33
4
SETTING
MENU.
On this menu you have all adjustable parameters
of your installation.
Several parameters are not available with all
systems.
In order to enter in the setting menu press on
the same time on the (-
◀
) and (
▶
+) keys. When
you enter on the installation menu (the first pa-
rameter “
TkM1
” is displayed), you could choose
another parameter by pressing the navigation
key (
OK
).
Once the desired parameter displayed you can
change the value with the keys (
▶
+) or (-
◀
).
4.1 MAXIMUM TEMPERATURE ON
TANK 1.
“
TkM1
” parameter (Default value “65°C”).
- Maximum value of desired water temperature
on the tank1 during normal operation. (Adju-
stable 15 to 95°C with factory value 65°C).
4.2 MAXIMUM DELTA TEMPERATURE
FOR TANK 1
“
dtM1
” parameter (Default value “15°C”).
- Difference between collector temperature
T1
and tank1 temperature
T2
to start the main
pump1. (Adjustable 3 to 40°C with factory
value 7°C).
4.3 MINIMUM DELTA TEMPERATURE
FOR TANK 1.
“
dtm1
” parameter (Default value “7°C”).
- Difference between collector temperature
T1
and tank1 temperature
T2
to stop the main
pump 1. (Adjustable 2 to (dTMax tank1 -2°C)
with factory value 3°C).
4.4 MAXIMUM TEMPERATURE ON
TANK 2.
“
TkM2
” parameter (Default value “65°C”).
- Maximum value of desired water temperature
on the tank2 during normal operation. (Adju-
stable 15 to 95°C with factory value 65°C).
4.5 MAXIMUM DELTA TEMPERATURE
FOR TANK 2.
“
dtM2
” parameter (Default value “15°C”).
- Difference between collector temperature
T1
and tank2 temperature
T3
to start the main
pump 1. (Adjustable 3 to 40°C with factory
value 7°C).
4.6 MINIMUM DELTA TEMPERATURE
FOR TANK 2.
“
dtm2
” parameter (Default value “7°C”).
- Difference between collector temperature
T1
and tank 2 temperature
T3
to stop the main
pump 1. (Adjustable 2 to (dTMax tank 2 -2°C)
with factory value 3°C).
N.B.:
With a system with two tanks you could
choose a priority tank in the “
Installation
” menu
in submenu “
Priority tank
”, and also choose
the time of the loading cycle for the secondary
tank in submenus “
Prio tank load
” and “
Prio
tank break
”.
4.7 TIME DELAY P2.
“
P2dY
” parameter (Default value “1 min”).
Available only with the system 6.
- delay time for the start up of the pump
P2
after the pump
P1
start up. (Adjustable 0 to
30 minutes with factory value 1 minute).
4.8 MINIMUM TEMPERATURE ON
COLLECTOR.
“
mtCo
” parameter (Default value “25°C”).
- This setting level is used to define a minimum
temperature on the collector to authorize the
solar loading. (Adjustable between 0°C and
99°C with default value 25°C).