8.2 Explanation of the menu
8.2.1 Explanation of menu level 1
SPx/rPx Upper / lower limit value for system pressure at which OUTx switches with
hysteresis setting� SPx/rPx is displayed if the parameter [Hno] or [Hnc] for OUTx
was set in the extended functions "EF" menu�
FHx/FLx Upper / lower limit value for system pressure at which OUTx switches with
window setting� FHx/FLx is displayed if the parameter [Fno] or [Fnc] for OUTx
was set in the extended functions "EF" menu�
EF
Extended functions / opening of menu level 2�
8.2.2 Explanation of menu level 2
rES
Restore factory setting�
ou1
Output function for OUT1:
• Switching signal for the pressure limits: hysteresis function [H ��] or window
function [F ��], either normally open [� no] or normally closed [� nc]�
• Output off [OFF] (function only available in operating mode [3])�
ou2
Output function for OUT2:
• Switching signal for the pressure limits: hysteresis function [H � �] or window
function [F � �] as normally open (� no) or normally closed (� nc) each�
• Output off [OFF] (function only available in operating mode [3])�
dS1 / dS2 Switch-on delay for OUT1 or OUT2�
dr1 / dr2 Switch-off delay for OUT1 / OUT2�
uni
Standard unit of measurement for system pressure (display):
[bAr] / [mbar] / [MPA] / [kPA] / [PSI] / [inHG]�
The selectable units of measurement depend on the respective unit�
P-n
Output logic: PNP/NPN�
Lo
Minimum value memory for system pressure�
Hi
Maximum value memory for system pressure�
dAP
Damping of the measured signal�
coLr
Assignment of the display colours "red" and "green" within the measuring range�
cFH / cFL
Upper / lower value for colour change�
Parameter only active after selection of a freely definable colour window in the
coLr parameter: [r-cF] or [G-cF]�
diS
Update rate and orientation of the display�
CMPT
Selection of the operating mode