background image

16 

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

3.7  PROGRAMMING THE P.C.B.

The Nike Mini 28 kW Special boiler is prepared 

for possible programming of several operation 

parameters. By modifying these parameters 

as described below, the boiler can be adapted 

according to specific needs.
To access the programming phase, do the 

following: place the main selector on Reset for 

an amount of time ranging between 15 and 20 

seconds (after approx. 10 sec. LEDs 2 and 3 will 

start flashing simultaneously. Wait for this to stop 

and then place the main selector on DHW and 

Central Heating). At this point, place the main 

selector switch back on domestic hot water-
heating (

).

When the programming phase has been 

activated, enter the first level where it is possible 

to choose the parameter to be set.

The parameter is marked by one of the fast 

flashing LEDs between 1 and 8 (Fig. 2-1).

The selection is made by turning the DHW 

temperature selector (10). For association of the 

LED to the parameter, see the following table:

List of parameters

Flashing 

LED 

(fast)

Minimum CH output (DO NOT 

USE)

LED 1

Maximum CH output  (DO NOT 

USE)

LED 2

Central heating ignitions timer

LED 3

Heating power output ramp

LED 4

Heating switch-on delay request 

from Room thermostat and 

Comando Amico Remoto remote 

control 

V2

 

LED 5

DHW thermostat

LED 6

Pump functioning

LED 7

Functioning gas

LED 8

Boiler mode (DO NOT USE) (it 

establishes whether the boiler 

operates in instantaneous or 

storage mode)

LEDs 8 

and 1

Once the parameter to be modified has been 

selected, confirm by turning the main selector 

switch to Reset momentarily until the LED 

relative to the parameter switches-off, then 

release.

Given the OK for selection, pass to the second 

level where it is possible to set the value of the 

parameter selected. The value is indicated by the 

slow flashing of one of the LEDs between 1 and 

8. The value is selected by turning the central 

heating temperature selector (11).

Once the value of the parameter to be modified 

has been selected, confirm the selection by 

momentarily turning the main selector switch 

onto Reset momentarily until the LED relative to 

the parameter switches off, then release.

Programming mode is exited if no operation is 

carried out for 30 seconds or if the main selector 

switch is positioned at OFF from the “parameter 

setting” level.

For association of the LED to the relative value, 

see the following tables:

Heating output.

 The boiler is produced and 

calibrated in the central heating phase at nominal 

output. 

Permanent reduction of the timer.

 The boiler 

has an electronic timing device that prevents the 

burner from igniting too often in the heating 

phase. The boiler has a standard supply of a timer 

adjusted at 180 seconds.

Heating switch-on timer 

(continuous variation)

Flashing 

LED 

(slow)

30 seconds

LED 1

55 seconds

LED 2

80 seconds

LED 3

105 seconds

LED 4

130 seconds

LED 5

155 seconds

LED 6

180 seconds (Standard setting)

LED 7

255 seconds

LED 8

Central heating ramp timing.

 The boiler 

distributes the maximum power set in the 

previous parameter. The boiler performs an 

ignition ramp of about 650 seconds to arrive 

from minimum power to nominal heating power.

Central heating ramp timer 

(continuous variation)

Flashing 

LED 

(slow)

65 seconds

LED 1

130 seconds

LED 2

195 seconds

LED 3

390 seconds

LED 4

455 seconds

LED 5

520 seconds

LED 6

585 seconds

LED 7

650 seconds (standard setting)

LED 8

Heating switch-on delay request from Room 

thermostat and Comando Amico Remoto 

V2

 .

 

The boiler is set to switch-on immediately after a 

request. In the case of particular systems (e.g. area 

systems with motorised thermostatic valves etc.) 

it may be necessary to delay ignition.

Heating switch-on delay request 

from Room thermostat and 

Comando Amico Remoto 

remote control 

V2

 (continuous 

variation)

Flashing 

LED 

(slow)

0 seconds (Standard setting)

LED 1

54 seconds

LED 2

131 seconds

LED 3

180 seconds

LED 4

206 seconds

LED 5

355 seconds

LED 6

400 seconds

LED 7

510 seconds

LED 8

DHW thermostat.

 With the “correlated” 

thermostat setting the switch-off of the boiler 

takes place on the basis of the temperature set 

using the domestic hot water adjustment selector 

switch (10). While with the setting of the "fixed" 

DHW thermostat the switch-off temperature is 

fixed at the maximum value independently from 

the position of the selector switch.

DHW thermostat

Flashing 

LED 

(slow)

Correlated

LED 1

Fixed (Standard setting)

LED 8

Circulating pump function.

 Two circulating 

pump operational modes can be selected in 

heating phase.

In “intermittent” mode it is activated from the 

room thermostat or from the remote control, in 

“continuous” mode the pump always runs when 

the main switch (9) is on CH.

Pump function

Flashing 

LED 

(slow)

Intermittent (Standard setting)

LED 1

Continuous

LED 8

Town Gas G110 – Industrial gas.

 The setting 

of this function is used to adjust the boiler in 

order to function with gases from the first family.

Gas G110 - Industrial gas (first 

family gas)

Flashing 

LED 

(slow)

Off (Standard setting)

LED 1

On

LED 8

Summary of Contents for 3.018921

Page 1: ...NIKE MINI 28 KW SPECIAL Instruction and warning booklet 1 040845ENG...

Page 2: ...as boilers As for the other issues related to boiler installation e g safety in the work site environment protection injury prevention it is necessary to comply with the provisions specified in the re...

Page 3: ...l heating system pressure 12 2 9 System draining 12 2 10 Anti freeze protection 12 2 11 Case cleaning 12 2 12 Decommissioning 12 3 Boiler start up initial check 13 3 1 Hydraulic diagram 13 3 2 Wiring...

Page 4: ...ies personal responsibility and invalidates the warranty Installation regulations theseboilerscannotbeinstalledinbedrooms studio flats and bathrooms They also cannot be installed in rooms with wood or...

Page 5: ...type used in the boiler which must comply with the regulations in force as insufficient levels can reduce generator output and cause malfunctions Ensure correct gas cock connection by following the m...

Page 6: ...ergas chrono thermostats are connected with 2 wires only Carefully read the user and assembly instructions contained in the accessory kit On Offdigitalchrono thermostat Thechrono thermostat allows set...

Page 7: ...dangerous situations for the user The flue ducts must be connected to the chimney or flue in the same room in which the appliance is installed or at most in the adjoining room and must comply with the...

Page 8: ...intervenes in the eventofgassupplyfailureandchecktherelative intervention time check activation of the main switch located upstream of the boiler The boiler must not be started up even if only one of...

Page 9: ...safety thermostat 6 Fumes hood 7 Delivery probe 8 Safety thermostat 9 System expansion vessel 10 Combustion chamber 11 Boiler circulator pump 12 3 bar safety valve 13 By pass 14 Three way valve motor...

Page 10: ...onnected parts with easily flammable substances Never leave containers or flammable substances in the same environment as the appliance It is prohibited and dangerous to obstruct the air intake even p...

Page 11: ...tacts resistance block LEDs 2 and 7 flash at the same time 04 Parasite flame block LEDs 1 and 7 flash at the same time 20 Loss of remote control communication LEDs 2 and 3 flash alternately 31 Insuffi...

Page 12: ...ure via the valve located at the bottom of the boiler Fig 2 2 N B close the valve after the operation If pressure values reach around 3 bar the safety valve may be activated In this case contact a pro...

Page 13: ...he exit of the appliance combustion products check that there is no backflow of combustion products into the room even during functioning of fans ensure activation of all adjustment devices seal the g...

Page 14: ...ent interventions of the over heating safety thermostat It can depend on reduced water pressure in the boiler little circulation in the heating system the blocked pump or an anomaly of the boiler P C...

Page 15: ...perations must be carried out by a qualified technician e g After Sales Technical Assistance Service Burner adjustment must be carried out using a U or digital pressure gauge connected to the gas valv...

Page 16: ...tables Heating output The boiler is produced and calibrated in the central heating phase at nominal output Permanent reduction of the timer The boiler has an electronic timing device that prevents the...

Page 17: ...with boiler in standby the function activates every 18 hours after the last boiler check power supply In case of functioning in domestic hot water mode the self check starts within 10 minutes after t...

Page 18: ...anel 4 towards you taking care to remove the 2 fixing screws 5 3 16 HEAT OUTPUT N B gasflowratesrefertoheatingpowerbelowa temperature of 15 C and a pressure of 1013 mbar Burner pressure values refer t...

Page 19: ...3994 Domestic hot water adjustable temperature C 38 77 Domestic hot water circuit flow limiter l min 11 Domestic circuit min pressure dynamic bar 0 3 Domestic hot water circuit max working pressure ba...

Page 20: ...Model Cod Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat in...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...Europe S r o 059051 Poprad Matejovce SK Tel 421 524314311 Fax 421 524314316 IMMERGAS SPA ITALY CERTIFIED COMPANY UNI EN ISO 9001 2015 Design manufacture and post sale assistance of gas boilers gas wat...

Reviews: