LW2720
Electronic level sensor
14
6 Mounting
CAUTION
With high process temperatures, parts of the unit may heat up.
w
Risk of burns
u
Do not touch the unit.
u
Protect the housing against contact with flammable substances and unintentional
contact.
u
Allow the unit and process adapter to cool down before maintenance.
Careful handling of the antenna
u
Be careful not to scratch or otherwise damage the antenna.
Before installing and removing the unit:
u
Make sure that no pressure is applied to the system. Also always take into account the
potential dangers related to extreme machine and medium temperatures.
u
Before installing the unit, observe the following mounting specifications.
6.1 Mounting position
The unit is a TLPR device. TLPR (Tank Level Probing Radar) equipment are devices for level
measurement in a closed space only (i.e. metallic, reinforced concrete or fibreglass tanks, or
similar enclosure structures made of comparable attenuating material).
u
Use preferably in metal tanks. When used in electrically non-conductive tanks: Non-metallic
u
Further requirements:
ETSI EN 302 372 (TLPR), Annex E
u
Observe the following when selecting the mounting position:
•
For optimal performance, the unit should be installed in locations with a clear and unobstructed
view of the medium surface.
•
The unit should be mounted with as few internal structures as possible within the signal beam.
•
Do not mount the unit close to or above the inlet stream (
Ò
Fig. Mounting).
•
Do not position the unit directly above a side manway door.
D
Fig. 6: Mounting
u
Distance to wall (D): D
min
= 200 mm (8 inch).
u
Recommended: ½ of tank radius.