10.11 Usage of Soft-start valves
Soft-start valves are only available for VS26.
Maximum number of soft-start valves in one valve island is 4.
Use always 2 single blank PCBs (VS2672763-KG00) with 1 soft-start valve (VS2672530-KG00).
VS2672530-KG00
VS2672763-KG00
Up to 4 soft-
start valves may be added at even positions (0, 2, 4, …20, 22, 24).
See below some configurations as examples when using the soft-start valve. Only number/
positions of valve blanking ISEM plates are counted with respect to station
numbering in below configurations.
Note : Only the new 2-station PCB (VS2672764-KG00) should be used in the below configurations.