SCH0410

l

  Maximum Load:  40 Amp single phase @ 40ºC.

l

  Maximum Channel Current:  10 Amps.

l

  Supply:  230 volts  -/+ 10% 50/60 Hz.

 

(optionally, 127 volt 60 Hz).

l

  Protection: 4 x  10 Amp MCB’s type C, 6KA rated. 

 

SCH1210 

- As 0410 but 3 phase + 12 x 10 Amp. 

 

SCI0805

l

  Maximum Load:  40 Amp single phase @ 40ºC.

l

  Maximum Channel Current:  5 Amps.

l

  Supply:  230 volts  -/+ 10% 50/60 Hz (same phase).

l

  Protection: 1 x 20 Amp Double pole input MCB’s 

 

type C, 6KA rated. 

SCH1200

l

  Maximum Load:  There is no load control. 

l

  Power switching is achieved by the DSI ballasts 

 

themselves.

l

  Maximum Channel Current:  Not applicable.

l

  Supply:  1 x 230 volts  -/+ 10% 50/60 Hz.

l

  Protection: Thermal non resetting fuse.

 
SCH0410
Dimmed Outputs

l

  4 x 1-10 volt at 0.1 Amp sink current per channel.

l

  4 x Tridonic DSI outputs (uses electronic power    

 

switching in ballasts).

Switched Outputs

l

  4 x 230 volt 10A (inductive or resistive).

 
SCH1210
Dimmed Outputs

l

  12 x 1-10 volt at 0.1 Amp sink current per channel.

l

  12 x Tridonic DSI outputs (uses electronic power

 

switching in ballasts).

Switched Outputs

l

  12 x 230 volt 10A (inductive or resistive).

 
SCI0805 
Dimmed Outputs 

l

  4 x 1-10 volt at 0.1 Amp sink current per channel.

l

  4 x Tridonic DSI outputs (uses electronic power 

 

switching in ballasts).

l

  4 x 5 Amp inductive.

Switched Outputs

l

  4 x 230 volt 5A (inductive or resistive).

 
SCH1200T
Dimmed Outputs

l

  12 x 0-10 volts at 0.1 Amp sink current per channel.

l

  12 x Tridonic DSI outputs (uses electronic power 

 

switching in ballasts).

Switched Outputs

l

  None. 

 
Terminal Sizes 
SCH0410, SCH1210, SCI0805

l

  Incoming supply, maximum cable size: 10mm2.

SI0805T

l

  Incoming supply, cable rated for 40 Amp or to  

 

correspond to input supply voltage.

l

  Maximum cable size 10mm2. 

SCH1200T

l

  Incoming supply, maximum cable size: 2.5mm2

l

  Ballast output, maximum cable size: 12 pairs  

 

2.5 mm2 per circuit.

SCH0410S  - Single pole 

4 channels

SCH0410N  - Neutral disconnect 

SCH0410D  - Double pole 

 

 

SCH1210S  - Single pole 

12 Channels

SCH1210N  - Neutral disconnect 

SCH1210D  - Double pole 

 

 

SCI0805T   - Single pole           

- Dual unit

SCI0805S   - Single pole                  

SCI0805N   - Neutral disconnect      

 

SCH1200T  - Terminals             

- 12 Channel, no relays

 

Common specifications as detailed on page 

12 plus the following features:

Key Features

SCH0410S

l

  40 Amp fully rated source controller.

SCH1210

l

  120 Amp total box load on 4 circuits.

SCI0805

l

  40 Amp total box load on 1 supply.

SCH1200

l

  A 12 channel device source controller.

l

  Suitable for both 0-10 volt analogue and DSI ballasts.

l

  Quiet operation.

Mechanical Data

SCH0410

l

  Weight:  4kg.

l

  Mains Cable Access: 4 x 25 mm, 4 x PG16 and 1 x 

 

PG21knockouts.

l

  Control Cable Access: 1 x 25 mm, 1 x PG16 

 

knockouts.

SCH1210

l

  Weight:  7.5kg.

UK version

l

  Mains Cable Access: 12 x 25 mm, 1 x PG29 

 

knockouts.

l

  Control Cable Access: 1 x 25 mm knockout.

Euro version

l

  Mains Cable Access: 12 x PG16 and 1 x PG29 

 

knockouts.

l

  Control Cable Access: 1 x PG16 knockout.

SCI0805

l

  Weight:  7.5kg.

l

  Mains Cable Access: 4 x 25 mm, 4 x PG16 and 1 x 

 

PG21knockouts.

l

  Control Cable Access: 1 x 25 mm, 1 x PG16 

 

knockouts.

SCH1200T

l

  Weight:  3kg.

l

  Mains Cable Access: 2 x 25 mm and 2 x PG16 

 

knockouts.

l

  Control Cable Access: 1 x 25 mm and 1 x PG16 

 

knockouts. 

Electrical Data

Load Types

l

  1-10volt HF Fluorescent, 100 per channel.

l

  DSI & DALI Fluorescent Ballasts

     SCH0410 & SCI0805, 32 / channel. 128 / unit
     SCH1210, SCH1220 & SCH1200T, 64 / channel; 128 / unit

l

  0-10 volt Iris control 20K Ohm input).

l

  1-10 volt Multi-Load transformers 100 (control only).

HF Ballast Controllers

15 of 23

INTELLIGENT  CONTROLS

Summary of Contents for SCI0405

Page 1: ...N Network 8 ASCII control messages 9 Typical system schematics 10 Service switches and LEDs 12 Specifications Inductive H F Ballast Power Switching Adaptive Trailing Edge Instruction Manual Read this document prior to installation Source Controllers INTELLIGENT CONTROLS ...

Page 2: ......

Page 3: ...2 of 23 INTELLIGENT CONTROLS ...

Page 4: ...e Controllers require ventilation and have slots on all sides to allow for a convection flow of air through the unit For this reason it is important to orientate the unit correctly and allow a minimum space between adjacent Source Controllers and other surfaces A minimum of 100mm of free space should be left either side of a Source Controller or between adjacent Controllers IMPORTANT NOTE Mounting...

Page 5: ...ected by 5Amp MCB s a supply capable of delivering more than 10Amps could be used but it is recommended that it should not exceed the rating shown on the label fitted inside the door Example 2 Fluorescent lamps with dimmable HF ballasts connected to a 4 channel 10A High Frequency Ballast Source Controller SCH0410S Channel 1 load is 8 x 58 Watt tubes Channel 2 load is 16 x18 Watt tubes Channel 3 lo...

Page 6: ...hase sequential as follows L1 Phase 1 R L2 Phase 2 Y L3 Phase 3 B L4 Phase 1 R L5 Phase 2 Y L6 Phase 3 B L11 Phase 2 Y L12 Phase 3 B Note Adaptive dimmers Source Controllers with prefix SCA are shipped in Switch mode and will be set according to type of connected load by the commissioning engineer Please retain all information concerning the type of load transformers that are installed for each di...

Page 7: ...ed at 0V and DIM2 If there is any doubt concerning which cable carries mains this must be resolved using a voltmeter before connecting to the Source Controller Connecting a mains potential cable to the Low Voltage terminals will damage the unit and invalidate warranty HF Ballast types The Source Controller is able to control either Analogue or DSI digital ballasts with each channel individually co...

Page 8: ...es are installed every iCAN network requires two Termination resistors only iCANnet Connections RS485 Control The RS485 Control terminals are located adjacent to the iCAN network terminals The terminals to be used are labelled RS485 RS485 0V See the ASCII control message section on page 13 RJ12 Connector The Source Controller is fitted with an RJ12 socket to allow local connection of a handheld pr...

Page 9: ... Number valid for 01 to 99 Axx defines the Area Number valid for 01 to 99 1 3 5 Command SC Set Channel Level This message sets the level of a channel in an area The syntax is SCxx Axx Lxx Fxx cr SCxx defines the channel number where xx is valid from 00 to 99 Channel 00 affect ALL channels in an area Axx defines the Area Number valid for 00 to 99 Lxx defines the Level valid for 00 to 99 in and FF f...

Page 10: ...k cables being terminated If iCANnet cables are terminated after Source Controllers have been energised it should be noted that cables will be carrying low voltage signals and mis connection of these could result in damage to other devices on the network Factory Set Source Controller Settings All channels set to Area 1 Physical Channel No Virtual Channel No Power Up Scene Last Scene Selected From ...

Page 11: ...work Sending a message to identify the device on the network The LEDs indicate the following l Normal operation l Message transmission and receipt l Override status ICANnet error status will occur when a Source Controller is not connected to an iCAN network for any reason Once either connected to a network of one or more other devices which are powered the error status will be removed It is still ...

Page 12: ...General Specifications 11 of 23 INTELLIGENT CONTROLS ...

Page 13: ...l One set of terminals for alarm input Electrical Data Terminal Sizes l Loads maximum cable size 1 x 4 mm2 or 2 x 2 5 mm2 per circuit l iCANnet cable size 5 x 1mm2 l Audio Visual Port RS485 2 x 1mm2 l Alarm input 2 x 1mm2 Memory l FLASH memory to be able to upgrade firmware EEPROM for 128 scene memory Fade Times l 0 1 seconds to 60 minutes Mains Stabilisation l 50 1 Mains Isolators Isolators are s...

Page 14: ...410 l 4 x 40 Amp rated Triacs SCI1205 SCI1210 SCI1220 l 12 x 40 Amp Triacs Switched Outputs l The Dimmed outputs may be configured as switches for non dimmed loads They require a minimum load of 30mA for them to latch Before connecting Discharge lamps consult with the iLight help desk Terminal Sizes l Incoming supply maximum cable size 10mm2 SCI0405S Single pole SCI0405N Neutral disconnect SCI0410...

Page 15: ...12 iCANnet Socket Control Board 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Supply Load Cable entry knockouts Control Cable entry knockouts Service switches and LEDs 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Channel Circuit Breakers MAINS IN RS485 Alarm Terminals iCANnet Terminals ...

Page 16: ...correspond to input supply voltage l Maximum cable size 10mm2 SCH1200T l Incoming supply maximum cable size 2 5mm2 l Ballast output maximum cable size 12 pairs 2 5 mm2 per circuit SCH0410S Single pole 4 channels SCH0410N Neutral disconnect SCH0410D Double pole SCH1210S Single pole 12 Channels SCH1210N Neutral disconnect SCH1210D Double pole SCI0805T Single pole Dual unit SCI0805S Single pole SCI08...

Page 17: ...Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 RS485 oV AL 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 RS485 oV AL 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Mains Supply In Supply Load Cable entry knockouts Supply Load Cable entry knockout...

Page 18: ...PG16 knockout Switched Relay Controllers 17 of 23 Electrical Data Load Types l This unit is designed to work with most lighting load types Please consult with the iLight help desk for guidance on true load calculations Care should be taken when specifying discharge lighting sources Switched Outputs l This device uses 12 x 230 volt 20A resistive and inductive relays Terminal Sizes l Incoming supply...

Page 19: ...ocket Control Board Supply Load Cable entry knockouts Control Cable entry knockouts Service switches and LEDs Channel Circuit Breakers MAINS IN 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 RS485 oV AL 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair RS485 Alarm Terminals iCANnet Terminals ...

Page 20: ... and 1 x PG29 knockouts l Control Cable Access 1 x PG16 knockout Electrical Data SCA0410 l Maximum Load 40 Amp single phase 40ºC l Maximum Channel Current 10 Amps l Supply 230 volts 10 50 60 Hz optionally 127 volt 60 Hz l Protection 4 x 10 Amp MCB s type C 6KA rated SCA1210 l Maximum Load 40 Amp three phase 40ºC l Maximum Channel Current 10 Amps l Supply 415 230 volts 10 50 60 Hz optionally 220 12...

Page 21: ...Adaptive Source Controllers 20 of 23 SCA1210S INTELLIGENT CONTROLS ...

Page 22: ...tches for non dimmed loads They require a minimum load of 30mA for them to latch Before connecting Discharge lamps consult with the iLight help desk Terminal Sizes l Incoming supply maximum cable size 10mm2 SCT0405S Single pole SCT0405N Neutral disconnect SCT0405D Double pole SCT1205S Single pole SCT1205N Neutral disconnect SCT1205D Double pole Common specifications as detailed on page 12 plus the...

Page 23: ...y Earth Terminals RJ12 iCANnet Socket Control Board 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Supply Load Cable entry knockouts Control Cable entry knockouts Service switches and LEDs 12V Orange Pair CAN H Blue White CAN L Blue 0V Green Pair SHIELD Brown Pair Isolator MAINS IN RS485 Alarm Terminals iCANnet Terminals ...

Page 24: ...arks of Cooper Controls Limited All servicing must be referred to iLight Cooper Controls Limited This equipment is designed for professional lighting control and is unsuitable for any other purpose Cooper Controls Limited reserves the right to make changes to the equipment described in this handbook without prior notice Errors and omissions excepted E OE Part No 7385000 Issue 10 January 2008 INTEL...

Reviews: