I N T E R N A L C H A N N E L S S E T T I N G S
25
MRBP.424321.001G2 Version 1.0 15/06/2020
conventional scale by two extreme points 4 and 20 mA.
It is possible to change scale value by using the buttons
and
. To copy the current
ADC code into one of scale values it is necessary to push the button
.
«
CODE 4 mA
»
- ADC value for mark 4 mA.
«CODE 20 m
A
»
- ADC value for mark 20 mA.
«
CURRENT ADC CODE
»
- channel ADC current code.
«
CURRENT, mA
»
- instantaneous channel current according to the given conventional scale
calibration.
The appearance of an asterisk in the upper line of the display - "CALIBRATION*" means that
the settings have been changed. To save the set values, it is necessary to select "SAVE". The asterisk
on the top line disappears after saving the set configuration parameters.
Notice:
While analog input calibration it is necessary to select current loop connection
method, that is used hereinafter while detector connection to the channel.
5.4
CHANNEL FACTORY DEFAULT SETTINGS
To set channel factory default it is necessary to enter
«
MENU
»
→ «
CHANNELS SETTINGS
»
→
«
INTERNAL CHANNELS
» →
«
CHAN.0
Х»
→
«
CHANNEL
FACTORY DEFAULTS
».
In the
«
CHANNEL FACTORY DEFAULTS
»
menu it is possible to set the following channel fac-
tory setting:
•
«
CONFIGURATION SETTINGS
»
- channel configuration and maintenance mode factory de-
fault;
•
«
CALIBRATION SETTINGS
»
- channel calibration factory default;
•
«
CONFIGURATION AND CALIBRATION SETTINGS
»
- channel configuration, maintenance
mode and calibration factory default.
5.4.1
«
CONFIGURATION SETTINGS
»
CH1: CHANNEL FACTORY DEFAULTS
CONFIGURATION SETTINGS
CALIBRATION SETTINGS
CONFIG. AND CALIB. SETTINGS