MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-
1 «Vega»
23
9.2 Factory default
Table 2
№ Operation
mode
Description
Factory
default
Notice
1.
«Far –
near
»
Far 25 meters
Near 15 meters
Far
Switching using the service
program
2.
«Fast-slow» Fast – standard mode
Slow
– analysis of simultaneous
operation of UV and IR
channels, delay for issuing a fire
signal 5 sec
Slow
In the slow mode, high noise
immunity, response time is not
more than 30 seconds.
Switching using the service
program
3. Fire fixation
Fixing the fire mode
w/o fixation
Removing the fire mode using
the service program, removing
the power supply and a
magnetic key. Switching using
the service program
5. Failure
fixation
Fixing the failure mode, due to
the dustiness of the input
windows, an increased level of
IR or UV interference, according
to the results of self-testing.
with fixation
Removing the mode by turning
off the power or using the
service program (sequentially
turning off and then turning on
the fixation mode)
Switching using the service
program
6. Heating
Heating of the optical part of the
detector to prevent
condensation and icing.
Turned off
Heating turn-
on point +30
Switching using the service
program.
To calculate cable products,
refer to the appendix for
information on power
consumption with heating on
Relays
«Fire» and «Failure» have NC and NO contact groups. The company produces
detectors with the following relay configuration:
«Fire» relay – normally open (always open when power off, closed when power on and
fire detected)
«Failure» relay – normally open (always open when power off, closed when power on
and instrument availability)
On request, manufacturing of the detectors with normally closed contact relay
groups is possible.
«Fire» relay – normally closed (always closed when power off, open when power
on and fire detected)
«Failure» relay – normally closed (always closed when power off, open when
power on and instrument availability)