36
Setting ranges
13.1
[LEnG]
cm
inch
Setting range
10���160
4�0���63
Step increment
0�5
0�2
[OFS]
cm
inch
Setting range
0���100
0���39�4
Step increment
0�5
0�2
The setting ranges for the switching limits (SP1, rP1, FH1, FL1) depend on the
probe length (L)� In general the following applies:
cm
inch
min
max
min
max
SP1 / FH1x
1�5 (3�5)
L - 3
0�6 (1�4)
L - 1�2
rP1 / FL1
1�0 (3�0)
L - 3�5
0�4 (1�2)
L - 1�4
Step increment
0�5
0�2
The values apply if [OFS] = 0� The values in brackets apply to the setting [MEdI] = [LOW]
(setting for the detection of oils and oil-based media)�
rP1 (FL1) is always smaller than SP1 (FH1)� If the value for SP1 (FH1) is reduced to a
•
value ≤ rP1 (FL1), the position of rP1 (FL1) also shifts.
If rP1 (FL1) and SP1 (FH1) are close together (approx� 3 x step increment), rP1 (FL1) is
•
changed automatically when SP1 (FH1) is increased�
If there is a greater distance between rP1 (FL1) and SP1 (FH1), rP1 (FL1) maintains the
•
set value even if SP1 (FH1) is increased�
The setting ranges for the analogue start point (ASP) and the analogue end point
(AEP) depend on the probe length (L)� In general the following applies:
cm
inch
min
max
min
max
ASP
1�0
---
0�4
---
AEP
---
L - 3�0
---
L - 1�2
Step increment
0�5
0�2
Minimum distance between [ASP] and [AEP] = 25 % of the active zone��