background image

 

 

 

 

 

 

 

 

 
 
 
 
 

Programming instructions  

IO-Link Display 1,44” 

    E30391 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

  

  

Summary of Contents for E30391

Page 1: ...Programming instructions IO Link Display 1 44 E30391 ...

Page 2: ...f process values 9 3 6 Predefined text instead of process values 11 3 7 Display configuration 13 3 8 QR code 13 4 IO Link process data cyclic communication 14 4 1 Output data 14 4 2 Input data 16 4 3 Examples 17 4 3 1 Example 1 display one process value 17 4 3 2 Example 2 display two process values 18 4 3 3 Example 3 display text instead of process values 19 4 3 4 Example 4 display info pages 19 4...

Page 3: ...ease read see the operating instructions www ifm com 2 Set up When the IO Link Display is connected to an IO Link master the IO Link port has to be configured In this example the IO Link master AL1000 from ifm electronic is used with the Siemens software Step 7 The IO Link Display has an interface with 1 byte input 4 2 Input data and 14 byte output 4 1 Output data ...

Page 4: ...o use an existing module with a wider interface 1 Drag for example a 24 24 byte I O module to the master port to which the IO Link Display is to be connected 2 Double click on the module 3 Enter name and comment as an option 4 Enter addresses for input and output ranges ...

Page 5: ...e entered by means of the IO Link parameter setting tool or a PLC by writing the corresponding parameters The LINERECORDER DEVICE can for example be used as IODD based parameter setting tool 3 1 It is possible to configure the following properties Process value display unit description text decimal places 3 2 Text content for info pages 3 3 Background colour of the info page 3 4 Text instead of pr...

Page 6: ... Connect the IO Link Display via the USB interface E30390 Start the LINERECORDER DEVICE Read parameters from the IO Link Display Change parameters Write parameters to the IO Link Display The IO Link Display can now be connected to the IO Link master ...

Page 7: ...ecimal place 1 1 decimal place 2 2 decimal places 3 3 decimal places Decimal place 2 101 0 Decimal place 3 102 0 Decimal place 4 103 0 3 3 Text content for info pages Up to 16 characters per line can be used Name Index subindex Type length Content Info page 1 line 1 120 0 String 16 Text content of page 1 Info page 1 line 2 121 0 Info page 1 line 3 122 0 Info page 1 line 4 123 0 Info page 1 line 5 ...

Page 8: ...e 5 Info page 5 line 2 12101 0 Info page 5 line 3 12102 0 Info page 5 line 4 12103 0 Info page 5 line 5 12104 0 Info page 6 line 1 12105 0 String 16 Text content of page 6 Info page 6 line 2 12106 0 Info page 6 line 3 12107 0 Info page 6 line 4 12108 0 Info page 6 line 5 12109 0 Info page 7 line 1 12110 0 String 16 Text content of page 7 Info page 7 line 2 12111 0 Info page 7 line 3 12112 0 Info p...

Page 9: ...d colour of the info pages Name Index subind ex Type length Content Background colour info page 1 140 0 INT8 1 Page colour 0 black white 1 red 2 green 3 yellow Background colour info page 2 141 0 Background colour info page 3 142 0 Background colour info page 4 143 0 Background colour info page 5 144 0 Background colour info page 6 145 0 Background colour info page 7 146 0 Background colour info p...

Page 10: ...0 Text 6 166 0 Text 7 167 0 Text 8 168 0 Text 9 169 0 Text 10 170 0 Text 11 171 0 Text 12 172 0 Text 13 173 0 Text 14 174 0 Text 15 175 0 Text 16 176 0 Text 17 177 0 Text 18 178 0 Text 19 179 0 Text 20 180 0 Text 21 181 0 Text 22 182 0 Text 23 183 0 Text 24 184 0 Text 25 185 0 Text 26 186 0 Text 27 187 0 Text 28 188 0 Text 29 189 0 Text 30 190 0 Text 31 191 0 Text 32 192 0 ...

Page 11: ... 16 m 1012 0 String 16 cm 1013 0 String 16 mm 1019 0 String 16 in 1034 0 String 16 m 1038 0 String 16 l 1040 0 String 16 ml 1048 0 String 16 gal 1053 0 String 16 ft std 1054 0 String 16 s 1056 0 String 16 ms 1058 0 String 16 min 1061 0 String 16 m s 1062 0 String 16 mm s 1067 0 String 16 ft s 1076 0 String 16 m s 1077 0 String 16 Hz 1081 0 String 16 kHz 1082 0 String 16 1 s 1083 0 String 16 1 min ...

Page 12: ... mA 1212 0 String 16 µA 1240 0 String 16 V 1243 0 String 16 mV 1342 0 String 16 1348 0 String 16 m min 1349 0 String 16 m h 1352 0 String 16 l min 1353 0 String 16 l h 1357 0 String 16 ft min 1358 0 String 16 ft h 1360 0 String 16 ft min std 1361 0 String 16 ft h std 1363 0 String 16 gal min 1364 0 String 16 gal h 1563 0 String 16 ml min 1573 0 String 16 Nm 1574 0 String 16 Nl 1589 0 String 16 Nm ...

Page 13: ... Setting values 0 90 180 270 diS B 802 0 Brightness of the display 0 25 50 75 100 diS S 803 0 Colour scheme of the display 0 black background 1 white background 3 8 QR code To display the content defined in this index as QR code on the screen set the layout type of the display to QR Code 4 1 Name Index subindex Type length Content QR code 830 0 String 122 URL or short free text ...

Page 14: ...process values in the output data stream and controls the display of the process values It is defined in the layout byte which layout is to be displayed e g 1 large process value or an info page INT16 INT16 INT16 INT16 INT8 INT8 INT8 INT8 INT8 INT8 Name Byte offset Type length Note content PDV1 value line 1 0 0 INT16 2 Process value x or text saved instead of the process value 3 5 3 5 PDV2 value l...

Page 15: ...e 81 text red 82 text green 83 text yellow Colour of the flashing process value 40 black white 41 red 42 green 43 yellow Colour of the flashing display text 120 text black and white 121 text red 122 text green 123 text yellow Color2 Display line 2 9 0 Color3 Display line 3 10 0 Color1 Display line 4 11 0 LEDs 12 0 Bool 1 bit 0 LED I off 1 LED I yellow 12 1 Bool 1 bit reserved 12 2 Bool 1 bit 0 LED...

Page 16: ...4 15 Display info page 5 16 Display info page 6 17 Display info page 7 18 Display info page 8 19 Display info page 9 20 Display info page 10 21 display of the QR code 4 2 Input data Bit 7 6 5 4 3 2 1 0 Function PDout inv Content inv Reserved ESC Enter Up Down If a key is pressed the corresponding flag is active During the runtime the following input data is available as INT8 value Address bit Func...

Page 17: ...ceived output data 9 1 Output data had already been marked as invalid by the transmitter 4 3 Examples 4 3 1 Example 1 display one process value 1 Define unit description text and number of decimal places index 80 90 and 100 3 2 2 In the output data stream set the layout to 1 byte 13 4 1 3 As an option define a text colour byte 8 4 1 4 Write the display value as Integer16 starting at byte 0 in the ...

Page 18: ...description text and number of decimal places index 80 90 and 100 3 2 2 In the output data stream set the layout to 2 byte 13 4 1 3 As an option define the text colours byte 8 4 1 4 Write both display values as Integer16 starting at byte 0 in the output data 4 1 ...

Page 19: ...ue by setting text red or text black and white At the same time this defines a text colour bytes 8 to 11 4 1 4 3 4 Example 4 display info pages 1 Define text of info page 1 Up to 16 characters per line can be used index 120 to 124 3 3 2 As an option select a background colour index 140 3 4 3 During the runtime set the layout to 11 to display info page 1 byte 13 4 1 ...

Page 20: ...ification data of the IO Link device Name Index subind ex Type length Content Vendor name 16 0 String 19 ifm electronic gmbh Vendor text 17 0 String 11 www ifm com Product name 18 0 String 9 E30391_AB Product ID 19 0 String 6 E30391 Product text 20 0 String 15 IO Link Display Serial number 21 0 String 12 Unique device identification Hardware version 22 0 String 2 Hardware version Software Version ...

Reviews: