11
UK
OU
Configuration of the analogue output
-I = current output 4���20 mA�
-Ineg = current output 20���4 mA�
ASP
Analogue start point
Measured value at which 4 mA (20 mA if OU = Ineg) is provided.
AEP
Analogue end point
Measured value at which 20 mA (4 mA if OU = Ineg) is provided.
Minimum distance between ASP and AEP: 50°C / 90°F�
Setting range:
ASP
AEP
in steps of
°C
-25���100
40���150
0�05
°F
-13���212
104 ���302
0�1
FOU
Response of the analogue output in case of a fault
-
FOU = ON: The analogue signal goes to the value (21.1 mA).
-
FOU = OFF: The analogue signal goes to the value (3.5 mA).
dOU
Configuration of the diagnostic output
[nc]
Normally closed (DESINA characteristics, wire-break can be detected)
Nominal operation: Diagnostic output active*
Fault warning:
Diagnostic output active*
Fault alarm:
Diagnostic output inactive
[nc+]
Normally closed extended (wire-break can be detected)
Nominal operation: Diagnostic output active*
Fault warning:
Diagnostic output provides 2-Hz signal*
Fault alarm:
Diagnostic output inactive
[no+] Normally open extended
Nominal operation: Diagnostic output inactive
Fault warning:
Diagnostic output provides 2-Hz signal*
Fault alarm:
Diagnostic output active*
[Hb] Heartbeat (wire-break and short circuit on the wire of the diagnostic can
be detected)
Nominal operation:
Diagnostic output provides 4-Hz signal*
Fault warning:
Diagnostic output provides 2-Hz signal*
Fault alarm:
Diagnostic output inactive
*pnp or npn, depending on the setting of the parameter P-n
P-n
Output polarity of the diagnostic output
2 settings can be selected:
PnP = positive switching / nPn = negative switching�