Operation & Service Manual 
Valve islands VS18/VS26 EtherNet/IP

 

09/2018 

Construction & Design is subject to change © 2018 Norgren GmbH 

11.  Electrical data 

 

Requirement 

Comment 

Valve voltage range (VA) 

24VDC +/-10% 

PELV 

Electronics voltage range (VB) 

24VDC +/-25% 

PELV 

Maximal currents: 

 

VA: 150mA + n x 30mA 

VB: 400mA 

n = number of activated valves 

Voltages are galvanic decoupled 

Yes 

 -- 

Protection against polarity reversal 

VA, VB 

 -- 

Overcurrent  protection VB, VA 

irreversible 

Protection against  overload and short-
circuit currents, fused with 2A slow-acting 
fuse 

PE/FE/Ground connection 

 

M4 thread on the rear of the connection 
module 

Reference section 2.1 

Electrical power supply connection  

M12 / 5-pin / A-coded / male connector 

M12-1: L1 (VB+) 

M12-2: N2 (VA-) 

M12-3: N1 (VB-) 

M12-4: L2 (VA+) 

M12-5: FE (Functional Earth) 

Bus connection 

M12 / 4-pin / D-coded / female connector 

M12-1: TD+ 

M12-2: RD+ 

M12-3: TD- 

M12-4: RD- 

 
 

 

Summary of Contents for VS18G

Page 1: ...Operation Service Manual Valve island VS18 VS26 with EtherNet IP Interface ...

Page 2: ...hints added 20 07 2017 004 All Changes in IP Address set up I O data solenoid object 31 07 2017 005 All ISEM description added valve island extension added minor comments 07 11 2017 006 2 4 4 10 1 10 11 12 2 12 3 Power up description updated ATEX Note added Mounting kit added FW version and serial number added New 2 station SPI board added soft start valve rules added technical data corrected 07 0...

Page 3: ...face Object 17 4 4 Firmware version and serial number 19 5 I O connection via Assembly Object 21 5 1 Bit allocation valve stations 21 5 2 Input data Assembly Object Instance 101d 22 5 3 Output data Assembly Object Instance 100d 24 6 Solenoid Object 25 7 Diagnostics and LEDs 26 7 1 Status LEDs 26 7 1 1 Status LEDs description 26 7 1 2 Link states for Port P1 and Port P2 26 7 1 3 Network Status LED ...

Page 4: ...vice Manual Valve islands VS18 VS26 EtherNet IP 09 2018 Construction Design is subject to change 2018 Norgren GmbH Contact information Norgren GmbH Site Fellbach Stuttgarter Straße 120 70736 Fellbach Tel 49 711 5209 0 ...

Page 5: ...nformation for the EtherNet IP variants all data sheets for the VS18 VS26 valve island series are applicable and remain valid The difference between the both variants consists of the sizes of valves and the resulting maximum flow rate All electrical connections and parameterization are the same for both variants Refer also to the datasheets on the following weblinks http cdn norgren com pdf en_5_1...

Page 6: ...ction module Its location shows the red arrow on the following picture 2 2 Intermediate supply exhaust module ISEM In cases where the channel diagnostics is activated on the valve island the channel diagnostics setting should be disabled at the position of each ISEM This needs to be done in order to avoid any misleading failure indication due to missing electronic components in the ISEM 2 3 ATEX N...

Page 7: ...ase is indicated by the following permanent Status LED states P1 off P2 off NS off MS red VB green VA green 2 4 2 Firmware release V1 002 and higher The requirement as described in chapter 2 4 1 is not applicable for the firmware release V1 002 and higher The initialization of the valve island is performed during the testing in production before delivery Note In case any changes are made on the ha...

Page 8: ...il 2 Cylinder screw M4 x 8 3 Mounting bracket 4 Cylinder screw M4 x 25 5 Cylinder screw M4 x 36 2 5 1 DIN rail assembly without mounting bracket Insert screw M4 x 25 4 into the left end plate bus node and position below the mounting nut 1 Insert screw M4 x 36 5 into the right end plate and position below the mounting nut 1 Place the valve island on the DIN rail Orientate straight flange of the mou...

Page 9: ...d Mounting panel assembly without mounting bracket 2 5 3 DIN rail assembly using the mounting bracket Hook the mounting bracket 3 into the left end plate bus node Insert screw M4 x 8 2 into the mounting bracket 3 and position below the mounting nut 1 Insert screw M4 x 36 5 on the right end plate and position below the mounting nut 1 Place the valve island on the DIN rail Orientate straight flange ...

Page 10: ...using the mounting bracket Hook the mounting bracket 3 into the left end plate bus node Insert screw M4 x 8 2 into the mounting bracket 3 Insert screw M4 x 36 5 on the right end plate Place the valve island on the mounting panel wall Tighten screws with the torque of 1 0 1 1 Nm Check the fit of the valve island Mounting panel assembly using the mounting bracket ...

Page 11: ...lectrical Connections of the VS18 VS26 valve islands Top view VS18 with 8 stations 1 Port 1 bus connector for EtherNet IP 4 pins M12 D coded female connector 2 Port 2 bus connector for EtherNet IP 4 pins M12 D coded female connector 3 Power supply connector 5 pins M12 A coded male connector 4 Status LEDs 5 Valve status LEDs 1 2 5 4 3 ...

Page 12: ... M12 4 pins female D coded Pin no Function 1 Transmission Data TD 2 Receive Data RD 3 Transmission Data TD 4 Receive Data RD Housing FE functional earth 3 2 POWER supply connector M12 5 pins male A coded Pin no Function 1 L1 VB 24V electronics power supply 2 N2 VA 0V valves power supply 3 N1 VB 0V electronics power supply 4 L2 VA 24V valves power supply 5 FE functional earth ...

Page 13: ...tions 2300 VS18 26 with 14 16 Stations 2400 VS18 26 with 18 20 Stations Note All explanations in this manual are based on Rockwell Automations Studio 5000 The following steps are necessary 4 1 EDS File Installation The EDS file is required to configure the VS18 VS26 valve island A symbol file is necessary to display an icon in the engineering tool EDS files are provided by the module vendor and ca...

Page 14: ...tallation Tool start the Installation Wizard Follow the installation steps described in the wizard After the installation the new module is shown in the catalogue 4 2 Hardware configuration Select valve island After the successful installation of the EDS file the module configuration is needed In context menu choose New Module after right clicking on Ethernet ...

Page 15: ...tion Design is subject to change 2018 Norgren GmbH In the module catalog choose the corresponding VS18 VS26 valve island and click on Create The picture below shows Select Module Type Dialog In the following dialogue tab General set the Name and the correct IP Address of the module ...

Page 16: ...on change Requested Packet Interval RPI greater than or equal to 10 ms and click OK The RPI times has a direct impact to the busload Note The lower the cycle times the higher the busload The picture bellow shows module tree with the new added module After successful configuration please perform download by clicking Download in the menu item Communication ...

Page 17: ...Address opens the dialog used to set up the IP Address The IP Address settings are transferred into the Discovery History if they are valid and confirmed with the OK button Pushing the Enable BOOTP DHCP Button enables the IP Address assignment for the chosen entry The VS18 VS26 valve island will appear with assigned IP Address in Discovery History list if address assignment was successful 4 3 2 St...

Page 18: ...ttribute 5 contains the configuration parameters required to operate as a TCP IP node At least network address and network mask needs to be configured Attribute 5 of TCP IP Interface Object Interface Configuration Next table shows the structure of the interface configuration attribute Structure of Attribute 5 Interface Configuration ...

Page 19: ...l number of the device using the Logix Designer Allen Bradley This information is accessible via the Identity Object Attribute 3 as described in this section Connect to the PLC by choosing the Go Online option in the Communications drop down menu As soon as the connection with the PLC is established select the corresponding Valve Island from the list of Ethernet modules and open the module Propert...

Page 20: ...lands VS18 VS26 EtherNet IP 09 2018 Construction Design is subject to change 2018 Norgren GmbH The identification and status data of the selected valve island such as the software version and serial number are shown in the Tab Module Info ...

Page 21: ...d one for output data 5 1 Bit allocation valve stations The following picture shows exemplarily a VS island with 6 valve stations To calculate the length of the used output data in bytes for the VS18 VS26 valve configuration please use the following formula 𝐵 𝐵𝑦𝑡𝑒𝑠 𝑉 2 𝑉 2 𝑀𝑂𝐷8 8 𝑉 4 6 8 10 12 14 16 18 20 Whereby V number of valve stations and MOD Modulo Operator The picture shows VS valve island ...

Page 22: ...X X X X X S 12 S 14 S 12 S 14 S 12 S 14 S 12 S 14 3 V 16 V 15 V 14 V 13 X X X X S 12 S 14 S 12 S 14 S 12 S 14 S 12 S 14 4 V 20 V 19 V 18 V 17 X X S 12 S 14 S 12 S 14 S 12 S 14 S 12 S 14 V Valve no S Solenoid side X Bytes reserved 5 2 Input data Assembly Object Instance 101d The right picture shows a valve island with 6 valve stations side 12 is in the front side 14 is on the backside Used acronym ...

Page 23: ...12 14 V11 12 V11 14 V10 12 V10 14 V09 12 V09 14 Open Load 1 V04 12 V04 14 V03 12 V03 14 V02 12 V02 14 V01 12 V01 14 Short Circuit Overload 2 V08 12 V08 14 V07 12 V07 14 V06 12 V06 14 V05 12 V05 14 Short Circuit Overload 3 V12 12 V12 14 V11 12 V11 14 V10 12 V10 14 V09 12 V09 14 Short Circuit Overload 4 V16 12 V16 14 V15 12 V15 14 V14 12 V14 14 V13 12 V13 14 Short Circuit Overload 5 V04 12 V04 14 V0...

Page 24: ...4 0 V04 12 V04 14 V03 12 V03 14 V02 12 V02 14 V01 12 V01 14 1 V08 12 V08 14 V07 12 V07 14 V06 12 V06 14 V05 12 V05 14 0 V04 12 V04 14 V03 12 V03 14 V02 12 V02 14 V01 12 V01 14 1 V08 12 V08 14 V07 12 V07 14 V06 12 V06 14 V05 12 V05 14 2 V12 12 V12 14 V11 12 V11 14 V10 12 V10 14 V09 12 V09 14 0 V04 12 V04 14 V03 12 V03 14 V02 12 V02 14 V01 12 V01 14 1 V08 12 V08 14 V07 12 V07 14 V06 12 V06 14 V05 12...

Page 25: ...Instance ID 32 31 30 29 28 27 26 25 Valve 17 20 V20 12 V20 14 V19 12 V19 14 V18 12 V18 14 V17 12 V17 14 Instance ID 40 39 38 37 36 35 34 33 Following table shows all Instance Attributes of the Solenoid Object Attr ID Acces Rule Name Data Type Description Schematic of Values 1 Get Set Solenoid Value Bool Output point value 0 Off 1 On 3 Get Set Enable Diagnostics Bool Enables Disables Diagnostics Ch...

Page 26: ...2 Link Port 2 TX RX Link NS Network Status MS Module Status VB Electronic Power Supply Status VA Valves Power Supply Status Link Status LED State Link Connection Established yellow Link Communication Active flashing yellow green Link Connection Not Established off Module Status LED State No Power off Connected green Not Connected flashing green Connection Timeout flashing red Duplicate IP n a red ...

Page 27: ...tus LEDs Each valve station has one or two separate status LEDs depending on its configuration which indicate the control states 14 and 12 for the corresponding pilot valve solenoids Electronics Power Supply States LED State Voltage O K green Undervoltage flashing red Overvoltage red Valve Power Supply States LED State Voltage O K green Undervoltage flashing red Overvoltage red Status LED State Va...

Page 28: ...output Set output Freeze output This behavior could be set up for each single solenoid via the following attributes of their instance of the solenoid object Attr ID Acces Rule Name Data Type Description Schematic of Values 6 Get Set Fault Action Bool Action taken on outputs value in recoverable fault state 0 Fault Value Attribute 1 hold last state 7 Get Set Fault Value Bool Value for use with Faul...

Page 29: ...t to change 2018 Norgren GmbH 9 Properties EtherNet IP Interface Specification Comments Number of ports 2 Link Speed 100Mbit s Duplex Mode Full Duplex QuickConnect N A DLR Mode N A Device Level Ring EtherNet IP ODVA Certification Compliant to IEC61158 IP Address modes Static BOOTP DHCP EDS languages EN ...

Page 30: ...mbinations Below illustration shows an overview of the preferred combinations of existing PCBs in order to build the required number of valve stations 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 4 4 6 4 2 8 4 4 10 4 4 2 12 4 4 4 14 4 4 4 2 14 4 4 4 4 18 4 4 4 4 2 20 4 4 4 4 4 4 2 4 station PCB 2 station PCB Note It is generally possible to use the new 2 station PCBs VS2672764 KG00 on all po...

Page 31: ...31 Operation Service Manual Valve islands VS18 VS26 EtherNet IP 09 2018 Construction Design is subject to change 2018 Norgren GmbH 10 2 Valve island with 4 stations 10 3 Valve island with 6 stations ...

Page 32: ...32 Operation Service Manual Valve islands VS18 VS26 EtherNet IP 09 2018 Construction Design is subject to change 2018 Norgren GmbH 10 4 Valve island with 8 stations 10 5 Valve island with 10 stations ...

Page 33: ...33 Operation Service Manual Valve islands VS18 VS26 EtherNet IP 09 2018 Construction Design is subject to change 2018 Norgren GmbH 10 6 Valve island with 12 stations 10 7 Valve island with 14 stations ...

Page 34: ...ice Manual Valve islands VS18 VS26 EtherNet IP 09 2018 Construction Design is subject to change 2018 Norgren GmbH 10 8 Valve island with 16 stations 10 9 Valve island with 18 stations 10 10 Valve island with 20 stations ...

Page 35: ...oft start valves may be added at even positions 0 2 4 20 22 24 See below some configurations as examples when using the soft start valve Only number positions of valve slices blanking plates ISEM plates are counted with respect to station numbering in below configurations Note Only the new 2 station PCB VS2672764 KG00 should be used in the below configurations 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1...

Page 36: ...oltages are galvanic decoupled Yes Protection against polarity reversal VA VB Overcurrent protection VB VA irreversible Protection against overload and short circuit currents fused with 2A slow acting fuse PE FE Ground connection M4 thread on the rear of the connection module Reference section 2 1 Electrical power supply connection M12 5 pin A coded male connector M12 1 L1 VB M12 2 N2 VA M12 3 N1 ...

Page 37: ...essure 10 bar VS18S VS26S models and VS18G VS26G solenoid pilot actuated valves with internal pilot supply 16 bar VS18G VS26G solenoid pilot actuated valves with external pilot supply Ambient temperature 15 C to 50 C Medium temperature 5 C to 50 C Consult our Technical Service for use below 2 C Materials Body sub base die cast aluminium Glandless spool sleeve Aluminium hard anodized Teflon coated ...

Page 38: ...Gal min Kv m h VS18G 5 2 550 0 56 0 48 VS18G 5 3 550 0 56 0 48 VS18S 2x2 2 550 0 56 0 46 VS18S 2x3 2 600 0 61 0 52 VS18S 5 2 650 0 66 0 57 VS18S 5 3 650 0 66 0 57 12 3 Technical data VS26 Ports 2 4 G1 4 NPTF 1 4 PIF 10 mm PIF 8 mm PIF 3 8 Valves ISO 15407 2 26 mm Flow values measured at 6 bar inlet pressure and with a pressure drop of 1 bar Series Function QN L min CV US Gal min Kv m h VS26G 5 2 1...

Page 39: ... certain condition or suitability for a certain application can be derived from our information The information given does not release the user from the obligation of exercising judgment and verification It must be remembered that our products are subject to a natural process of wear and ageing This document as well as the data specifications and other information presented in it are the sole prop...

Reviews: