Trailing Edge Source Controllers
Electrical Data
SCI0405
l
Maximum Load: 20 Amp single phase @ 40ºC.
l
Maximum Channel Current: 6 Amps.
l
Supply: 230 volts -/+ 10% 50/60 Hz.
(optionally, 127 volt 60 Hz).
l
Protection: 4 x 6 Amp MCB’s type C, 6KA rated.
SCI1205
l
Maximum Load: 40 Amp single phase @ 40ºC.
l
Maximum Channel Current: 6 Amps.
l
Supply: 230 volts -/+ 10% 50/60 Hz.
(optionally, 127 volt 60 Hz).
l
Protection: 12 x 6 Amp MCB’s type C, 6KA rated.
Load Types
l
Incandescent 230 volt lamps.
l
Capacitive loads
l
Trailing edge electronic transformers.
Minimum Load
l
20 watts per channel.
Dimmed Outputs
SCT0405
l
4 x 19 Amp rated Transistors.
SCT1205
l
12 x 19 Amp rated Transistors.
Switched Outputs
l
The Dimmed outputs may be configured as switches,
for non-dimmed loads. They require a minimum load
of 30mA for them to latch. Before connecting
Discharge lamps, consult with the iLight™ help desk.
Terminal Sizes
l
Incoming supply, maximum cable size: 10mm2.
SCT0405S - Single pole
SCT0405N - Neutral disconnect
SCT0405D - Double pole
SCT1205S - Single pole
SCT1205N - Neutral disconnect
SCT1205D - Double pole
Common specifications as detailed on
page 12 plus the following
:
Key Features
SCT0405
l
- 4 x 5 Amp fully rated Source Controller.
SCT1205
l
- 12 x 5 Amp fully rated Source Controller.
l
Dims resistive, capacitive and low voltage electronic
transformer loads.
l
Quiet operation.
Mechanical Data
SCT0405
l
Weight: 4kg.
l
Mains Cable Access: 4 x 25 mm, 4 x PG16 and 1 x
PG21knockouts.
l
Control Cable Access: 1 x 25 mm, 1 x PG16
knockouts.
SCT1205
l
Weight: 10kg.
l
Mains Cable Access: 12 x 25 mm, 1 x PG29
knockouts.
l
Control Cable Access: 1 x 25 mm knockout.
21 of 23