UK
7.2 Feedback contacts / monitored or automatic start
Automatic start
Automatic activation without monitoring�
Monitoring of the feedback contacts (normally closed) for automatic start
Release is made when the feedback contacts are
closed�
Consider the current flowing through the feedback
contacts (→ 10 Technical data).
1: Feedback contact
Monitored start
Release of the solid state outputs:
►
Press and release the start button (> 50 ms)�
This function is not active when used as two-hand
control�
2: Start button
Monitoring of the feedback contacts (normally closed) for monitored start
Release of the solid state outputs:
The feedback contacts are closed
►
Press and release the start button (> 50 ms)�
This function is not active when used as two-hand
control�
Consider the current flowing through the feedback
contacts (→ 10 Technical data).
1: Feedback contact
2: Start button