3
UK
4 Installation
1
1: LED
►
Fit the prismatic reflector or the reflective tape behind the object to be detected.
►
Align the retro-reflective sensor to it and secure it to a bracket.
Maximum range is only possible with precise alignment.
5 Electrical connection
The unit must be connected by a qualified electrician.
►
The national and international regulations for the installation of electri-
cal equipment must be adhered to.
►
Voltage supply according to EN 50178.
►
Disconnect power.
►
Connect the unit as follows:
DC PNP
pin 1 = L+ (10...36 V DC)
pin 3 = L-
pin 4 = load (200 mA)
(pin 2 = not connected)