LW2120
Electronic level sensor
20
Parameter
Options
Explanation
Access
Negative level
[Equal to zero] = negative levels (below the
zero point) are not displayed.
[Permitted] = negative levels are displayed.
If the tank offset is > 0, the level value can be
negative. This parameter defines whether nega-
tive levels are displayed or whether they should
equal zero.
With the option [Permitted], even false echoes in
the area of the (positive) tank offset are detected
that affect the measurement and lead to meas-
urement errors. With the option [Equal to zero],
these false echoes can be suppressed.
The set value is not part of the data storage. It is
not stored in the master.
P-n
[PnP] = positive switching
[nPn] = negative switching
Output polarity for the switching outputs.
ou1
[SSC1] = configures OUT1 as switching
output. OUT1 is assigned to SSC1 (switch-
ing channel 1).
[OFF] = output OFF (high impedance)*
Output configuration for OUT1.
*) This does not affect IO-Link communication.
ou2
[I] = configures OUT2 as analogue output
4...20 mA.
[SSC2] = configures OUT2 as a switching
output. OUT2 is assigned to SSC2 (switch-
ing channel 2).
[OFF] = output OFF (high impedance)
Output configuration for OUT2.
dS1
Setting range: 0...60 s
Switching delay for SSC1 (switching channel 1).
The switching delay behaves according to VD-
MA*
)
.
dr1
Setting range: 0...60 s
Switch-off delay for SSC1 (switching channel 1).
The switch-off delay behaves according to VD-
MA*
)
.
SSC1 Param. SP1
Setting range: 0.005...15 m
Set point 1 for SSC1 (switching channel 1).
Only available if SSC1 is not deactivated.
Set point 1 must be smaller than or equal to the
set tank height [Reference height].
!
SSC1 Param. SP2
Setting range: 0...14.995 m
Set point 2 for SSC1 (switching channel 1).
Only available with window function and two-
point mode.
!
SSC1 Config. Log-
ic
[no] = normally open
[nc] = normally closed
Switching logic for SSC1 (switching signal chan-
nel 1).
SSC1 Config Mode [Deactivated] = switching behaviour deacti-
vated
[single point] = hysteresis function single
point mode
[window] = window function
[two point] = hysteresis function two point
mode
Switching mode for SSC1 (switching signal chan-
nel 1).
SSC1 Config Hys-
teresis
Setting range 0...0.5 m
Switching hysteresis for SSC1 (switching chan-
nel 1).
Only available in single-point mode and with win-
dow function.
!
dS2
Setting range: 0...60 s
Switching delay for SSC2 (switching channel 2).
The switching delay behaves according to VD-
MA*
)
dr2
Setting range: 0...60 s
Switch-off delay for SSC2 (switching channel 2).
The switch-off delay behaves according to VD-
MA*
)