Ikon ISP18 Installation & Operation Manual Download Page 7

7

NOTICE

GAS CONNECTION

The data plate on the rear of the stockpot indicates the type of gas your unit is equipped

to burn. DO NOT connect to any other gas type.

Gas supply connections and any pipe joint compound must be resistant to the

action of propane gases.

Purge the supply line to clean out any dust, dirt, or any foreign matter before connecting

the line to the unit.

Codes require that a gas shut-off valve be installed in the gas line ahead of the stockpot.

The gas supply line must be at least the equivalent of ¾” iron pipe.
A pressure regulator is supplied and must be installed outside of the broiler when making

the gas supply connection.

Standard orifices are set for 5"WC (Water Column) for

Natural Gas — 10"WC (Water Column) for Propane. Use the

1

/

8

” pipe tap on the burner

manifold for checking pressure.

Make sure the gas piping is clean and free of

obstructions, dirt, and piping compound.
An adequate gas supply is necessary. Undersized or low pressure lines will restrict the

volume of gas required for satisfactory performance. A minimum supply pressure of 7"

W.C. for natural gas and 11" W.C. for propane gas is recommended. With all units

operating simultaneously, the manifold pressure on all units should not show any

appreciable drop.
When testing the gas supply piping system, if test pressures exceed ½ psig (3.45 kPa),

the stockpot and its individual shutoff valve must be disconnected from the gas supply

piping system. When test pressures are ½ psig (3.45 kPa) or less, the stockpot must be

isolated from the gas supply piping system by closing its individual manual shut -off valve

during any pressure testing of the system.

Prior to lighting, check all joints in the gas supply line for leaks.

Use soap and water solution. Do not use an open flame.

OPERATION

The stockpot range and its parts are hot. Use care when operating,

cleaning or servicing the stockpot range.

CONTROLS

The burner i s in two sections, controlled by two heavy duty infinite control valves. The

center “Star” section (Fig. 6) is on separate burner with an input of 40,000 BTU/hr. It is

controlled by the right burner valve knob. The outer circle of the burner (Fig . 6) is the

other separate 40,000 BTU/hr input burner, controlled by the left burner valve knob.
These two separate burners provide heat flexibility. With one burner off and the second

burner set low, up to both burners full on, you can move from low simmer on up to

80,000 BTU/hr input.

Summary of Contents for ISP18

Page 1: ...L ISP18 MODEL ISP182 WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE INJURY OR DEATH READ THE INSTALLATION OPERATING AND MAINTENANCE INSTRUCTIONS T...

Page 2: ...IMPORTANT IN THE EVENT A GAS ODOR IS DETECTED SHUT DOWN UNITS AT MAIN SHUTOFF VALVE AND CONTACT THE LOCAL GAS COMPANY OR GAS SUPPLIER FOR SERVICE FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER...

Page 3: ...nce see Page 10 UNPACKING INSTALLATION This stockpot was inspected before leaving the factory The carrier assumes full responsibility for the safe delivery upon acceptance of the shipment Check for po...

Page 4: ...STANDARDS The Stockpot Range must be installed in accordance with In the United States of America 1 State and local codes 2 National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition T his shall inclu...

Page 5: ...nd locate the leg plate to alight the four screw holes Fig 1 3 Screw legs plate with four screws on the bottom until tight Fig 2 Use a pipe or strap wrench with a towel so as not to scratch leg if nee...

Page 6: ...ositioned with the vent plug and adjustment screw upright Fig 4 Fig 3 Fig 4 The minimum supply pressure upstream of the regulator should be 7 9 W C for natural gas and 11 12 W C for propane gas At no...

Page 7: ...ropane gas is recommended With all units operating simultaneously the manifold pressure on all units should not show any appreciable drop When testing the gas supply piping system if test pressures ex...

Page 8: ...t turn main gas supply OFF and repeat steps 1 through 4 TO COMPLETELY SHUTDOWN THE BURNERS AND PILOT LIGHTS For complete shutdown Turn the main gas supply valve OFF CLEANING T op grate s may be immers...

Page 9: ...omplete listing of Service and Parts depots refer to http www blueairinc com W hen calling f or service the following information should be available from the appliance serial plate Mode l Number Seri...

Page 10: ...ow Fig 7 2 As Fig 8 show screw out the Nat gas orifice 32 3 0mm counter clockwise then screw in the LP gas orifice 43 2 3mm clockwise Fig 8 3 Change the pressure regulator spring kit to LP gas model s...

Page 11: ...recognize however that replacement parts and occasional professional service may be necessary to extend the useful life of this unit When service is needed contact a IKON Authorized Service Agency or...

Page 12: ...ONSEQUENTIAL DAMAGES TO BUYER OR ANY THIRD PARTY INCLUDING WITHOUT LIMITATION LOSS OF PROPERTY PERSONAL INJURY LOSS OF BUSINESS OR PROFITS OR OTHER ECONOMIC LOSSES OR STATUTORY OR EXEMPLARY DAMAGES WH...

Reviews: