![IFM Efector 180 IX5030 Operating Instructions Manual Download Page 10](http://html1.mh-extra.com/html/ifm/efector-180-ix5030/efector-180-ix5030_operating-instructions-manual_3873892010.webp)
10
After installation you have to adjust the unit to the valve positions to be detected�
You can carry out the adjustment process in a variable and time-saving way� First
clarify which type of valve you have� The sensor differentiates between two types:
1� Valves with 2 operating positions (closed and open)
2� Valves with 3 operating positions (closed, open and a position inbetween for
the seat lift)
For valves with 2 operating positions the wear of the valve seals is monitored
automatically� This function is not possible for the detection of three operating
positions�
The programming options are shown in the programming overview ( → 7�1) After
entering into the programming mode (Teach mode) the unit first expects the
adjustment of the closed position (close)�
However, you can also start with any other position�
If e�g� the valve is already in the open position (open), just start adjusting this
position� To do so, press the Pos� button 2 x, thus skipping the adjustment of the
closed and the seat position� You can carry out the skipped adjustment steps
afterwards�
Skipping a current programming step is also required for example if you use
valves with only 2 operating positions for which the position of the seat lift is not
available� If the position seat lift is not adjusted ("taught") the unit automatically
passes into an operating mode which monitors the wear of the valve seals (see
also chapter Set-up / operation)�
The unit cannot be taught via the AS-i bus�