 1 043869ENG rev ST...

Reviews: