IHP Superior Fireplaces MHD40STDMN Assembly, Installation And Operation Instructions Download Page 23

Installation

900608-00  01/2019

Innovative Hearth Products
MHD40 Series Multi-View Direct-Vent Gas Fireplaces

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE

23

The unitized design of the 

Secure Vent

 compo-

nents will engage and seal both the inner and 

outer pipe elements with the same procedure.  

Sealant and securing screws are not required.

NOTE:

 An elbow may also be attached to the 

appliance collar.  Attach in the same manner as 

you would a vent section. 

E.  Attach vent components to each other -

 Other 

vent sections may be added to the previously 

installed section in accordance with the require-

ments of the vent tables.  To add another vent 

component to a length of vent run, align the 

dimpled end of the component over the inclined 

channel end of the previously installed section, 

adjusting the radial alignment until the four lock-

ing dimples are aligned with the inlets of the four 

incline channels of the previous section.  Push 

the vent component against the previous section 

until it fully engages, then twist the component 

clockwise running the dimples down and along 

the incline channels until they seat at the end of 

the channels. 

This seating position is indicated 

by the alignment of the arrow and dimple as 

shown in

 

Figure 23 

on 

Page 18.

F.

 

Install firestop/spacer at ceiling - 

When using Secure Vent, use SV4.5VF firestop/

spacer at ceiling joists; when using Secure Flex, 

use SF4.5VF firestop/spacer. If there is living 

space above the ceiling level, the firestop/ 

spacer must be installed on the bottom side of 

the ceiling. If attic space is above the ceiling, 

the attic insulation shield must be installed on 

the top side of the joist.  Route the vent sections 

through the framed opening and secure the 

firestop/spacer with 8d nails or other appropriate 

fasteners at each corner.

Remember to maintain 1" (26 mm) clearance 

to combustibles, framing members, and attic 

or ceiling insulation when running vertical 

chimney sections

.

HORIZONTAL (OUTSIDE WALL) 

TERMINATION SYSTEM

Figures 34, and Figures 43 to 48 

on 

Pages 

37-42 

and their associated  Horizontal Vent 

Table illustrate the various horizontal venting 

configurations that are possible for use with 

these appliances.  

Secure Vent

®

 pipe applica-

tions are shown in these figures; 

Secure Flex

® 

pipe may also be used. A Horizontal Vent Table 

summarizes each system’s minimum and 

maximum vertical and horizontal length values 

that can be used to design and install the vent 

components in a variety of applications.
Both of these horizontal vent systems terminate 

through an outside wall. Building Codes limit 

or prohibit terminating in specific areas. Refer 

to 

Figures 5-6

 for location guidelines.

Secure Vent

 SV4.5 direct-vent system compo-

nents are unitized concentric pipe components 

featuring positive twist lock connection, (

refer 

to 

Figure 23

 

on

 

Page 18

)

.  All of the appliances 

covered in this document are fitted with collars 

having locking inclined channels. The dimpled 

end of the vent components fit over the appliance 

collar to create the positive twist lock connection.

A.

 

Plan the vent run -

 

Analyze the vent routing and determine the 

types  and  quantities  of  sections  required       

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 

mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) net 

section lengths are available.  It is recommended 

that you plan the venting so that a joint does not 

occur in the ceiling or roof joists.  Allow for elbows 

as indicated in 

Figure 25

 

on 

Page 19

Maintain a minimum 1" (26 mm) clearance to 

combustibles on the vertical sections. Clearances 

for the horizontal runs are; 3" (77 mm) on top, 1" 

(26 mm) on sides, and 1" (26 mm) at the bottom.

B.

 

Frame exterior wall opening -

 

Locate the center of the vent outlet on the exte-

rior wall according to the dimensions shown in 

Figures 13-14 on Page 13

.  Cut and/or frame an 

opening, 10-1/2" x 12-1/8" (267 mm x 308mm) 

inside dimensions, about this center.

C.

 

Frame ceiling opening -

 If the vertical route 

is to penetrate a ceiling, use plumb line to locate 

the center above the appliance. Cut and/or frame 

an opening, 10-1/2" x 10-1/2" (267 mm x 267 

mm) inside dimensions, about this center (refer 

to 

Figure 22

 

on

 Page 18).

D. Attach vent components to appliance - 

To 

attach a vent component to the appliance collar, 

align the dimpled end over the collar, adjusting the 

radial alignment until the four locking dimples are 

aligned with the inlets of the four incline channels 

on the collar 

(refer to 

Figure 23

 on

 Page 18

).

Push the vent component against the collar until it 

fully engages, then twist the component clockwise, 

running the dimples down and along the incline 

channels until they seat at the end of the channels. 

G.

 

Support the vertical run sections - 

On the vertical run, support the venting sys-

tem every 8 feet (2.4m) above the fireplace 

vent outlet with field-provided support straps 

(Plumber's tape). 

 

Attach the straps to the vent 

pipe and secure to the framing members with 

nails or screws.

 

See 

 

Figure 24C on Page 19

.

H. Change vent direction - 

 At transition 

from or to a horizontal/inclined run, install the 

SV4.5E45 and SV4.5E90 elbows in the same 

manner as the straight vent sections.  The 

elbows feature a twist section to allow them 

to be routed about the center axis of their 

initial collar section to align with the required 

direction of the next vent run element. 

Twist 

elbow sections in a clockwise direction only 

so as to avoid the possibility of unlocking any 

of the previously connected vent sections.

 

See 

Figure 25 

on 

Page 19

.

I.

 

Continue installation of horizontal/inclined 

sections -

  Continue with the installation of the 

straight vent sections in horizontal/inclined run 

as described in 

Step E

. Install support straps 

every 5 ft. (1.52 m) along horizontal/inclined 

vent runs using conventional plumber’s tape. 

See 

Figure 34, Page 23

,

 

it is very important 

that the horizontal/inclined run be maintained 

in a straight (no dips) and recommended to 

be in a slightly elevated plane, in a direction 

away from the fireplace of 

1/4" rise per foot (20 

mm per meter) which is ideal, though rise per 

foot run ratios that are smaller are acceptable all 

the way down to at or near level.  Use a carpen-

ter’s level to measure from a constant surface 

and adjust the support straps as necessary. 

It is important to maintain the required clear-

ances to combustibles: 1" (26 mm) at all sides 

for all vertical runs; and 3" (77 mm) at the 

top, 1" (26 mm) at sides, and 1" (26 mm) at 

the bottom for all horizontal/inclined runs.

Figure 34 - TYPICAL HORIZONTAL VENT INSTALLATION

Horizontal / Inclined Run

Support

Brackets

Building

Support

Framing

SV4.5E90

Elbow

Ceiling

 Firestop / Spacer

SV4.5VF

 When Using Secure Flex, 

Use Firestop / Spacer SF4.5VF

Fireplace

SV4.5L6/12/24/36/48

Vent Sections

Vertical

Rise

SV4.5HT-2

Termination

Shown

Support Bracket Spacing

Every 5 ft (1.52 m)

Exterior

Wall

SV4.5HT-2

Termination

Shown

Shown With Optional Radiant Panels

See 

Figure 24C 

on 

Page 19 

 for 

vertical vent section support.

f i r e - p a r t s . c o m

Summary of Contents for Superior Fireplaces MHD40STDMN

Page 1: ...entretiendoivent treassur spar un installateur ou un service d entretien qualifi ou par le fournisseur de gaz INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for future refe...

Page 2: ...VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de conta...

Page 3: ...uras graves si se toca Mantenga a los ni os alejados de la chimenea en funcionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el con...

Page 4: ...5 oneventrestrictortobeappliedasshownon Page16 restrictoristapedtotheenvelope 6 barriers 7 front face assemblies 8 one fuel conversion kit Nat Gas to LP Gas locatedinthebottomcontrolcompartment NOTE I...

Page 5: ...odesor in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or the Natural Gas and Propane Instal lation Code CAN CGA B149 1 The appliance when installed mu...

Page 6: ...gas line connector used shall not exceed 36 inches 92 centimeters in length The individual manual shutoff must be a T handle type valve Massachusetts Horizontal Vent Requirements IntheCommonwealthofM...

Page 7: ...factured Home Construction and Safety Standard Title 24 CPF Part 3280 ou la norme CAN CSA Z240 S rie MM Maisons Mobiles Manufactured Home installations must be installed in accordance with these instr...

Page 8: ...nt Termination Clearances Terminatemultipleventterminationsaccordingto the installation codes listed above and Figure 3 NOTE See Figure 36 on Page 24 for the exterior wall recess allowances of the squ...

Page 9: ...de corner 6 152 mm minimum 6 152 mm minimum H Clearance to each inside of center line extended above meter regulator assembly 36 910 mm within a height of 15 ft above the meter regulator assembly 36 9...

Page 10: ...ppliance face with these exceptions they must not cover any portion of the removable glass panel or control compartment Vertical installation clearances to combustible mantels vary according to the de...

Page 11: ...loor 0 0 FromBottomof Unit To Ceiling 64 1626 Vent 3 77 Top 1 26 Sides Bottom SERVICE CLEARANCES Feet meters Front Back Sides 3 feet 0 9 meters Table 5 Figure 10 Unit Parts Identification Top View of...

Page 12: ...provided and bring in the electrical service line Step 6 Page 30 Make connection to gas supply Step7 Page31 Verifyingapplianceoperation Step 8 Page 31 Install the logs decorative volcanic stone and g...

Page 13: ...his dimension based on 5 8 drywall For 1 2 drywall use 23 Provide Additional Space For Side Vent Seal Cap If Installing Against A Solid Wall 10 1 2 12 1 8 5 1 8 Figure 14 Figure 13 FIREPLACE FRAMING S...

Page 14: ...40 1 4 1022 41 1041 37 940 34 1 8 867 23 1 2 597 27 3 4 705 23 7 8 607 41 1041 2 51 FRAMING SPACERS Top and both sides FINISHED WALL BRACKET Front and back edge of unit top Stepped to accept drywall o...

Page 15: ...p 6 on Page 30 Installingagassupplylinefromthefuelsupplyto theapplianceinvolvesnumerousconsiderations of materials protection sizing locations con trols pressure sediment andmore Certainlyno one unfam...

Page 16: ...exigences du foumisseunde gaz Use only approved venting components See Approved Vent Components on Page 4 These fireplaces must be vented directly to the outside The vent system may not service multip...

Page 17: ...1 6 0 7 5 2 3 2 5 7 3 9 1 0 0 0 0 5 5 7 3 2 5 7 9 1 1 0 0 0 5 6 5 1 4 2 5 2 1 0 2 0 0 0 7 0 7 6 4 2 5 0 2 1 0 0 7 0 8 2 5 2 1 2 0 1 0 7 0 8 4 6 2 2 2 0 0 1 7 0 8 6 7 2 3 2 0 0 0 8 0 8 9 7 2 5 2 3 2 0...

Page 18: ...onent to a length of ventrun alignthedimpledendovertheinclined channel end of the previously installed section adjusting the radial alignment until the four locking dimples are aligned with the inlets...

Page 19: ...8 feet 2 4 m Maximum 1 26 mm minimum clearance to combustibles Figure 24C Another method where the vent is not adjacent toawall isillustratedinFigure24D Here sup portstraps 96K93 andsupportplates 96K9...

Page 20: ...htheterminationdownuntilitfullyengages thentwisttheterminationclockwiserunningthe dimples down and along the incline channels until they seat at the end of the channels I Install the roof flashing Ext...

Page 21: ...1 Top Vent TWO 90 DEGREE ELBOWS 40 feet 12 2 meters Maximum uCeiling Firestop Spacer SV4 5VF uWhenusingSecureFlex use Firestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4...

Page 22: ...Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF uCeiling Firestop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF Table D H H1 Maximum V Mini...

Page 23: ...ccurintheceilingorroofjoists Allowforelbows as indicated in Figure 25 on Page 19 Maintain a minimum 1 26 mm clearance to combustiblesontheverticalsections Clearances for the horizontal runs are 3 77 m...

Page 24: ...articular range of wall thicknesses L Install Firestop Spacer at exterior wall When using the square termination install SV4 5HF Secure Vent SF4 5HF Secure Flex Firestop Spacer over the opening at the...

Page 25: ...ratios that are smaller are acceptable all the way down to at or near level NOTE SV4 5VF SecureVent SF4 5VF SecureFlex firestop spacermust be used anytime vent pipe passes through a combustible floor...

Page 26: ...quired ThisTableshowsa1 V to5 H ratio Forevery1 foot of V vertical you are allowed 5 feet of H H1 horizontal run up to a maximum horizontal run of 20 feet Table H H H1 Maximum V Minimum feet meter fee...

Page 27: ...H1 V1 v Wall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF vWall Firestop Spacer SV4 5HF Figure 41 Side Vent THREE 90 DEGREE E...

Page 28: ...he way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adaptor collar approximately 1 2 from the end 3 Pull and extend the inner flexible vent pipe 4 Slidethei...

Page 29: ...cancauseimproperanddangerous operation ATTENTION Aumomentdel entretien descommandes tiqueteztouslesfils avant de les d brancher Des erreurs de c blage peuvent entra ner un fonc tionnement inad quat et...

Page 30: ...is recommended in the gas piping within the home to prevent moisture and debris in the line from damaging the valve These appliances are equipped with a gas flex lineforuse wherepermitted inconnectin...

Page 31: ...y so that none of the wires become loose or disconnected Step 7 VERIFYING APPLIANCE OPERA TION MILLIVOLT Thermocouple Hood Igniter Rod 3 8 Min 9 mm Thermopile Pilot Nozzels Figure 50 Figure 51 Piezo I...

Page 32: ...shutter gap should be increased If air shutter is open too far Flame will be blue Air shutter gap should be decreased Sooting is caused by incomplete combustion in the flames and lack of combustion ai...

Page 33: ...e 53 2 Light appliance follow lighting procedure on lighting label in control compartment or see the Installation and Operation Manual 3 Allow the burner to operate for at least 15 minutes while obser...

Page 34: ...his Area Must Remain Clear of Combustible Materials 3 77 mm Top Spacers Header Step 11 INSTALL FRONT FACE Install front face assembly with barrier Step 12 HOOD INSTALLATION Refer to Figure 55 All of t...

Page 35: ...e fonctionnement du foyer en le faisant basculerdeMarche Arr t etvice versa Nettoyez soigneusement la plaque murale de l interrupteur ou le thermostat mural pour liminer la poussi re etlestracesdegrai...

Page 36: ...ure Vent Components Cat No Model Description H1968 SV4 5HT 2 HorizontalSquareTermina tion With Firestop spacer H2246 Adaptor 74L61 H2152 SV4 5CGV 1 Vertical Termination Cap High Wind Vent Sections Rig...

Page 37: ...52M H2248 SF4 5HF 10 Firestop Spacer Hori zontal flex 3 1 1spacing 10 Pack H2249 SF4 5VF 10 Firestop Spacer Vertical flex 1 1 1 spacing 10 Pk 56L74 SFVT30 Vertical Termination for flex flat to 6 12 wi...

Page 38: ...ly so that none of the wires become loose or disconnected d Locate the two 2 latches at the top of the control compartment To disengage the two latches from the bottom vee flange of the glass enclosur...

Page 39: ...for natural and propane models Figure 59 illustrates the orifice Always check and verify correct orifice size B Install the burner as shown in Figure 60 Ensure that the arm of the venturi of the burn...

Page 40: ...ter des br luresouqueleursv tements ne s enflamment WARNING Clothing or other flammable material should not be placed on or near the appliance AVERTISSEMENT On ne devrait pas placer de v tements ni d...

Page 41: ...y to the left away from the fireplace Refer to Figure 62 for access to the gas control valve Millivolt appliances will be fitted with the gas control valve shown in Figure 62 Familiarize yourself with...

Page 42: ...menea encendi ndola y apag ndola Limpiebienlaplacadelinterruptoro eltermostatodeparedparaquitarelpolvoyaceite Pegue la etiqueta en la superficie de la placa del interruptor que controla la chimenea Fi...

Page 43: ...aware of shrubs and plantings that may encroach on the termination The appliance and venting system should be thoroughly inspected before initial use and at least annually by a qualified service techn...

Page 44: ...oors certified with the appliance shall be used Seules des portes certifi es pour cet appareil doivent tre utilis es These are direct vent appliances They are designed to operate only when the front g...

Page 45: ...Figure 65 Do not use more than is necessary Ensure that the main burner ports remain uncovered by the ember material 5 Place Volcanic Stone Spread volcanic stone evenly over firebox floor 6 Install Ve...

Page 46: ...ard Against The Grate Here Position Log 2 Over The Grate Bar And Slide It Against The Back Of The Grate Here Position Groove At The Bottom Of Log 2 Over The Grate Here And Slide It Against The Back Of...

Page 47: ...1 3 Figure 67 3 Grate Assembly 5 Position Small End Of Log 6 On The Notch Of Log 3 Here 6 4 Position The Round End Of Log 6 Against The Notch Of Log 4 Here Two Charred Spots Face The Front Position Th...

Page 48: ...shutter opening will need to be An appliance operated with the air shutter opened too far may have flames that appear blue and transparent These weak blue and transparent flames are termed anemic Prop...

Page 49: ...parts always give the following information 1 The model number of the appliance 2 The serial number of the appliance 3 The part number 4 The description of the part 5 The quantity required 6 The inst...

Page 50: ...wall mounted or placed in the valve compartment Wall Thermostat Wall surface mounted Thermostat or manual ON OFF operation Large LCD screen to display room and set temperature in F and C Connects to...

Page 51: ...er Kits Cat No Model No Description H0778 EBLK PF MHD40PF H0779 EBLK ST MHD40ST OFF ON Wall Switch Kit TheOFF ONwallswitchkitmaybeusedtocontrolthe operation of the fireplace burner Install the OFF ON...

Page 52: ...used by long lateral runs too many elbows and or exterior portions of the systembeingexposedtocoldweather Alsoinspectwallstraps or plumbers s tape to ensure it is secure and in place Appliance Checkou...

Page 53: ...immediately call your service technician or gas supplier LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE If the pilot will not stay lit after several tries turn the gas control knob to OFF and call...

Page 54: ...imm diatement un technicien qualifi ou le fournisseur de gaz Si la veilleuse ne reste pas allum e apr s plusieurs tentatives r glez la manette d admission du gaz la position OFF et appelez un technic...

Page 55: ...shooting should only be accomplished by a qualified service technician Clean and or adjust pilot flame for maximum flame impinge ment on thermocouple Figure 50 on Page 31 Check burner orifice for stop...

Page 56: ...Face Assembly with Barrier J7531 0 1 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in proper...

Page 57: ...or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damage...

Page 58: ...Date fireplace was Installed Type of gas fireplace uses Dealer name Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices a...

Reviews: