16
Explanation main menu
t�HGH
Flow adjustment to maximum value (high teach)
= 100 % flow with the operating mode REL�
t�LOW
Flow adjustment to minimum value (low teach)
= 0 % flow with the operating mode REL�
INI
Change to the Initialisation menu
ASP1
Analogue start point for temperature (OUT1)
= temperature value at which the output signal is 4 mA�
AEP1
Analogue end point for temperature (OUT1)
= temperature value at which the output signal is 20 mA�
ASP2
Analogue start point for flow (OUT2)
= flow value at which the output signal is 4 mA�
AEP2
Analogue end point for flow (OUT2)
= flow value at which the output signal is 20 mA�
EF
Extended functions� Opening of the lower menu levels�
Explanation initialisation menu (INI)
ModE
Selection of the operating mode for flow measurement: REL, LIQU, GAS�
MEdI
Medium selection: H2O, GLYC, OIL1, OIL2, AIR�
diA
Setting the internal pipe diameter in mm or inch�
CGA
Calibration of the measurement graph (gradient) in %�
Explanation extended functions (EF)
rES
Restoring the factory settings�
IO-L
Activate IO-Link communication for parameter setting�
CFG
Change to the submenu basic settings
MEM
Change to the submenu min/max memory
DIS
Change to the submenu display settings