44
Current consumption
< 500 mA
Function display
voltage (green), error (1 x red), output status (2 x
yellow), input (2 x yellow)
Power-on delay time
< 6 s
Duration of switch-off test pulses
≤ 500 µs
Voltage drop (per OSSD)
≤ 2.5 V @ 100 mA
Response time
[ms]
acc� to input circuit
→
chapter
8�1
8�2
8�3
8�4
8�5
Release 40 ms
160 ms
40 ms
110 ms
110 ms
Safety requirement 30 ms
100 ms
30 ms
30 ms
30 ms
Ambient temperature
-25���55 °C
Protection rating
IP 20
Housing materials
PA
Input characteristics (S34, S43)
"1": > 11 V, 6 mA
"0": < 5 V, < 500 µA
Output characteristics
S33 push-pull short-circuit proof
"0": I
sink
~ 30 mA
"1": I
source
≥ 50 mA, U > 18 V
S44 "0": I
R
≤ 300 µA
"1": I
source
≥ 50 mA, U > 18 V
Y7 "0": I
R
≤ 300 µA
"1": I
source
≥ 11 V @ 30 mA, ≥ 15 V @ 15 mA
Mission Time (TM)
175 200 h
PFH
D
2�91 x 10
-10
/ h
Comments
Additional information in the context with the cULus
approval (UL 508):
• Maximum ambient temperature 55 °C
• The safety functions are not evaluated by UL� The
approval is accomplished according to UL 508,
general use applications�
• Use 60/75 °C copper conductors only
• For use in pollution degree 2 environment
Summary of Contents for efector100 G1503S
Page 9: ...9 UK 5 2 Block diagram L L ...
Page 16: ...16 Input circuit Output status LED display L L ...
Page 17: ...17 UK Input circuit Output status LED display L L ...
Page 33: ...33 UK 8 4 2 Function Input circuit Output status LED display L L N O contact activated ...
Page 34: ...34 Input circuit Output status LED display L L N O contact activated ...
Page 35: ...35 UK Input circuit Output status LED display L N O contact activated ...
Page 40: ...40 Input circuit Output status LED display L L N O contact activated ...
Page 47: ...47 UK ...