7 Electrical connection
►
Disconnect power. Also disconnect any independently supplied relay load
circuits.
The nominal voltage is 24 V DC. This voltage may vary between 19.2 V and
28.8 V.
In case of a single fault the operating voltage must not exceed a maximum
of 28.8 V DC. Therefore a safe separation between current supply and
transformer is necessary.
To guarantee functional reliability an output capacity of min. 2000 µF / A has
to be ensured if a power supply with diode bridge is used.
►
Connect the units as indicated in the following tables:
7.1 Wiring diagram transmitter
Core colours
Name
Type
Description
brown
L+ (24 V DC)
Input
Operating voltage
white
Range 0
Configuration protected area width
blue
L- (0 V DC)
Operating voltage
green
Range 1
Configuration protected area width
grey
FE
Functional earth
red
24 V AC / DC
Heating 24 V AC / DC
yellow
0 V DC
Heating 0 V DC
pink
n.c.
not connected
The protected area width (range) to be used is configured via range 0 and
range 1.
Configuration protected area width (range)
Range 0
Range 1
Description
24 V
0 V
Selection range low (0...7 m)
0 V
24 V
Selection range high (3...15 m)
0 V
0 V
Transmitter in test function (→ 8.4 Test function)
24 V
24 V
No function, configuration error
For proper function of the safety light curtains the white and green cores
of the transmitter have to be connected according to the indications in the
above table.