Troubleshooting
2011-02-23
37
8 Troubleshooting
Pos: 54 /806-IHSE/Hilfe im Problemfall/Bildausfall/473-xx @ 5\mod_1278579209183_6.doc @ 42555 @ 2
8.1
Blank Screen
Diagnosis
Possible Reason
Measure
LED
Power
off
Power supply
Check power supply units and
the connection to the mains.
LED
Link
Status
off
Connection between
CON Unit and CPU Unit
Check interconnect cable and
connections.
CPU Unit: LED
Video OK
off
No video signal detected
by source (computer,
CPU)
Check DVI-D cable to CPU.
Download DDC information from
console monitor (see Chapter
6.2, Page 27).
Reboot CPU if necessary.
No monitor detected
Check connection, length and
quality of the DVI-D cable to
monitor, tighten cable
thumbscrews.
No video signal detected
from CPU Unit
Check connection, length and
quality of interconnect cable
between the units.
Download DDC information from
console monitors (see Chapter
6.2, Page 27).
Reboot CPU if necessary.
CON Unit: LED
Video OK
off
Suboptimal transmission
parameters
Execute Auto-Adjust (see
Chapter 6.1, Page 27).
If necessary, manually adjust
parameters for monitor
resolution (see Chapter 5.1.1,
Page 22) and cable length (see
Chapter 5.1.2, Page 23).