background image

12

7.3  Adjustment of the valve positions of valves with 3 

operating positions

1

Press the Pos� button for at 

least 2 s�

All LEDs flash 2 x simultaneously� The unit is 

in the programming mode� Then only the LED 

"close" is lit� 

The unit is now ready for the adjustment of the 

closed position (close)�

2

Put the valve into the 

 closed position and press 

 the Teach button�

The LED "close" goes out and the LED "seat" 

lights� The unit has stored the closed position 

and is now ready for the adjustment of the 

position seat lift (seat)�

3

Put the valve into the position 

seat lift and press the Teach 

button�

The LED "seat" goes out and the LED "open" 

lights� The unit has stored the position seat 

lift and is now ready for the adjustment of the 

open position (open)�

4

Put the valve into the open 

position and press the Teach 

button�

The LED "open" goes out and the LED "close" 

lights again� The unit has now stored all 

positions�

5

Press the Pos� button for at 

least 5 s� After 5 s the LED 

"open" flashes at about 2 Hz�

After releasing all stored measured values 

are checked� If no errors are detected all 

LEDs simultaneously flash 2 x� The unit 

automatically quits the programming mode 

and immediately passes into the operating 

mode�

If, however, an error is found during the 

check the LED "close" flashes at about 8 Hz� 

Acknowledge the error message by pressing 

the Pos� button and repeat the adjustment�

Summary of Contents for Efector 180 IX5030

Page 1: ...Operating instructions Electronic rising stem valve sensor IX5030 704770 00 04 2010 UK...

Page 2: ...6 4 Installation 7 5 Electrical connection 8 5 1 Assignment of the data bits 8 6 Operation 9 7 Programming 9 7 1 Programming overview 9 7 2 Adjustment of the valve positions of valves with 2 operatin...

Page 3: ...3 UK 1 Preliminary note 1 1 Symbols used Instruction Reaction result Cross reference Important note Non compliance can result in malfunction or interference Information Supplementary note...

Page 4: ...ogrammable switch points can be freely selected in the measuring range The position is signalled visually by 3 LEDs sensor valve spindle with target adapter fixture actuator of the valve position butt...

Page 5: ...mm height at least 10 mm The end surface must be flat Material stainless steel to DIN 17440 material number 316L 1 4404 2 1 Permissible shapes and dimensions of the target 24mm 10mm 24mm 10mm 10mm 24...

Page 6: ...ng reading the valve positions The taught valve positions are automatically assigned certain switching characteristics of the three outputs several operating modes are available see chapters Programmi...

Page 7: ...fixture adapter 3 Fix the sensor to the 3 hole flange 3 by means of the included fixing screws 6 The sensor 1 must either be integrated into a valve top or correctly fitted to the actuator 4 by means...

Page 8: ...de of plastic A metallic objects x min 10 mm y min 46 5 mm 5 Electrical connection The unit must be connected by a qualified electrician The national and international regulations for the installation...

Page 9: ...with a blunt object Sharp edges may damage the buttons open close Power fault seat 7 Programming 7 1 Programming overview P 2s P P P T T T P 5s Run mode P actuate Pos button T actuate Teach button Te...

Page 10: ...rview 7 1 After entering into the programming mode Teach mode the unit first expects the adjustment of the closed position close However you can also start with any other position If e g the valve is...

Page 11: ...step This is necessary because your valve does not have the position seat lift The LED open lights The unit is now ready for the adjustment of the open position 4 Put the valve into the open position...

Page 12: ...utton The LED seat goes out and the LED open lights The unit has stored the position seat lift and is now ready for the adjustment of the open position open 4 Put the valve into the open position and...

Page 13: ...tly If possible put the valve into all available positions and check whether the unit switches correctly and whether the operations are correctly indicated by the LEDs 8 1 Indication by LED for the di...

Page 14: ...hatched diagonally all outputs are open not switched All modes are also possible in inverted form i e the open and closed positions can be inverted The sensor detects this automatically the assignmen...

Page 15: ...close Flashes at 8 Hz directly after leaving the programming mode adjustment error Taught position values are not within the detection range or positions are not allowed or plausible Acknowledge the e...

Page 16: ...4 8 38 6 2 4 5 26 5 15 5 3 88 6 52 4 4 3 Max spindle stroke Measuring distance Initial value of the measuring range zero point Programming buttons Pos Teach LED green open LED red close LED green AS i...

Page 17: ...17 UK...

Reviews: