E84036 Installation Manual 

 

 

 

 

Product Description 

The E84036 is a DIN-rail mountable power supply for three-phase mains systems, which provides a 
floating, stabilized and galvanically separated SELV/PELV output voltage. 
 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring, measurement equipment or the like. 
Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life without additional appropriate safety devices, that are suited for the end-
application. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Use ferrules for wires on the 
input terminals. Unused screw terminals should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide 
protection against spilled liquids. 
The device is designed for overvoltage category II zones. Below 2000m altitude the device is tested 
for impulse withstand voltages up to 4kV, which corresponds to OVC III according to IEC 60664-1. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage 
between the input terminals and the PE potential must not exceed 576Vac. The device is not designed 
to be used on corner grounded delta systems. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A 
B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 

 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive or capacitive loads. 
Do not apply return voltages from the load to the output terminals higher than 35V. 
The output voltage can be adjusted with a small flat-blade screwdriver behind the flap on the front. 
The green DC OK LED reports an output voltage above 90% of the adjusted voltage of a running 
device. 
The DC OK relay monitors the output voltage and the contact is closed when the DC OK LED is on. 
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 
The red overload LED is on when the output voltage falls below 90% of the adjusted value

 

or in case 

of a short circuit in the output. The LED is flashing, when the device has switched off due to over-
temperature or when the “Remote OFF” signal is activated. Input voltage is required. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to 
60°C. The output voltage of all devices shall be adjusted to the same value (±100mV) in 
“Single Use” mode with the same load conditions on all units, or the units can be left with the factory 
settings. After the adjustments, set the unit to “Parallel Use” mode, in order to achieve load sharing. 
The “Parallel Use” mode regulates the output voltage in such a manner that the voltage at no load is 
approx. 4% higher than at nominal load. If more than three devices are connected in parallel, a diode, 
fuse or circuit breaker with a rating of 50 or 63A is required on each output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32V. The output 
shuts down and automatically attempts to restart. 
The device is equipped with a remote ON/OFF function to turn the output off. For this connect pin 15 
with pin 16. 
The output voltage can be remotely adjusted between 14 and 28Vdc by applying a control voltage 
between pin 15 and the (-) terminal. 

 

Technical Data

 

All values are typical figures specified at 3x 400Vac 50Hz input voltage, 
symmetrical phase voltages, 24V, 40A output load, 25°C ambient 
temperature and after a 5 minutes run-in time unless otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 – 28Vdc 

Factory setting 24.1V 

Output current 

Continuous: 

 

40 – 34.3A 

Below +60°C ambient 

 

30 – 25.7A 

At +70°C ambient 

 

Short-term, up to 4s: 

 

60 – 51.5A 

Below +70°C ambient 

 

Derate linearly b60°C and +70°C 

Input voltage AC 

3AC 380 - 480V 

-15% / +20% 

Mains frequency 

50 – 60Hz 

±6% 

Input current AC 

1.65 / 1.35A 

At 3x400 / 480Vac 

Power factor 

0.88 / 0.90 

At 3x400 / 480Vac 

Input inrush current 

4.5 / 4.5A peak 

At 3x400 / 480Vac, 
temp. independent 

Efficiency 

95.3 / 95.2% 

At 3x400 / 480Vac 

Losses 

47.3 / 48.4W 

At 3x400 / 480Vac 

Hold-up time 

25 / 25ms 

At 3x400 / 480Vac 

Temperature range 

-25 to +70°C 

 

Max. wire size (litz wire) 

4mm² 

For input terminals 

Wire size AWG 

AWG 20-10 

For input terminals 

Max. wire diameter 

2.8mm 

For input terminals 

Wire stripping length 

7mm / 0.28inch 

For input terminals 

Tightening torque 

1Nm / 9lb.inch 

For input terminals 

Max. wire size (litz wire) 

10mm² 

For output terminals 

Wire size AWG 

AWG 22-8 

For output terminals 

Max. wire diameter 

5.2mm 

For output terminals 

Wire stripping length 

12mm / 0.5inch 

For output terminals 

Tightening torque 

2.3Nm / 20lb.inch  For output terminals 

Max. wire size (litz wire) 

1.5mm² 

For signal terminals 

Wire size AWG 

AWG 26-14 

For signal terminals 

Max. wire diameter 

1.5mm 

For signal terminals 

Wire stripping length 

7mm / 0.28inch 

For signal terminals 

Size 

(wxhxd)

 

110x124x127mm  Without DIN-rail 

Weight 

1500g / 3.3lb 

 

 

Functional Diagram 

L2
L3

L1

+

+

-

-

Output

Over-

Voltage

Protection

PFC

Converter

Power

Converter

Output

Filter

Output

Power

Manager

Temper-

ature

Shut-

down

Input Fuse
Input Filter
Input Rectifier
Inrush Current
Limiter

DC-OK

LED

Remote ON/OFF

Voltage control

ON/

OFF

15
16

Overload

LED

DC-OK

Contact

DC-ok

Relay

13
14

V

OUT

Output

Voltage

Regulator

Single /

Parallel

Event Datalogger

 

 

Output Characteristic 

Output voltage in single mode

70A

24V

Output current

12V

0V

10A

30A

40A

50A

0A

Adjustment range

28V

20A

60A

B

A

A: continuous

B: for 4s

 

 

Temperature Range 

Allowed output current at 24V

Ambient temperature

0A

-25

A: continuous

B: short term (typ. 4s)

60A

0

+70°C

30A

B

40A

+60

A

 

 