7.3.1 Scale analogue value
►
Select [ASP2] and set the value at which 4 mA is provided�
►
Select [AEP2] and set the value at which 20 mA is provided�
Minimum distance between ASP2 and AEP2 = 20 % of the measuring
span (scaling factor 5)�
[ASP2]
[AEP2]
7.3.2 Select the standard unit of measurement (option)
►
Select [uni�P] and set the unit of measurement:
5 [bAr] / [mbar] / [MPA] / [kPA] / [PSI] / [mWS] / [inH2O]
The selectable units of measurement depend on the respective
unit�
[uni]
7.4 User settings (optional)
7.4.1 Set damping for the analogue output
►
Select [dAA] and set the damping constant (rise time 10���90 %) in
seconds� Setting range: 0�000���4�000 s�
Damping [dAA] only influences the analogue output / analogue
signal path�
[dAA]
7.4.2 Set damping for the switching signal
►
Select [dAP] and set the damping constant in seconds (t value: 63 %)�
Setting range: 0�000���4�000 s�
Damping [dAP] influences the process data flow (IO-Link
communication)�
[dAP]
7.4.3 Zero-point calibration
►
Select [coF]�
Compared to the real measured value, the internal measured value
(operating value of the sensor) is shifted�
• Teach range: - 3���+ 3 % of the measuring span
[coF]
Setting to zero is made with the command “Teach COF“�[coF] is reset with
the command “Reset COF“�