![IFM Efector 180 IX5030 Operating Instructions Manual Download Page 11](http://html1.mh-extra.com/html/ifm/efector-180-ix5030/efector-180-ix5030_operating-instructions-manual_3873892011.webp)
11
UK
7.2 Adjustment of the valve positions of valves with 2
operating positions
1
Press the Pos� button for at
least 2 s�
All LEDs flash 2 x simultaneously� The unit is
in the programming mode� Then only the LED
"close" is lit�
The unit is now ready for the adjustment of the
closed position (close)�
2
Put the valve into the
closed position and press the
Teach button�
The LED "close" goes out and the LED "seat"
lights� The unit has stored the closed position
and is now ready for the adjustment of the
position seat lift (seat)�
3
Press the Pos� button once,
thus skipping the current
programming step� This is
necessary because your
valve does not have the
position seat lift�
The LED "open" lights� The unit is now ready
for the adjustment of the open position�
4
Put the valve into the open
position and press the Teach
button�
The LED "open" goes out and the LED "close"
lights again� The unit has now stored all
positions�
5
Press the Pos� button for at
least 5 s� After 5 s the LED
"open" flashes at about 2 Hz�
After releasing all stored measured values
are checked� If no errors are detected all
LEDs simultaneously flash 2 x� The unit
automatically quits the programming mode
and immediately passes into the operating
mode�
If, however, an error is found during the
check the LED "close" flashes at about 8 Hz�
Acknowledge the error message by pressing
the Pos� button and repeat the adjustment�