Diagnostics
LED Diagnostic
output
Analogue
output
normal oper-
ation
• temperature deviation between
measuring element and
reference element ≤ calibration
check limit (ccL)
• no error
green
4���20 mA
1)
warning
• temperature deviation between
measuring element and
reference element > calibration
check limit (ccL)
• failure reference element
blue
4���20 mA
1)
alarm
• failure measuring element or
failure of both sensor elements
red
21�5 mA
2)
Table 1: diagnostic function
1)
For [OU2] = Ineg: 20���4 mA
2)
For [FOU2] = OFF: 3�5 mA
Warnings are provided with a delay time of 10 minutes� Alarms are provided
immediately�
5.5 Simulation mode
Normal operation and diagnostic function (warnings and alarms) can be simulated
based on freely selected parameters using this function�
►
Set the requested duration of the simulation with [S�Tim]�
►
Set a simulation value for the measuring element or select the simulation of a
fault of the measuring element with [TEMP]�
►
Set a simulation value for the reference element or select the simulation of a
fault of the reference element with [REF_TEMP]�
►
Write values to the unit�
►
Click on [Start simulation]�
> The simulation runs for the duration set under [S�Tim]�
►
Click on [Stop simulation] to abort the simulation�