ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
Function
The fieldbus modules
63
5.3.14
Module 12 – fieldbus data PLC input
10585
Data content
10648
Up to 128 bytes of freely definable data
Direction of data
10595
C
F
Data from the fieldbus interface to the controllerE
Module settings
10649
Value range = 0...128 [bytes]
0
module is deactivated
1...128
module is activated (details
data interpretation)
Data interpretation
10650
Module 12 contains the input data from the controller PLC's point of view, i.e. data which are for
example sent by a higher-level PLC to the controller.
These data can be accessed via the PLC application program of the controller.
Access in the application program is carried out via the variables
-
PLC_Input[0]
to
-
PLC_Input[127]
.
In case of double word representation in the host PLC the following allocation of the individual bytes
results: