5 Electrical connection
►
Disconnect power�
►
Connect the IO-Link device via the M12 socket to an IO-Link master�
(18…30 V DC PELV; according to DIN EN50178, secondary circuit with maximum
30 V DC).
- Tightening torque: 0�6���0�8 Nm
- Recommended maximum cable length: according to IO-Link specification 1�1�3
►
To connect the device, use M12 connectors with protection rating IP 65 / IP 66 /
IP 67 or higher�
L+
L-
IO-Link
SSC
n.c.
1 BN
2 WH
4 BK
3 BU
5 GR
Pin 2 can be programmed as an
input (reset, preset)
or
as an output (SSC1.2)
via IO-Link�
t > 50 ms
high
low
The high signal must be applied for
at least 50 ms to trigger the digital
input�The unit triggers on the falling
edge�